ECB violations
1930 Webster Avenue, Bronx • Block 03027 • Lot 0010
33 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Feb 8, 2024 | 39105659M | RESOLVE | CLASS - 1 | OBSERVED ON THE OUTSIDE OF THE BUILDING GOING FROM THE GROUND FLOOR TO THE BASEMENT RUSTED A CORRODED METAL STEP. THI... | $1,250 | $0 | May 17, 2024 |
| Aug 1, 2022 | 39067057K | RESOLVE | CLASS - 2 | I OBSERVED ON THE ROOF LEVEL THE IMPROPER INSTALLATION OF A LIGHT FIXTURE WITH IT BEING USED AS A RACEWAY. THE RACEWA... | $0 | $0 | Nov 4, 2022 |
| Aug 1, 2022 | 39067058M | RESOLVE | CLASS - 2 | I OBSERVED IN THE COOLING ROOM AND IN THE SIDE COURTYARD OPEN JUNCTION BOXES WITH EXPOSED CONDUCTORS. ALSO NOTED IN T... | $0 | $0 | Nov 4, 2022 |
| Aug 1, 2022 | 39067053N | RESOLVE | CLASS - 2 | AT ROOF LEVEL, EXPOSURE # 4, PARAPET WALL/CHIMNEY IS LEANING, APPROXIMATE LENGTH 50FT., MAINTAIN EXTERIOR BUILDING WALL | $0 | $0 | Nov 4, 2022 |
| Jun 9, 2022 | 39063779Y | RESOLVE | CLASS - 2 | AT CELLAR LEVEL ,EMERGENCY LIGHTS/EXIT SIGNS ARE REQUIRED, INDICATING THE EVACUATION PATH. ALSO, THERE IS NO BACKUP P... | $0 | $0 | Jul 29, 2022 |
| May 20, 2021 | 35553811L | RESOLVE | CLASS - 1 | ALTERED/CHANGED BLDG OCCUPIED W/O VALID C/O AS PER 28-118.3.1-28-118.3.2.NOTED:DURING INSP OBSERVED@EXP1-CELLAR LEVEL... | $6,250 | $0 | Aug 6, 2021 |
| Mar 31, 2021 | 35378321N | RESOLVE | CLASS - 1 | ALTERED/CHANGED BUILDING OCCUPIED W/O A VALID C OF O AS PER 28-118.3.1-28-118.3.2. AT TIME OF INSPECTION RIGHT SIDE O... | $2,500 | $0 | Jul 16, 2021 |
| Apr 15, 2019 | 35422402K | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE EFFECTIVE ELECTRICAL CONTINUITY FOR METAL RACEWAYS.OBSERVED CONDUIT FOR GROUND ELECTRODE CONDUCTOR... | $600 | $0 | Jun 21, 2019 |
| Apr 15, 2019 | 35422401Z | RESOLVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS DEVICES,APPLIANCES OR WIRING IN USE. OBSERVED I... | $0 | $0 | Jun 21, 2019 |
| Apr 15, 2019 | 35415196N | RESOLVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS DEVICES,APPLIANCES OR WIRING IN USE. OBSERVED I... | $0 | $0 | May 31, 2019 |
| Oct 15, 2018 | 35361590K | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. LIGHT FIXTURES IN GAS METER ROOM ARE NOT WORKING. RMDY: REPAIR... | $0 | $0 | Nov 30, 2018 |
| Sep 20, 2017 | 35290916X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 9/20/17@ ABOVE ADDRESS NO BALL DRIP FOUND AFTER THE 1S... | $0 | $0 | Feb 9, 2018 |
| Sep 20, 2017 | 35290915Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLAINT MANNER. OBSERVED ON (BD) 9/20/17 @ ABOVE ADDRESS JIM CAPS INSTALLED THROUG... | $0 | $0 | Nov 17, 2017 |
| Aug 16, 2017 | 35277014K | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUM/VIO#35271675K ISSUED ON 06/23/17 & TO FILE A C OF C PURSUANT TO... | $400 | $0 | Nov 6, 2017 |
| Jun 23, 2017 | 35271675K | RESOLVE | CLASS - 2 | FAILURE TO MAITNAIN BLDG IN CODE COMPLAINT MANNER. NOTED: IN A GAS METER ROOM IN CELLAR LEVEL. EXCESSIVE STORAGE CONT... | $250 | $0 | Sep 1, 2017 |
| Apr 27, 2017 | 35253286H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED IN A GAS METER ROOM IN CELLAR EXCESSIVE STORAGE CONTRARY ... | $250 | $0 | Jun 30, 2017 |
| Apr 27, 2017 | 35253343P | RESOLVE | CLASS - 1 | ELECTRICAL W/O A PERMIT. AT THE TIME OF INSPECTION I OBSERVED PERIMETER LED LIGHTS & CONDUITS NEWLY INSTALLED. RECEPT... | $1,600 | $0 | Jul 7, 2017 |
| Apr 27, 2017 | 35253287J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: FAILURE TO COMPLY W/THE LAW FOR WATER SUPPLY SYSTEM PER PC 602.3;2... | $250 | $0 | Jul 7, 2017 |
| Apr 27, 2017 | 35253342N | RESOLVE | CLASS - 2 | FAILURE TO GROUND ELECTRICAL SYSTEMS. AT THE TIME OF MY INSPECTION. I OBSERVED NO BLDG GROUND CONDUCTION FROM WATER M... | $2,400 | $0 | Jul 7, 2017 |
| Apr 27, 2017 | 35252984K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3; 27-345. NOTED: FIRE STOPPING MISSIN... | $0 | $0 | Jun 16, 2017 |
| Apr 27, 2017 | 35253285X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. LACK OF A SYSTEM OFAUTOMATIC SPRINKLERS WHERE REQUIRED PER BC 903.... | $500 | $0 | Jun 30, 2017 |
| Apr 27, 2017 | 35253288L | RESOLVE | CLASS - 1 | SEC. 411.1 MISC VIOLATION: RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT. OBSERVED IN LAUNDRY ROOM ON 1ST FL 2 GA... | $1,600 | $0 | Jul 7, 2017 |
| Dec 2, 2016 | 35221120L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3;27-345. NOTED: CELLAR LEVEL,CEILIN... | $250 | $0 | Mar 3, 2017 |
| Dec 2, 2016 | 35235126J | RESOLVE | CLASS - 2 | FGC408.2. MISC. VIO. DRIPS-FUTURE CONNECTS EXIT DOWN STACAM OF APPLIANCE. OBSERVED ON 12/02/16 FUTURE GAS CONNECTION ... | $800 | $0 | Jun 30, 2017 |
| Jun 8, 2016 | 35195362H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALL(S)OR APPURTENANCES.DEFECTS NOTED 1 FRONTRIGHT SIDE EXTERIOR(FACADE)WALL HAVE STEP CRACK... | $1,250 | $0 | Jul 29, 2016 |
| Jun 8, 2016 | 35195360Y | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING DEFECTS NOTED:EXIT DOOR NOT SELF CLOSING@2ND FLR THROUGH 5TH FLR(S)&EXIT TO LEFT SIDE COUR... | $2,500 | $0 | Jul 29, 2016 |
| Jun 8, 2016 | 35195361X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.DEFECT NOTED:MISSINGCEILING TILES @VARIOUS LOCATIONS IN CELLAR. | $2,500 | $0 | Jul 29, 2016 |
| Apr 25, 2003 | 34382153Z | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT. NOTED- RENOVATION WORK BEING DONE ON 1ST FLOOR REAR APT OF 5 STORY HOTEL. FLOOR JOISTS SUPPORT... | $0 | $0 | Jun 27, 2003 |
| Apr 8, 2003 | 34386404M | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE ALL REQUIRED INFORMATION TO DEMONSTRATE COMPLIANCE WITH ALL APPLICABLE LAWS FOR RELATED APPLICATIO... | $0 | $0 | May 23, 2003 |
| Sep 21, 2000 | 34261420N | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL.UPON INSPECTION AT ABOVE ADDRESS ON THE 5TH FLOOR NUMEROUS BRICKS MISSING ... | $180 | -$180 | Jan 19, 2001 |
| Feb 25, 2000 | 34155563L | RESOLVE | Non-Hazardous | OCCUPANCY CONTRARY TO THAT ALLOWED BY CERTIFICATE OF OCCUPANCY #62287 STATES JANITORS CLASS "A"APT.NOW OCCUPIED WITH ... | $0 | $0 | Apr 14, 2000 |
| Jan 13, 2000 | 34155374M | RESOLVE | Non-Hazardous | OCCUPANCY CONTRARY TO THAT ALLOWED BY CERTIFICATE OF OCCUPANCY.#62287, STATES JANITORS CLASS "A" APT. NOW OCCUPPIED W... | $1,000 | $0 | Mar 24, 2000 |
| Sep 30, 1999 | 34155370P | RESOLVE | Non-Hazardous | OCCUPANCY CONTRARY TO THAT ALLOWED BY CERTIFICATE OF OCCUPANCY #62287 STATES JANITOR'S CLASS A APT NOW OCCUPIED WITH ... | $400 | $0 | Nov 12, 1999 |