ECB violations

East 179 Street, Bronx • Block 03028 • Lot 0027

40 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Feb 5, 2026 39176213X RESOLVE CLASS - 2 OBSERVED IN THE BASEMENT PVC PIPING INSTALLED UNDER THE SINK. THE GAS SHUT OFF VALVE IS OBSTRUCTED BY SHEETROCK. AN O... $3,125 $3,125 Apr 17, 2026
Feb 5, 2026 39176124Y ACTIVE CLASS - 2 FOUND ROCKMILLS MP-40 OIL FIRED BOILER WITH EXPOSED WIRING, OPENINGS ON CEIL AND WALLS, BOILER ROOM DOOR NOT SELF CLO... $6,250 $6,250 Apr 17, 2026
Jan 29, 2025 39136819Y RESOLVE CLASS - 2 CARLIN BURNER 702CRD OPERATING ON LOW FIRED ONLY AND SERVICE IS REQUIRED. CORRECT VIOLATING CONDITION & SUBMIT CERTIF... $312 $312 Feb 9, 2026
Feb 9, 2024 39105716J RESOLVE CLASS - 2 OBSERVED EXCESSIVE CARBONIZE BUILD UP IN THE BOILER ROOM AND ALSO ON THE BOILER. AS PER PC 102.3MAINTENANCE. INSTALLA... $0 $0 Apr 19, 2024
Jan 19, 2024 39103824H RESOLVE CLASS - 2 FACILITATING UNLICENSES ELECTRICAL WORK DUE TO ELECTRICAL WORK PERFORMED IN CELLAR/BASEMENT., OBTAIN PERMIT $0 $0 Aug 5, 2024
Jan 19, 2024 39103820K RESOLVE CLASS - 1 FOUND THE MAINTAINCE STAFF INSTALLING AND WIRING A LIGHT FIXTURE, WITHOUT PERMIT, CELLAR LEVEL MAINTAINCE OFFICE., OB... $2,500 $0 Aug 5, 2024
Jan 19, 2024 39103825J RESOLVE CLASS - 2 OPEN HOLES FOUND IN CEILING OF CRAWL SPACE IN BOILER MECHANICAL ROOM, CELLAR LEVEL., REPAIR AND/OR REPLACE $0 $0 Mar 29, 2024
Jan 19, 2024 39103822Y RESOLVE CLASS - 2 EMERGENCY LIGHTS DO NOT FUNCTION, (TURN ON) 3RD & GROUND FLOOR., REPAIR/REPLACE LIGHTING $0 $0 Mar 29, 2024
Jan 19, 2024 39103823X RESOLVE CLASS - 1 IMPROPER AND UNSAFE STORAGE OF GAS CONBUSTIBLE POWERED MACHINERY IN BOILER MECHANICAL ROOM, CELLAR LEVEL. STORAGE OF ... $2,500 $0 Aug 5, 2024
Jan 19, 2024 39103821M RESOLVE CLASS - 2 ROOF SELF-CLOSING DOOR DOES NOT CLOSE AND LATCH., REPAIR AND/OR REPLACE $0 $0 Mar 29, 2024
Aug 4, 2022 39067397R RESOLVE CLASS - 2 AT CELLAR LEVEL, ELECTRICAL ROOM, FOUNDATION WALLS,SHOWS SIGNS OF WATER PENETRATION THROUGH WALLS AND CEILING, MAINTA... $0 $0 Sep 30, 2022
Aug 4, 2022 39067396P RESOLVE CLASS - 2 -FOUR-STORY BUILDING, CRACKED FACADES, PEELING PAINT OR WATERPROOFING MATERIAL AND LOSS OF MORTAR., MAINTAIN EXTERIOR... $620 $620 Sep 30, 2022
Aug 4, 2022 39067398Z ACTIVE CLASS - 2 AT CELLAR LEVEL, GAS/BOILER & STORAGE ROOMS, SLAB / CEILING ARE BEING SUPPORTED BY SECTIONS OF METAL BEAMS AND TUBULA... $1,250 $0 Jan 27, 2023
Aug 4, 2022 39067395N RESOLVE CLASS - 2 AT CELLAR LEVEL, GAS/ STORAGE & BOILER ROOMS, SLAB / CEILING SHOWS DEFLECTION IN SEVERAL AREAS AND ARE BEING SUPPORTE... $0 $0 Sep 30, 2022
Sep 20, 2021 39047767R RESOLVE CLASS - 2 FOUND EXPOSED WIRING, COVER MISSING ON ELECTRICAL BOX. SAFETY RELIEF VALVE MANUFACTURE LABEL NOT LEGIBLE, SAFETY VALV... $0 $0 Nov 5, 2021
Jan 16, 2020 39015901M RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. GAS LEAK FOUND IN BASEMENT ON GAS METER FOR APT. 24 ON THE HOU... $1,250 $0 Sep 25, 2020
Mar 15, 2019 35359848X RESOLVE CLASS - 1 UNLAWFUL ACTS. FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER IN JANUARY 17, 2019 TWO ELECTRICAL VIOLATIONS WERE... $2,500 $0 Jul 12, 2019
Feb 28, 2019 35359829K RESOLVE CLASS - 1 UNLAWFUL ACTS. FAILURE TO COMPLY W/ AN ORDER OF THE COMMISSIONER. IN 1/9/19 AN ADMINISTRATIVE CODE VIOLATION WAS ISSU... $6,250 $0 Apr 19, 2019
Feb 26, 2019 35386438R RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: AT TIME OF INSPECTION I OBSERVED AT EXP#1&4 SEVERAL STEP CR... $0 $0 Apr 19, 2019
Jan 17, 2019 35379774K RESOLVE CLASS - 1 UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE. OBSERVED T... $300 $0 Jul 12, 2019
Jan 17, 2019 35379771P RESOLVE CLASS - 2 ELECTRICAL WORK W/O A PERMIT. OBSERVED IN BASEMENT REAR STORAGE AREA BEHIND BOILER ROOM THE INSTALLATION OF A CIRCUIT... $0 $0 Apr 5, 2019
Jan 17, 2019 35379772R RESOLVE CLASS - 1 FAILURE TO PROTECT TEMPORARY WIRING FROM IMPROPER CONTACT. OBSERVED THE INSTALLATION OF TEMPORARY POWER TO SIDEWALK S... $1,600 $0 Jul 12, 2019
Jan 9, 2019 35359772Z RESOLVE CLASS - 1 UNLAWFUL ACTS.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.IN OCTOBER 17,2018.ADMINISTRATIVE CODE VIOLATION WA... $0 $0 Mar 1, 2019
Dec 28, 2018 35373052L RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. OBSERVED AT EXP #1 & #4 SEVERAL STEP CRACKS BETWEEN 2ND & 3RD ... $6,250 $0 Feb 15, 2019
Oct 17, 2018 35361837N RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 10/17/18 AT ABOVE ADDRESS NO FRESH AIR VENT IN THE GAS... $0 $0 Dec 7, 2018
Oct 17, 2018 35361592Y RESOLVE CLASS - 1 EXPOSED ENERGIZED WIRING. OBSERVED THE FOLLOWING VIOLATING CONDITION INSIDE BOILER STORAGE ROOM LOCATED IN THE CELLAR... $1,600 $0 Dec 7, 2018
Oct 17, 2018 35347130Z RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES SECTION OF WALL COMING APART FROM MAIN WALL. ROOF LEVEL, CRACKI... $1,250 $0 Jan 18, 2019
Oct 17, 2018 35347129L RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3; 27-345 AT CELLAR LEVEL BACK ROO... $625 $0 Jan 18, 2019
Sep 10, 2018 32097761R RESOLVE CLASS - 2 11B,50A,50B-AS PER CLASS 2 (B254) 28.301.1:FAILURE TO MAINTAIN.11B:BOILER BLOW DOWN VALVE IN ACCESSIBLE FOR OPERATION... $310 $0 Nov 2, 2018
Apr 23, 2018 32096649M RESOLVE CLASS - 2 B254,50A,50B,50C,50D,50E,50F,50G. AS PER CLASS 2 (B254) 28.301.1 FAILURE TO MAINTAIN.50A-NO ACCESSIBLE BLOWDOWN VALVE... $310 $0 Jun 15, 2018
Sep 19, 2017 35293676J RESOLVE CLASS - 1 UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, MATERIAL, APPARATUS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERVE... $1,600 $0 Feb 9, 2018
Sep 19, 2017 35293675H RESOLVE CLASS - 1 FAILURE TO GROUND ELECTRICAL SYSTEMS. OBSERVED @ WATER MAIN LOCATED INTHE CELLAR: MAIN GROUNDING CONDUCTOR FOR BLDGS ... $1,000 $0 Feb 9, 2018
May 4, 2017 35260334Z RESOLVE CLASS - 1 SEC: FGC 408.2. FUTURE CONNECTIONS EXIST ON GAS PIPING. OBSERVED IN CELLAR FUTURE CONNECTIONS EXISTING ON GAS PIPING.... $0 $0 Sep 13, 2017
Sep 8, 2016 35207665K RESOLVE CLASS - 2 401.5,408.2,407.2 MISC VIOLATION.AT THE TIME OF MY INSPECTION, 11AM,ON09/08/2016 I OBSERVED IN THE BASEMENT.CELLAR OF... $400 $0 Nov 18, 2016
Feb 26, 2016 35171520H RESOLVE CLASS - 2 WORK W/O A PERMIT. AT CELLAR ALTERED PLUMBING WATER & WASTE LINES & ELECTRIC TO INSTALL WATER CLOSET,LAVATORY & 2 WAS... $800 $0 Apr 15, 2016
Jun 29, 2011 34891797J RESOLVE CLASS - 1 FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER.NO FIRE STOPPING.DEFECT:@ CELLAR BOILER ROOM,A CONCRETE MASONRY U... $1,000 $0 Sep 9, 2011
Jun 29, 2011 34891796H RESOLVE CLASS - 1 FAILURE TO MAINTAIN INTERIOR OF BLDG.DEFECT:@ CELLAR,THERE ARE ROTTED WOOD COLUMNS & FLR JOIST.WOOD COLUMNS ARE 4X4 &... $1,000 $0 Dec 23, 2011
Dec 2, 2009 34754819K RESOLVE CLASS - 1 PLUMBING WORK W/O A PERMIT & PERFORMED UNLICENSED PLUMBING WORK W/O MASTER PLUMBING LICENSE. NEW PLUMBING OBSERVED TH... $400 $0 Jan 22, 2010
Jul 5, 2008 34680951Z RESOLVE CLASS - 3 FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER NOTED @ LOBBY MAIL BOX INSERT APPROX 2' X 3' HAS FALLEN OUT OF SLOT... $500 $0 Aug 29, 2008
Jan 10, 2007 34559096M RESOLVE Non-Hazardous FAILURE TO MAINTAIN EXTERIOR BRICK WALL.PARAPIT WALL BRICK LEANING OUTOF PLUMB APROX.2 TO 3"LOCATION FRONT EAST ELEVA... $2,500 $0 Jul 20, 2007