Issued Violation Status Severity Description Penalty Balance due Hearing
Jun 29, 2026 39194115L ACTIVE CLASS - 1 VIOLATION WAS ISSUED ON ONE OF TWO DEVICE, THAT SERVICE A 14 STORY BUILDING, DEVICE # 2P4026 IS FOUND TO BE OUT OF SE... $3,125 $3,125 Sep 4, 2026
Apr 10, 2026 35729702Z ACTIVE CLASS - 1 FAILURE TO MAINTAIN BLDG EXTERIOR FACADE AND APPURTENANCES.REFER TO PREVIOUS VIOLATION FROM 04/02/26 35716927R SOME C... $5,030 $5,030 Jul 17, 2026
Apr 3, 2026 39183142N ACTIVE CLASS - 2 RESPONDING TO A 311 COMPLAINT; UPON INSPECTION I FOUND A DEVICE OUT OFSERVICE. REMEDY; REPAIR REPAIR THEN CONTACT NYC... $655 $655 Jul 17, 2026
Mar 25, 2026 39181711P ACTIVE CLASS - 2 FOUND A ROCKMILL MP250 STEAM BOILER LEAKING FROM INSIDE THE BOILER CHAMBER/ SMOKE ALARM NOT WORKING/ CORRECT ALL VIOL... $6,250 $6,250 May 29, 2026
Mar 3, 2026 39178988K ACTIVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987.UPON INSPE... $6,250 $6,250 May 15, 2026
Jan 12, 2026 39173527P ACTIVE CLASS - 2 CLASS 2: TOP OF CAR INSPECTION INOPERATIVE, REPAIR. TOP OF CAR LIGHT INOPERATIVE, REPAIR. DOOR OPERATOR INTERNAL COMP... $3,125 $3,125 Mar 20, 2026
Jan 8, 2026 39172959Y ACTIVE CLASS - 1 1) IN CAR STOP SWITCH IS NOT WORKING (CU) 2) THE WORM AND GEAR IS NOT PROPERLY MESH (CU). 3) THE BRAKE SHOE IS RATTLI... $12,500 $12,500 Mar 20, 2026
Jan 8, 2026 39172958M ACTIVE CLASS - 1 AN ELEVATOR IN SECTION OF BUILDING OR BUILDING IS OUT-OF-SERVICE. UPON INSPECTION THE DEVICE IS FOUND TO BE OUT-OF-SE... $12,500 $12,500 Mar 20, 2026
Dec 1, 2025 39168836M ACTIVE CLASS - 1 RESPONDING TO A 311 COMPLAINT, UPON INSPECTION FOUND THE DEVICE NOT WORKING. REMEDY; REPAIR DEVICE SO A FULL INPSECTI... $6,250 $6,250 Feb 6, 2026
Jul 25, 2025 35693620N ACTIVE CLASS - 1 UNLAWFUL ACTS, FAILURE TO COMPLY WITH COMMISSIONER'S ORDER. NOTE: UNSAFE FACADE DUE TO DEFECTED/BULGING FACADE AT EXP... $12,500 $12,500 Oct 3, 2025
Jul 25, 2025 35693622R ACTIVE CLASS - 1 UNLAWFUL ACTS, FAILURE TO COMPLY WITH COMMISSIONER'S ORDER. NOTE: UNSAFE FACADE DUE TO DEFECTED/BULGING FACADE AT EXP... $12,500 $12,500 Oct 3, 2025
Jul 3, 2025 39152745K ACTIVE CLASS - 2 CLASS 2 VIOLATION ISSUED, UPON INSPECTION. THE DEVICE IS FOUND TO BE OUT-OF-SERVICE. AS PER 1 RCNY 11-02. REMEDY; RES... $3,125 $3,125 Sep 19, 2025
Apr 2, 2025 35716927R ACTIVE CLASS - 1 FAILURE TO MAINTAIN BLDG EXTERIOR FACADE AND APPURTENANCES. NOTE: AT TIME OF INSPECTION, I OBSERVED AT EXP #3 SOUTH-(... $25,000 $25,000 Jun 6, 2025
Jan 29, 2025 39136810H ACTIVE CLASS - 2 FTM ROCKMILLS BOILER MP-250 WHICH PROVIDES STEAM,AND IS OIL FIRED .LEAKING WATER AT MAKE UP CONDENSATION PUMP /LACK O... $3,125 $3,125 Apr 4, 2025
Jan 29, 2025 37033086L RESOLVE CLASS - 2 FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS #39096568P ISSUED ON 10/05/2023, AND FAILURE TO FILE... $3,125 $3,125 May 2, 2025
Nov 26, 2024 39131346K ACTIVE CLASS - 1 RESTORE SERVICE DEVICE. ONE OF ONLY TWO ELEVATORS IN A 17 STORY MULTIPLE DWELLING OUT OF SERVICE. THIS CONDITION AFFE... $6,250 $6,250 Jan 31, 2025
Oct 24, 2024 39128399R ACTIVE CLASS - 1 : FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON IN... $6,250 $6,250 Jan 3, 2025
Oct 18, 2024 38275587H ACTIVE CLASS - 1 97-X-17=ENTIRE DEVICE INOPERATIVE UPON, INSPECTION THE DEVICE IS FOUNDTO BE OUT SERVICE. REMEDY: RESTORE SERVICE TO T... $6,250 $6,250 Jan 3, 2025
Oct 11, 2024 39127295H ACTIVE CLASS - 2 RESPONDING. TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION, THE DEVICE WAS FOUND OUT OF SERVICE, THIS DEVICE PROVIDE SE... $3,125 $3,125 Dec 20, 2024
Aug 30, 2024 35686131R ACTIVE CLASS - 2 FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES. NOTE:-OBSERVED SPALLING COATING UNDER BALCONY SLABS=O... $6,250 $6,250 Nov 15, 2024
Jul 15, 2024 39119070R ACTIVE CLASS - 2 ELEVATOR CURRENTLY OUT OF SERVICE, STUCK ON LOBBY LEVEL, RESTORE TO SERVICE $3,125 $3,125 Sep 20, 2024
Apr 16, 2024 38275576M ACTIVE CLASS - 1 97-X-17, 56-L-10. 97-X-17=UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE. THIS IS A 16 STORY BUILDING WITH ... $25,000 $25,000 Jun 21, 2024
Apr 11, 2024 37027548X ACTIVE CLASS - 2 FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 8B AND 9B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTE... $10,000 $10,000 Jul 5, 2024
Mar 25, 2024 38275523Z ACTIVE CLASS - 2 AGGRAVATED II CONDITION.RESPONDENT HAS HISTORY OF FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS.RESPONDENT FAILED TO C... $10,000 $10,000 Jul 5, 2024
Mar 21, 2024 38275518Y RESOLVE CLASS - 1 97-X-17, 56-L-10. 97-X-17=ENTIRE DEVICE INOPERATIVE-ENTIRE DEVICE STILL REMAINS UNDER CEASE USE NOT LIFTED ON THIS 16... $6,250 $6,250 May 31, 2024
Mar 19, 2024 39109150H ACTIVE CLASS - 2 FAILURE TO MAINTAIN. OBSERVED EXTERIOR BALCONIES AT ALL EXPOSURES AND FLOORS ARE IN DISREPAIR, PEELING AND CHIPPING P... $3,125 $3,125 May 31, 2024
Mar 7, 2024 39108058K ACTIVE CLASS - 2 ROCKMILL MP-250 STEAM OIL FIRE BOILER LEAKING/BOILER ACRON FRESH AIR FAN NOT WORKING/SMOKE ALARM NOT WORKING/MISSING ... $3,125 $3,125 May 17, 2024
Mar 5, 2024 39107793M RESOLVE CLASS - 1 RESPONDING TO 311 ELEVATOR COMPLAINT, UPON INSPECTION OF DEVICE IN A TWO CAR BUILDING, DEVICE IS UNDER CEASE USE ORDE... $6,250 $6,250 May 17, 2024
Feb 23, 2024 38275517M RESOLVE CLASS - 1 97-X-10, 56-L-10. (97) ENTIRE DEVICE INOPERATIVE UPON INSPECTION ARRIVAL DUE TO (56)- HOIST MACHINE WORK BEEN PERFORM... $3,125 $3,125 May 3, 2024
Dec 21, 2023 38275501H RESOLVE CLASS - 1 CEASE USE 56L10 AND 56Y13 EXCESSIVE HOIST MACHINE NOICE DUE TO DEFECTIVE BEARINGS MUST REPAIR IMMEDIATELY.MACHINE OIL... $3,125 $3,125 Mar 1, 2024
Dec 21, 2023 38275502J RESOLVE CLASS - 1 CEASE USE 42X10 INOPERATIVE DOOR LOCK MONITORING MUST REPAIR IMMEDIATELY.THIS A SAFETY DEVICE THAT ENSURES PASSENGER ... $3,125 $3,125 Mar 1, 2024
Oct 5, 2023 39096568P ACTIVE CLASS - 2 ELEVATOR NOT ADDRESS ALL INCAR STATION CALLS; NOT STOPPING ON FLOORS THAT ARE ADDRESSED; REPAIR IN CAR CALL STATION, ... $625 $625 Dec 15, 2023
Jan 20, 2023 39078260J ACTIVE CLASS - 2 HOLE IN THE CEILING, DUE TO WATER LEAK. IN APARTMENT 15-J, REPAIR AND/OR REPLACE; REPAIR/REPLACE $3,125 $3,125 Mar 31, 2023
Nov 4, 2022 39073427J RESOLVE CLASS - 1 ELEVATOR CURRENTLY OUT OF ORDER AND NOT TAKING CALLS.; REMEDY REPAIR AND RESTORE TO SERVICE $3,125 $3,125 Jan 27, 2023
Oct 19, 2022 37022829J ACTIVE CLASS - 2 FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... $3,125 $3,125 Feb 28, 2025
Apr 8, 2022 39059913Y RESOLVE CLASS - 2 CLASS 2 VIOLATION ISSUED, IN CAR CALL OPERATION STATION INDICATOR NOT WORKING REMEDY; REPAIR, / LOBBY INDICATOR NOT W... $1,563 $1,563 Sep 26, 2025
Jan 20, 2022 39054602Y ACTIVE CLASS - 1 CLASS 2 VIOLATION ISSUED ITEM, IN CAR CALL STATION DEFECTIVE, BUTTON, DEVICE NOT STOPPING ON SELECTIVE FLOOR ,REMEDY,... $6,250 $6,250 May 6, 2022
Jun 1, 2021 37021663Y ACTIVE CLASS - 2 FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... $3,125 $3,125 Feb 28, 2025
Aug 27, 2020 39027634P ACTIVE CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS PER 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. REMEDY; INSTALL... $6,250 $6,250 Oct 16, 2020
Aug 27, 2020 39027635R ACTIVE CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS PER 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. REMEDY; INSTALL... $6,250 $6,250 Oct 16, 2020
Jun 6, 2020 39023590Y ACTIVE CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... $6,250 $6,250 Aug 21, 2020
Jun 6, 2020 39023591X ACTIVE CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... $6,250 $6,250 Aug 21, 2020
May 7, 2020 39022018Z RESOLVE CLASS - 1 5-A-10 DOOR RESTRICTOR ALTERED (CEASE USED) RE INSPECTION REQUIRED. $3,125 $0 Jul 31, 2020
Jan 23, 2020 39016197M ACTIVE CLASS - 1 CLASS 1= NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC... $6,250 $6,250 Jul 31, 2020
Jan 24, 2019 38267854N RESOLVE CLASS - 1 05A10,59H11,39O02,100M07-05A10)CEASE USE ITEM. DOOR ZONE RESTRICTOR HAS BEEN TAMPERED WITH, DISABLED AND RENDERED INO... $1,250 $0 Mar 15, 2019
Nov 2, 2018 39000697M ACTIVE CLASS - 2 FRESH AIR FAN IS DEFECTIVE-COLD WATER PIPES SWEATING ONTO BURNER-CONDESATE FLOAT SWITCH IS DEFECTIVE-HW GAGES AT COIL... $625 $625 Dec 21, 2018
Oct 15, 2018 37013679Z ACTIVE CLASS - 2 FAILURE TO SUBMIT A REQUIRED CYCLE 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPUR... $1,250 $0 Nov 15, 2019
Aug 29, 2018 38262746N RESOLVE CLASS - 1 05X10,29L10,52E10,59B07,56L10,68BB7-5X)REPAIR DOOR ZONE RESTRICTOR. 29L)REPAIR DOOR STOP ON OPERATOR. 59B)PROVIDE RIV... $1,250 $0 Oct 19, 2018
Jul 12, 2018 32097191Y ACTIVE CLASS - 1 B154,15,32,50A,50B B154 51 HAZARDOUS OPERATING A BOILER THAT WAS SEALED BOILER TUBE LEAKING, 15,32A,50A OIL LEAKING, ... $6,250 $0 Oct 26, 2018
Mar 27, 2018 32093339N ACTIVE CLASS - 2 50)AS PER CLASS 2(B254)28-301.1 FEDERAL BOILER (BOILER #44273-02) IS NOT OPERATIONAL (BURNER REMOVED). CORRECT VIOLAT... $625 $0 Sep 14, 2018