ECB violations
2346 Prospect Avenue, Bronx • Block 03114 • Lot 0044
30 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 28, 2026 | 39190102Y | RESOLVE | CLASS - 2 | CLASS 2: CATEGORY 5 TEST TAG HAS NO DATE, AND DOB RECORDS INDICATE THIS TEST HAS NEVER BEEN PERFORMED, EVEN THOUGH DE... | $0 | $0 | Aug 21, 2026 |
| May 28, 2026 | 39190179M | ACTIVE | CLASS - 1 | OBSERVED OBSTRUCTED SPRINKLER HEADS THROUGHOUT BUILDING, IN BASEMENT PVC BEING USED ON SEWER MAIN, STEAM FITTINGS BEI... | $2,500 | $2,500 | Aug 21, 2026 |
| Mar 31, 2026 | 35726894Z | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING FACADE WALL"S" AND APPURTENANCES. NOTE: AT THE TIME OF INSPECTION I OBSERVED AT EX #3, E... | $2,500 | $2,500 | Dec 7, 2026 |
| Feb 11, 2025 | 37033254L | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS #39103733M ISSUED ON 01/18/2024, AND FAILURE TO FILE... | $1,250 | $1,250 | Jun 29, 2026 |
| Feb 12, 2024 | 39105771M | RESOLVE | CLASS - 2 | OBSERVED MOLD ON THE CEILING OF BOILER ROOM LOCATED IN THE BASEMENT/CELLAR., REPAIR AND/OR REPLACE | $625 | $0 | Apr 19, 2024 |
| Jan 18, 2024 | 39103732K | RESOLVE | CLASS - 2 | UNPERMITTED FOAM USED TO SEAL HOLE PENETRATIONS THROUGHOUT THE BUILDING., PROVIDE/MAINTAIN FIRE STOPPING | $625 | $0 | Aug 23, 2024 |
| Jan 18, 2024 | 39103733M | RESOLVE | CLASS - 2 | UNPERMITTED PLASTIC ACCESS PANALS INSTALLED THROUGHOUT BUILDING., REPAIR AND/OR REPLACE | $625 | $0 | Mar 29, 2024 |
| Aug 9, 2022 | 39067637R | RESOLVE | CLASS - 2 | I OBSERVED IN THE BASEMENT ELECTRICAL EQUIPMENT THE INSTALLATION OF DATA SERVER EQUIPMENT AND WIRING. ELECTRICAL EQUI... | $0 | $0 | Sep 30, 2022 |
| Aug 9, 2022 | 39067689Z | ACTIVE | CLASS - 1 | ELECTRICAL BRAKE MONITORING SWITCH DEFECTIVE BROKEN , AND PARAMETER 74 IS TURNED OFF ON THE CONTROLLER. SO THE ELEVAT... | $1,280 | $1,280 | Feb 8, 2027 |
| May 5, 2022 | 39061687H | RESOLVE | CLASS - 2 | EXISTING EMERGENCY LIGHTS, ON THE 6TH FLOOR (STAIR A&B), 5TH FL (STAIR A), 4TH FL (STAIR A),3RD FL (STAIR A), 2ND FL ... | $625 | $0 | Jul 1, 2022 |
| Apr 3, 2019 | 38268911P | RESOLVE | CLASS - 2 | 12.B.10,59.B.7=(12,B,10)MISSING TWO LIGHT FIXTURES IN THE CAB (59,B,7) BRAKE MAINTENANCE TAG MISSING ATE TEST WAS PER... | $312 | $0 | Jul 12, 2019 |
| Mar 14, 2019 | 35359015L | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONERS.AN UNLAWFUL ACT. FAILURE TO CORRECT AND CERTIFY (WITH THE BUILDI... | $0 | $0 | May 3, 2019 |
| Nov 8, 2018 | 35372237N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED IN CELLAR A BALL VALVE AND A BOILER DRAIN INSTALLED O... | $312 | $0 | Jan 18, 2019 |
| Nov 8, 2018 | 35373086J | RESOLVE | CLASS - 1 | UNAPPROVED,UNSAFE,UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS,MATERIALS,DEVICES,APPLIANCES,OR WIRING IN USE.OBSERVED IN... | $300 | $0 | Feb 1, 2019 |
| Nov 8, 2018 | 35373087L | RESOLVE | CLASS - 2 | FAILURE TO SECURE/SUPPORT RACEWAYS/CABLE ASSEMBLIES/BOXES/CABINETS/FITTINGS.OBSERVED A.C.DISCONNECT ON ROOFTOP HOT PR... | $0 | $0 | Feb 1, 2019 |
| May 23, 2018 | 35331842K | RESOLVE | CLASS - 1 | FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH SECTION.OBSERVED AT WATER MAIN LOCATED IN THE CEL... | $1,200 | $0 | Dec 14, 2018 |
| May 23, 2018 | 35331843M | RESOLVE | CLASS - 2 | FAILURE TO INSTALL GROUND FAULT CIRCUIT INTERRUPTER(GFCI)PROTECTION ASREQUIRED.OBSERVED IN LAUNDRY ROOM LOCATED ON TH... | $2,400 | $0 | Oct 12, 2018 |
| May 23, 2018 | 35331813L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER:NO FIRE STOPPING PERBC 712.3; 27-345.NOTED:@CELLAR:BOILER ROOM NO F... | $625 | $0 | Oct 12, 2018 |
| Sep 18, 2017 | 35290904Z | RESOLVE | CLASS - 1 | FGC411.1. RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT. OBSERVED ON 9/18/17 @ ABOVE ADDRESS RESIDENTIAL GAS FLEX... | $800 | $0 | Feb 27, 2018 |
| Nov 13, 2015 | 35118981H | RESOLVE | CLASS - 1 | 1604.1 INADEQUATE STRUCTURAL DESING IN THAT DESIGN COMPUTATIONS DO NOT DEMONSTRATE CONFORMANCE WITH THE APPLICABLE ST... | $1,600 | $0 | Feb 12, 2016 |
| Sep 25, 2015 | 35139598H | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER. CONTRACTOR WAS INSTRUCTED TO BACKFILL EXPOSED FOUNDATION OF ADJOINI... | $2,430 | $0 | Nov 20, 2015 |
| Jun 2, 2015 | 35121397X | RESOLVE | CLASS - 1 | BC 3307.2.1 FAILURE TO PROVIDE/MAINTAIN TEMP WALKWAY.UPON INSP AAS NOTED THE TEMP WALKWAY'S ON EXP#1 & #4 IS LAYING I... | $1,600 | $0 | Aug 28, 2015 |
| Apr 16, 2015 | 35118421J | RESOLVE | CLASS - 2 | BC3304.4.4 FAILURE TO PROVIDE 3'6"GUARDRAIL ON SOLID ENCLOSURE AROUND OPEN AND ACCESSIBLE SIDES OF EXCAVATION NOTED: ... | $400 | $0 | Jun 5, 2015 |
| Apr 16, 2015 | 35118420H | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE APPROVED/ACCEPTED PLANS AT JOBSITE AT TIME OF INSPECTION NO APPROVED CONSTRUCTION DOCUMENTS AT TIM... | $0 | $0 | Jun 5, 2015 |
| Apr 16, 2015 | 35118423N | RESOLVE | CLASS - 2 | BC1704.1.1 FAILURE TO PROVIDE/FILE A SPECIAL INSPECTION STATEMENT OF RESPONSIBILITY PRIOR TO PERMIT ISSUANCE AND PRIO... | $0 | $0 | Jul 24, 2015 |
| Apr 16, 2015 | 35118422L | RESOLVE | CLASS - 1 | BC3304.8 EXCAVATION NOT ADEQUATELY DRAINED OF RAIN WATER AND/OR SUB- SURFACE WATER. NOTED: CONTRACTOR WAS PUMPING WAT... | $1,600 | $0 | Jun 5, 2015 |
| Apr 16, 2015 | 35118419K | RESOLVE | CLASS - 2 | BC3309.6 FAILURE TO MONITOR ADJOINING STRUCTURES FOR MOVEMENT IN ALL DIRECTIONS DURING EXCAVATIONS RELATED ACTIVITY T... | $400 | $0 | Jun 5, 2015 |
| Dec 17, 2014 | 35121758M | RESOLVE | CLASS - 1 | BC3309.9 WEATHER PROOFING INTEGRITY OF ADJOINING PROPERTY.AT TIME OF DEMO SIGNOFF INSPECTION NOTED THAT THE WEATHER P... | $1,600 | $0 | Mar 13, 2015 |
| Dec 17, 2014 | 35121757K | RESOLVE | CLASS - 1 | BC3301.4.1 MAINTENANCE SIDEWALKS,TRIPPING HAZARDS AT TIME OF INSPECTION NOTED @EXP1 SIDEWALK A HOLE APPRX 4'X4'HOLE O... | $1,600 | $0 | Mar 13, 2015 |
| Dec 11, 2012 | 34956892M | RESOLVE | CLASS - 2 | ZONING - ILLEGAL USE IN ESIDENTIAL DISTRICT NOTED: BLDG DEPT RECORDS INDICATE LEGAL USE IS THREE (3) FAMILY HOUSE AND... | $0 | $0 | Feb 25, 2014 |