ECB violations
1000-1016 East 180 Street, Bronx • Block 03132 • Lot 0001
50 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 13, 2024 | 39114205M | RESOLVE | CLASS - 1 | CEASE USE ITEM: INOPERATIVE ZONE LOCK RESTRICTOR. CLASS 2 ITEMS: REPALCE WORN GIBS WHERE NEEDED. SECURE GIBS WHERE NE... | $1,250 | $0 | Jul 19, 2024 |
| Apr 29, 2024 | 39112941L | RESOLVE | CLASS - 2 | CLASS 2: PHONE INOPERATIVE REPAIR & CONNECT SERVICE TO 24 HR EMERGENCY OPERATOR. CAB POSITION INDICATOR INOPERATIVE C... | $0 | $0 | Aug 16, 2024 |
| Apr 29, 2024 | 39112870N | RESOLVE | CLASS - 2 | CLASS 2: CAB LIGHT DAMAGED & INOPERATIVE. REPLACE LIGHT & FIX WIRING. ACCESS DOOR DAMAGED REPAIR DOOR. CAR DOOR MISAL... | $0 | $0 | Aug 16, 2024 |
| Nov 17, 2022 | 39074228L | RESOLVE | CLASS - 2 | CLASS 2 VIOLATION ISSUED ITEMS ARE 1) FLOORS 1/2/3/AND 4 HOIST WAY DOOR KEEPER LOOSE UNSECURED, REMEDY; REPAIR. 2) FL... | $625 | $0 | Jul 21, 2023 |
| Jul 28, 2022 | 39066928M | RESOLVE | CLASS - 1 | DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED MISSING PARTS(CU). EXCCESSIVE PLAY IN THE STUDYING PLATE. | $1,250 | $0 | Sep 16, 2022 |
| Feb 7, 2022 | 39055703H | RESOLVE | CLASS - 1 | OUT OF SERVICE | $625 | $0 | May 20, 2022 |
| Jan 31, 2022 | 39055259K | RESOLVE | CLASS - 1 | NO DLM INSTALLED IN CONTROLLER AS MANDATED IN APPENDIX K OF THE 2014 BUILDING CODES, REMEDY INSTALL DOOR LOCK MONITIO... | $1,250 | $0 | May 20, 2022 |
| Dec 3, 2021 | 39052236Y | RESOLVE | CLASS - 2 | CLASS 2 VIOLATION ISSUED, NO ACCESS IN MOTOR, PROVIDE KEYS FOR LOCATION,/ IN CAR PHONE NOT WORKING,REPAIR. | $625 | $0 | Mar 18, 2022 |
| May 23, 2020 | 38273406K | RESOLVE | CLASS - 2 | 2X10/5H11/10H11/16H11/17H11/18F1/28H11-2X10:INOPERATIVE PHONE REPAIR.15H11:CAR DOOR ROLLERS AND TRACK WORN REPLACE DE... | $625 | $0 | Jul 31, 2020 |
| May 23, 2020 | 38273407M | RESOLVE | CLASS - 2 | 5H11/10H11/28H11/32E1/17H11-5H11:CAR DOOR HANGER ROLLERS AND TRAK WORNDEFECTIVE LOTS OF RUMBLING AND WORCE.10H11:CAR ... | $625 | $0 | Jul 31, 2020 |
| May 23, 2020 | 38273405Z | RESOLVE | CLASS - 2 | 2X10/6H11/10H11/16E1/17H11/28H11-2X10:PHONE INOPERATIVE REPAIR.6H11-CAR DOOR HANGER ROLLERS AND TRACK WORN DEFECTIVE ... | $625 | $0 | Jul 31, 2020 |
| Jun 10, 2019 | 38270136X | RESOLVE | CLASS - 2 | 02X10,35M07,71X10,12I10,40P16;(02-X)=REPAIR IN CAR PHONE(35-M)=PROVIDECOVER FOR ELECTRIC WIRING IN HOISTWAY(71-X)=REP... | $625 | $0 | Aug 2, 2019 |
| Aug 21, 2018 | 38264735R | RESOLVE | CLASS - 1 | 02X10,67X10,70O02,40P16-02X10)REM: REPAIR ALARM BELL AND CONTACT NYCDOB FOR RESTORATION TO SERVICE. 67X10)REM: REPAIR... | $1,250 | $0 | Oct 5, 2018 |
| Jan 31, 2018 | 38261200R | RESOLVE | CLASS - 1 | CU-05X10,02B10,70Z02,31V10. 05X10-DOOR RESTRICTOR INOPERATIVE REPAIR AND CONTACT NYCDOB TO RESTORE TO SERVICE; 02B10-... | $1,000 | $0 | Mar 30, 2018 |
| Apr 26, 2017 | 38254744J | RESOLVE | CLASS - 1 | 16J01:FLOOR HOISTWAY DOOR HAS A WIDE GAP ON THE RETURN END WHEN DOOR'SIN CLOSE POSITION,CREATING A HAZARDOUS CONDITIO... | $5,000 | $0 | Jul 14, 2017 |
| Mar 15, 2017 | 38252093X | RESOLVE | CLASS - 1 | 97X17 THE ONLY ELEVATOR IN BLDG OUT OF SERVICE.UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE CREATING A HA... | $1,000 | $0 | May 5, 2017 |
| Feb 1, 2017 | 38252957Y | RESOLVE | CLASS - 1 | 97X17 THE ONLY ELEVATOR IN BLDG OUT OF SERVICE. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE CREATING A ... | $1,000 | $0 | Mar 31, 2017 |
| Sep 28, 2016 | 38246209H | RESOLVE | CLASS - 1 | 97X10. UPON INSP THE DEVICE IS FOUND TO BE OUT OF SERVICE. REM: RESTORE BACK TO SERVICE IMMEDIATELY. | $1,000 | $0 | Nov 18, 2016 |
| Jul 12, 2016 | 38244140J | RESOLVE | CLASS - 1 | 02X10,05B09,40M07. (02X)REPAIR PHONE. (05B)RESTRICTOR WEDGE NOT OPERABLE REPAIR. (40M)PROVIDE MOTOR ROOM ACCESS. | $1,000 | $0 | Sep 2, 2016 |
| Apr 29, 2016 | 35158197K | RESOLVE | CLASS - 2 | PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATION. SIDEWALK SHED LIGHTS. NOTE: OBSERVED SIDEWALK SHED ERECTED AT... | $2,400 | $0 | Jun 17, 2016 |
| Jan 25, 2016 | 38240574Z | RESOLVE | CLASS - 2 | 40P07,39P07. 40P07-NO ACCESS TO MACHINE ROOM (PROVIDE); 39P07-FROM 5THFLR HATCH DOOR NO MEANS TO ACCESS TOP OF ELEVAT... | $500 | $0 | Mar 18, 2016 |
| Mar 21, 2015 | 38235477K | RESOLVE | CLASS - 2 | 28I11,10H11,02L10,67L10,17H11,40M07.28-CAR DOOR HANGER ROLLERS DAMAGED REPLACE.110-CAR DOOR GIBBS EXCESSIVELY WORN RE... | $500 | $0 | May 15, 2015 |
| Dec 23, 2014 | 38234362X | RESOLVE | CLASS - 2 | 05V10. 05V10-REPAIR ELEVATOR RELEVELING ON 4TH FLR DOWN DIRECTIONAL FLOOR STOP. | $0 | $0 | Feb 6, 2015 |
| Apr 24, 2014 | 38231005Y | RESOLVE | CLASS - 1 | 97X10 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER SERVICE EQUIPMENT ELEVATOR AS PER BC3001.2 27-987 DOB RECORDS... | $1,000 | $0 | Jul 11, 2014 |
| Apr 1, 2014 | 38230790Y | RESOLVE | CLASS - 1 | B151.97X10:FAIL TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.SERVICE EQUIP ELEVATORS.DOB RECORDS SHOW THE ONLY ELEVATOR ... | $1,030 | $0 | May 16, 2014 |
| Jun 4, 2013 | 38227384L | RESOLVE | CLASS - 2 | 70Y10,08V10. 70-CLEAN OIL AND REPAIR LEAK (PISTON HEAD); 08-ELEVATOR RE-LEVELING AT FLOOR STOPS | $0 | $0 | Jul 19, 2013 |
| Mar 5, 2013 | 35001691K | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE SAFETY MEASURES SUCH AS SIDEWALK SHED,FENCE ETC. TOPROTECT PUBLIC FORM UNSAFE CONDITIONS AS PER 1R... | $2,400 | $0 | Apr 19, 2013 |
| Jul 6, 2011 | 38217217P | RESOLVE | CLASS - 2 | 17H11 60Q03 100M07. 17H11-REPLACE WORN 1ST FLR HOISTWAY DOOR GIBBS. 100M07-PROVIDE FIRE EXTINGUISHER IN MOTOR ROOM. | $250 | $0 | Sep 2, 2011 |
| Nov 18, 2009 | 38207562R | RESOLVE | CLASS - 1 | 97,X,10- 97 X 10- ONLY ELEVATOR IN BUILDINGS IS OUT OF SERVICE THEREBYCREATING CONDITIONS DANGEROUS TO HUMAN LIFE.REP... | $1,000 | $0 | Feb 5, 2010 |
| Nov 4, 2009 | 38207036R | RESOLVE | CLASS - 1 | 16R10 CEASE USE THE 1ST FL HOISTWAY DOOR REPAIR OR REPLACE | $0 | $0 | Apr 4, 2011 |
| Oct 30, 2009 | 38207139J | RESOLVE | CLASS - 1 | CU-17M10,08V10,17H10. CU 17M10, 08V10,17H10. CU-17M10-3FL HOISTWAY DOOR GIBS MISSING. CU-08V10-ELEV RELEVELING AT FL ... | $1,000 | $0 | Dec 18, 2009 |
| Sep 29, 2009 | 38206470P | RESOLVE | CLASS - 2 | 11X10.35Q3.60Q3.68M7.71X10.77Q3 11X10 REPAIR DOOR OPEN BUTTON IN CAR STATION 35Q3 INSTALL COVERS FOR ELECTRICAL BOXES... | $250 | $0 | Nov 20, 2009 |
| Mar 5, 2007 | 38165059R | RESOLVE | Non-Hazardous | 83L10,23L10,11L10,83U10.83L-CAR LEVELS ON EVERY FL ON THE DOWN DIRECTIONS.23L-HALL BUTTON STATION LIGHTS ARE OUT ON A... | $350 | $0 | Apr 20, 2007 |
| Jan 18, 2005 | 38156934L | RESOLVE | Non-Hazardous | 83X10 83- REPAIR AND RESTORE TO SERVICE SO A FULL INSPECTION COULD BE DONE BY THIS DEPARTMENT. | $180 | $0 | Mar 4, 2005 |
| Sep 10, 2004 | 38148988R | RESOLVE | Non-Hazardous | 40D06/10H10/05J10/17M07/12X10/33O02 05-EXCESSIVE GAP AT RETURN POST. 17M07-LOBBY H/DOOR- 12X10- WORK LIGHT TOP OF CAR... | $180 | $0 | Oct 22, 2004 |
| Feb 23, 2004 | 38145042M | RESOLVE | Non-Hazardous | 5#1/15M7/31H10/66O2/83E1 (5)CAR DOOR DOESY NOT NOT OPEN FULLY (15)CERTIFICATE FRAME MISSING (31)WORN GUIDE HOES(66)PI... | $180 | -$180 | May 7, 2004 |
| Feb 23, 2004 | 38145043Y | RESOLVE | Non-Hazardous | 3A9/20I11/31H10/66O2(3)L-BRACKETS ON CAR DOOR FRAME REMOVE (20)VISION GLASS IN LOBBY (31)WORN GUIDE SHOES (66)PIT DIRTY | $180 | $0 | Apr 28, 2004 |
| Oct 1, 2003 | 38142285N | RESOLVE | Non-Hazardous | 83X10/ 83U15/ #83=YOU MUST RESTORE THIS DEVICE BACK TO SERVICE SO A PROPER INSPECTION CAN BE MADE. #83=YOU MUST FIND ... | $180 | $0 | Nov 21, 2003 |
| Sep 29, 2003 | 38142276L | RESOLVE | Non-Hazardous | 47Y10/ 47BB05/ 28Q03/ 03O02/ 47B07/ 84I10/ 17H10/ 57O02/ 21Q03/ 30P07/#47=INSUFFICIENT OIL LEVEL. #84=WORK LIGHT TOP ... | $180 | $0 | Nov 21, 2003 |
| Apr 25, 2003 | 38137071L | RESOLVE | Non-Hazardous | 62O02,62Y02,80X11. 80-PHONE LINE TO OUTSIDE COMMUNICATION OUT OF ORDER | $350 | $0 | Jun 6, 2003 |
| Mar 17, 2003 | 34385778M | RESOLVE | Hazardous | FAILURE TO MAINTAIN. DEFECT IS: ROOF MEMBRAIN HAS FAILED AT VARIOUS LOCATIONS CAUSING SHEETING TO ROT AND SAG. REMEDY... | $2,000 | $0 | Nov 7, 2003 |
| Jan 13, 2003 | 38134950Y | RESOLVE | Non-Hazardous | 79X11. 79=RESTORE TO SERVICE FOR A COMPLETE INSPECTION BY THIS DEPART-MENT. | $350 | $0 | Feb 28, 2003 |
| Dec 12, 2002 | 34387504Y | RESOLVE | Hazardous | FAILURE TO MAINTAIN .DEFECTS ARE:THE PATCHED ROOF MEMBRAIN HAS FAILED CAUSING THE SHEETING TO ROT & LOSE STRUCTURAL I... | $800 | $0 | Jul 18, 2003 |
| Dec 12, 2002 | 34387502K | RESOLVE | Hazardous | FAILURE TO MAINTAIN-DEFECTS ARE:THE PATCHED ROOF MEMBRAIN HAS FAILED CAUSING THE SHEETING TO ROT & LOSE STRUCTURAL IN... | $800 | $0 | Jul 18, 2003 |
| Dec 12, 2002 | 34387503M | RESOLVE | Hazardous | FAILURE TO MAINTAIN ;DEFECTS ARE:THE RATCHED ROOF MEMBRAIN HAS FAILED CAUSING THE SHEETING TO ROT & LOSE STRUCTURAL I... | $800 | $0 | Jul 18, 2003 |
| Aug 21, 2001 | 38118607R | RESOLVE | Non-Hazardous | 43Y11/ 21X11/ 18Q03/ 16H12/ 57Y09/ 57O02 | $180 | $0 | Oct 5, 2001 |
| Feb 27, 1996 | 38054409X | RESOLVE | Non-Hazardous | 07X,10D.07-REPAIR SAFTY EDGE 10-REPAIR CAR STATION. | $100 | -$100 | May 10, 1996 |
| Apr 12, 1994 | 38039094P | RESOLVE | Non-Hazardous | 14M, 43Y, 50Y, 57Y, 57O, 74#. 74. ELEVATOR LEVELING OFF PROPERLY ADJU-ST. | $0 | $0 | May 27, 1994 |
| Feb 13, 1991 | 34049859L | RESOLVE | Hazardous | REQUIRED MEANS OF EGRESS OBSTRUCTED AT EXIT- LOCK AT TOP OF PL- REMEDYREMOVE OBSTRUCTION HAVE EXIT CONFORM TO CODE. E... | $400 | $0 | Jul 12, 1991 |
| Feb 14, 1990 | 34034247Z | RESOLVE | Hazardous | FAILURE TO HAVE APPROVED PA PLANS AVAIALBLE FOR INSPECTION. USE OF PROHIBITED HARDWARE. REMEDY: PROVIDE APPROVED PA P... | $150 | $0 | Mar 30, 1990 |