ECB violations
2240 Grand Concourse, Bronx • Block 03158 • Lot 0005
40 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 30, 2026 | 39186710X | RESOLVE | CLASS - 1 | OBSERVED LACK OF SPRINKLER COVERAGE ON FLRS 1 THROUGH 5 PER BC 28-301.1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIAN... | $2,500 | $2,500 | Feb 19, 2027 |
| Jan 3, 2024 | 39102621N | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS STATED IN ECB# 39094408R ISSUED ON 09/08/2023. PURSUANT T... | $2,500 | $2,500 | Mar 15, 2024 |
| Sep 8, 2023 | 39094410X | RESOLVE | CLASS - 3 | OBSERVED THROUGHOUT BUILDING ESCUTCHEON PLATES ARE NOT FLUSH WITH CEILING., REPAIR AND OR REPLACE | $500 | $500 | May 17, 2024 |
| Sep 8, 2023 | 39094411H | RESOLVE | CLASS - 3 | OBSERVED IN THE BASEMENT IN THE BOILER ROOM CRACK ON CAST IRON VENT PIPE. ALSO FERNCO COUPLINGS INSTALLED ON CASTION ... | $0 | $0 | Dec 15, 2023 |
| Sep 8, 2023 | 39094408R | RESOLVE | CLASS - 1 | OBSERVED THE FOLLOWING UNIT APARTMENTS CURRENTLY OCCUPIED CONTRARY AND WHILE UNDER A PARTIAL VACATE ORDER, (112-512(5... | $4,800 | $0 | Dec 15, 2023 |
| May 4, 2022 | 39061578Z | RESOLVE | CLASS - 2 | I OBSERVED AT BASEMENT/CELLAR LEVEL IN GAS METER ROOM EXCESSIVE COMBUSTIBLE STORAGE( BIKES, WINDOW FANS,TABLES, PAINT... | $625 | $0 | Aug 5, 2022 |
| May 4, 2022 | 39061579K | RESOLVE | CLASS - 2 | AT ROOF LEVEL, FENCE INSTALLED ON PARAPET WALL, EXP # 2, IS PARTIALLY COLLAPSED TOWARDS THE BUILDING., REPAIR AND/OR ... | $625 | $625 | Aug 5, 2022 |
| Aug 7, 2020 | 35476784Z | RESOLVE | CLASS - 2 | AT TIME OF INSPECTION,OBSERVED ONGOING CONSTRUCTION ACTIVITES CONTRARYTO MAYORS EMERGENCY EXECUTIVE ORDER 120 AND SUB... | $0 | $0 | Jan 8, 2021 |
| Jun 7, 2019 | 35434230L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 6/07/19 @ABOVE ADDRESS IN CELLUR/BASEMENT 3 INCH W... | $0 | $0 | Dec 6, 2019 |
| Mar 28, 2019 | 35386222H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDNG IN CODE-COMPLIANT MANNER. OBSERVED ON 3/28/19 AT ABOVE ADDRESS IN CELLAR/BASEMENT 3" WATE... | $0 | $0 | Jun 7, 2019 |
| Jan 15, 2019 | 35372711L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 1-15-19 AT ABOVE ADDRESS IN CELLAR 3 INCH WATER SERVIC... | $0 | $0 | May 17, 2019 |
| Jan 14, 2019 | 35359782M | RESOLVE | CLASS - 1 | UNLAWFUL ACTS.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.IN DECEMBER 14, 2018.AN ELECTRICAL VIOLATION WAS IS... | $2,500 | $0 | Mar 1, 2019 |
| Dec 10, 2018 | 35372708K | RESOLVE | CLASS - 2 | WORK WITHOUT A PERMIT. OBSERVED ON 12/10/18 AT ABOVE ADDRESS, NEW FIRE DEPARTMENT CONNECTION INSTALLED WITHOUT ANY PE... | $3,125 | -$3,125 | Feb 15, 2019 |
| Dec 10, 2018 | 35340505Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35346974Y ISSUED ON 09/26/2018 AND TO ... | $0 | $0 | Feb 21, 2019 |
| Nov 21, 2018 | 35372855K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER.OBSERVED IN CELLARA THREE(3)INCH WATER SERVICE INSTALLED FOR MORE... | $0 | $0 | May 17, 2019 |
| Nov 2, 2018 | 35373080Z | RESOLVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPRATUS,MATERIAL DEVICES,APPLIANCES, OR WIRING IN USE.OBSERVED THR... | $4,000 | $0 | Feb 21, 2019 |
| Sep 26, 2018 | 35346974Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: NO CONNECTION TO FIRE DEPARTMENT CONNECTION AT FRONT OF... | $0 | $0 | Dec 7, 2018 |
| Sep 17, 2018 | 35360444H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER. NOTED: AT CELLAR LEVEL A 3 INCHES WATER SERVICE FOR MORE THAN 150 ... | $3,125 | $0 | Nov 16, 2018 |
| Aug 21, 2018 | 35347487L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: NO CONNECTION TO FIRE DEPT CONNECTION AT FRONT OF BUILD... | $0 | $0 | Oct 5, 2018 |
| Jul 30, 2018 | 35342243M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED IN CELLAR A 3"WATER SERVICE FOR MORE THAN 150 FIRE SPR... | $0 | $0 | Sep 26, 2018 |
| Jul 11, 2018 | 35346078X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.I OBSERVED NO CONNECTION TO FIRE DEPARTMENT CONNECTION AT FRONT... | $0 | $0 | Sep 21, 2018 |
| Jun 8, 2018 | 35331758H | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED AT CELLAR LEVEL WATER SERVICE STORAGE ROOM, A 3"WATER... | $3,125 | $0 | Aug 22, 2018 |
| May 19, 2018 | 35331677X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT FRONTOF BUILDING NO FIRE DEPT CONNECTION INSTALLED A... | $0 | $0 | Nov 15, 2018 |
| May 15, 2018 | 32096882Z | RESOLVE | CLASS - 2 | B254;50A-50G:AS PER CLASS 2 (B254) 28.301.1 FAILURE TO MAINTAIN. 50A)RAINCAP INSTALLED ON CHIMNEY TERMINAL.BOILER EQU... | $625 | $0 | Aug 10, 2018 |
| May 4, 2018 | 35337899Z | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO #35322573R ISSUED ON 03/17/18 & TO FILE A CERT OF CORRE... | $1,250 | $0 | Aug 10, 2018 |
| May 3, 2018 | 35331802X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3; 27-345 NOTED: NO FIRE STOP WAS ... | $625 | $0 | Aug 22, 2018 |
| Mar 28, 2018 | 35325772N | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER. NOTED: AT FRONT OF BLDG,NO FIRE DEPT CONNECTION INSTALLED AS IN RE... | $3,125 | $0 | May 18, 2018 |
| Mar 17, 2018 | 35322573R | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.AT CELLAR LEVEL,A 3"WATER SERVICE FOR MORE THAN 150 FIRE SPRINK... | $3,125 | $0 | May 4, 2018 |
| Dec 2, 2017 | 35297554J | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED IN CELLAR A 3" WATER SERVICE FOR MORE THAN 150 FIRE SPRIN... | $2,500 | $0 | May 11, 2018 |
| Oct 20, 2017 | 35294419N | RESOLVE | CLASS - 1 | MISCELLANEOUS VIOLATIONS. RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT. OBSERVED IN LAUNDRY ROOM ON FIRST FLOOR ... | $4,000 | $0 | Dec 29, 2017 |
| Oct 20, 2017 | 35297207P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED AT FRONT OF BLDG NO FIRE DEPT CONNECTION INSTALED AS IN R... | $0 | $0 | Jun 8, 2018 |
| Oct 20, 2017 | 35294421M | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED IN CELLAR A 3'WATER SERVICE FOR MORE THAN 150 FIRE SPR... | $1,000 | $0 | Dec 29, 2017 |
| Oct 20, 2017 | 35294286Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3; 27-345. NOTED: OBSERVED AT CELL... | $250 | $0 | Dec 29, 2017 |
| May 1, 2017 | 35260282X | RESOLVE | CLASS - 2 | ELECTRICAL WORK W/O PERMIT. AT THE TIME OF MY INSPECTION I OBSERVED CIRCUIT BREAKER PANELS AT ENTRANCE END OF THE HAL... | $800 | $0 | Aug 11, 2017 |
| May 1, 2017 | 35253297N | RESOLVE | CLASS - 1 | SEC. 411.1 MISC VIOLATION: RESIDENTIAL FLEX USED ON COMMERCIAL EQUIPMENT. OBSERVED IN LAUNDRY ROOM ON 1ST FL RESIDENT... | $1,600 | $0 | Aug 11, 2017 |
| May 1, 2017 | 35260283H | RESOLVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,MATERIALS APPARATUS,DEVICE OR WIRING IN USE. AT THE TIME OF MY INSP... | $1,600 | $0 | Aug 11, 2017 |
| Dec 12, 2016 | 35222510L | RESOLVE | CLASS - 1 | SEC: FGC 411.1. RESIDENTIAL GAS FLEX ON COMMERCIAL EQUIPMENT OBSERVED ON 12/12/16 @ ABOVE ADDRESS RESIDENTIAL GAS FLE... | $800 | $0 | Feb 17, 2017 |
| Dec 12, 2016 | 35222509Y | RESOLVE | CLASS - 1 | SEC: FGC 408.2. DRIPS- FUTURE CONNECTS EXIST, DOWN STREAM OF APPLIANCE OBSERVED ON 12/12/16 FUTURE GAS CONNECTION FOU... | $0 | $0 | Feb 17, 2017 |
| Oct 21, 1993 | 34097563Z | RESOLVE | Non-Hazardous | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE COFO. COFO#60221. FROM FIRSTFLOOR: TWO FAMILIES SRO OFFICE AND LAUNDRY AND ... | $0 | $0 | Jan 14, 1994 |
| Mar 19, 1990 | 34036624Y | RESOLVE | Non-Hazardous | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C OF O. C OF O DOE NOT SHOWOFFICES ON 1ST FL. REMEDY: AMEND C OF O TO INDIC... | $250 | $0 | Jul 27, 1990 |