| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Feb 17, 2022 | 35569100L | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #35378322P ISSUED 3/31/21 AND FILE CERTIFI... | $1,250 | $0 | Sep 23, 2022 |
| Nov 3, 2021 | 35528738J | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/COMMISSIONER'S ORDER CONTAINED IN SUMMONS/V35378322P ISSUED3/31/21 &TO FILE C/C PURSUANT TO28-201... | $0 | $0 | May 13, 2022 |
| Aug 3, 2021 | 35535155N | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35378322P ISSUED ON 3/31/2021 AND TO F... | $3,125 | $0 | Nov 12, 2021 |
| May 24, 2021 | 35531273X | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/COMMISSIONER'S ORDER CONTAINED IN SUMMONS/V35378322P ISSUED 3/31/21&TO FILE C/C PURSUANT TO28-201... | $1,250 | $0 | Aug 6, 2021 |
| Mar 31, 2021 | 35378322P | RESOLVE | CLASS - 1 | ALTERED/CHANGE BUILDING OCCUPIED W/O A VALID C OF O AS PER 28-118.3.1-28-118.3.2. AT TIME OF INSPECTION,NOTED:AT CELL... | $2,500 | $0 | Jul 16, 2021 |
| May 3, 2019 | 35414823Z | RESOLVE | CLASS - 2 | FAILURE TO SECURE/SUPPORT RACEWAYS/CABLE ASSEMBLIES/BOXES/CARD BOARDS/FITTING. OBSERVED IN REAR COURTYARD RACEWAYS SU... | $0 | $0 | Jul 19, 2019 |
| May 3, 2019 | 35414822R | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE GROUND FAULT CIRCUIT INTERRUPTER(GFCI)PROTECTION. OBSERVED ON 2ND,3RD,& 5TH FLOORS DEFECTIVE & IMN... | $1,200 | $0 | Jul 19, 2019 |
| May 22, 2018 | 32096893Y | RESOLVE | CLASS - 2 | 50A-B. AS PER CLASS 2 (B254) 28-301.1, FAILURE TO MAINTAIN. (50A)BOILER/TANK ROOM USED FOR STORAGE OF COMBUSTIBLE MAT... | $312 | $0 | Jul 6, 2018 |
| Apr 20, 2017 | 35252977M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3;27-345. NOTED: FIRE STOP MISSINF IN ... | $250 | $0 | Jun 16, 2017 |
| Apr 20, 2017 | 35271656P | RESOLVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT MATERIALS,APPARATUS,DEVICE,APPLIANCE OR WIRING IN USE.OBSERVED EMT ... | $400 | $0 | Sep 1, 2017 |
| Apr 20, 2017 | 35252973P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER. OBSERVED ON 4/20/17@ ABOVE ADDRESS GAS PIPE IN BASEMENT NOT SUPPOR... | $250 | $0 | Jun 16, 2017 |
| Dec 15, 2016 | 35214499J | RESOLVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT OF BLDG DEPT RECORDS. AT CELLAR 1 SUPERS APT,BOILER & STORAGE NOW 2 OFFICE IN CELLAR C OF ... | $1,200 | $0 | Feb 3, 2017 |
| Dec 15, 2016 | 35222701Y | RESOLVE | CLASS - 2 | WORK W/OUT A PERMIT. OBSERVED ON 12/15/16 @ ABOVE ADDRESS GAS PIPING TO LAUNDRY EQUIPMENT REMOVED W/OUT ANY PERMITS N... | $0 | $0 | Feb 3, 2017 |
| Dec 15, 2016 | 35222702X | RESOLVE | CLASS - 2 | FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED. OBSERVED ON 12-15-16 PLUMBING & PC 107.4(2014 CODE)WORK REMOVE... | $500 | $0 | Feb 3, 2017 |
| Aug 13, 2013 | 35021495L | RESOLVE | CLASS - 2 | SEC. EC 408.4. VIOLATION OF THE ELECTRICAL TECHNICAL STANDARDS. NINE PANELS HAVE NOT BEEN PROVIDED W/DIRECTORIES. AT ... | $200 | $0 | May 9, 2014 |
| Aug 13, 2013 | 35021491Y | RESOLVE | CLASS - 2 | FAILURE TO PROTECT CONDUCTORS AGAINST OVERCURRENT PER EC. ELECTRICAL SERVICE SWITCH 400A FUSES ON 2 1/0 AWG WIRED. @ ... | $1,200 | $0 | May 9, 2014 |
| Aug 13, 2013 | 35021493H | RESOLVE | CLASS - 1 | VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. SERVICE SWITCH NOT LOCATED AT CLOSEST POINT OF ENTRY INTO BLDG.... | $400 | $0 | May 9, 2014 |
| Aug 13, 2013 | 35021494J | RESOLVE | CLASS - 3 | FAILURE TO CLOSE UNUSED OPENINGS (KNOCKOUTS) IN PANELS AND SEVICE EQUIPT. KO SEALS NOT PROVIDED TO CLOSE KNOCKOUT HOL... | $150 | $0 | May 9, 2014 |
| Aug 13, 2013 | 35021496N | RESOLVE | CLASS - 1 | FAILURE TO PROPERLY GROUP/LABEL DISCONNECTS. 400 AMP SERVICE SWITCH NOT IDENTIFIED AS SUCH. AT 11:55AM OBSERVED IN EL... | $250 | $0 | May 9, 2014 |
| Aug 13, 2013 | 35021497P | RESOLVE | CLASS - 1 | UNAPPROVED,UNSAFE,UNSAFE,UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS,MATERIALS,DEVICES,APPLIANCES AND WIRING IN USE. 20... | $400 | $0 | May 9, 2014 |
| Aug 13, 2013 | 35021499Z | RESOLVE | CLASS - 1 | SEC. EC 320.40. VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. ARMORED CABLE NOT PROPERLY TERMINATED INTO TOP ... | $400 | $0 | May 9, 2014 |
| Aug 13, 2013 | 35021489P | RESOLVE | CLASS - 2 | FAILURE TO PROPERLY SECURE/SUPPORT ELECTRICAL METALLIC TUBING (EMT). (EMT) ELECTRICAL METALLIC TUBING IN SERVICE ROOM... | $250 | $0 | May 9, 2014 |
| Aug 13, 2013 | 35021498R | RESOLVE | CLASS - 1 | SEC. EC 110.14A. VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS 400 AMP FUSED SERVICE SWITCH CONDUCTOR (LUGS) N... | $0 | $0 | May 9, 2014 |