ECB violations

Bronx High School Of Music, Bronx • Block 03247 • Lot 0070

214 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Mar 17, 2009 34761991H RESOLVE CLASS - 1 EXIT DOOR TO STAIRWAY B 4TH FLOOR TABLE & CHAIR TOTALLY OBSTRUCTION 1 DOOR ALSO EXIT DOORS ON STAGE IN AUDITORIUM PAD... $0 $0 Jul 10, 2009
Mar 17, 2009 34761993L RESOLVE CLASS - 2 ILLEGAL HARDWARE ON 1ST FLOOR STAIRWAY C & D EXIT VESTIBULE DOOR IN CAFETERIA HAVE KEY CYLINDER LOCKING DEVICE. REM: ... $0 $0 Jul 10, 2009
Mar 17, 2009 34761994N RESOLVE CLASS - 3 RE 34646955R EXTERIOR BRICK FACADE HAS BECOME POROUS AND ALLOWING RAI N WATER TO ENTER THE BLDG CAUSING INTERIOR DAMA... $0 $0 Jul 10, 2009
Mar 9, 2009 34761955K RESOLVE CLASS - 2 CORRIDOR WIDTH DECREASED BY OBSTRUCTIONS ON 3RD FLR STAIR 'A' TABLES,BARRIOR ALSO FRONT OF AUDITORIUM 1ST FLR SCANNIN... $0 $0 May 15, 2009
May 7, 2008 34646992X RESOLVE Hazardous REISSUE: 34592925P EXTERIOR ROOF HAS BECOME POROUS AND ALLOWING RAIN WATER INTO THE BLDG CAUSING INTERIOR DAMAGED IN ... $0 $0 Jun 27, 2008
May 7, 2008 34646994J RESOLVE Hazardous EXTERIOR BRICK FACADE HAS BECOME POROUS AND ALLOWING RAIN WATER INTO THE BLDG CAUSING INTERIOR DAMAGED AT STAIRCASE "... $0 $0 Jun 27, 2008
May 7, 2008 34646993H RESOLVE Hazardous REISSUE: 34592924N INTERIOR STAIRWAY DOOR IS MISSING LOCATED AT STAIRWAY "F" AT 2ND FLR LEVEL. REMEDY: REPLACE MISSIN... $0 $0 Jun 27, 2008
Apr 29, 2008 34646956Z RESOLVE Non-Hazardous REISSUE 345929236 EXIT PASSAGEWAY CORRIDOR WIDTH DECREASED BY REFRIGERATOR LOCATED IN THE CAFETERIA 1ST FL BY EXIT RE... $0 $0 Jun 27, 2008
Apr 29, 2008 34646957K RESOLVE Hazardous EXIT PASSAGEWAY IS PARTIALLY OBSTRUCTED IN 2 PLACES 1 STAIRWAY "B" & BY TABLES & CHAIRS 2 FRONT EXIT AUDITORIUM IS OB... $0 $0 Jun 27, 2008
Apr 29, 2008 34646955R RESOLVE Hazardous REISSUE 345922921 EXTERIOR BRICK FACADE HAS BECOME POROUS & ALLOWING RAIN WATER TO ENTER THE BLDG CAAUSING INTERIOR D... $0 $0 Jun 27, 2008
Apr 28, 2008 34646958M RESOLVE Hazardous EXTERIOR ROOF HAS BECOME POROUS & ALLOWING RAIN WATER INTO THE BLDG CAUSING INTERIOR DAMAGE IN RM 5 ABOVE THE REMEDY:... $0 $0 Jun 27, 2008
Aug 31, 2007 34592922J RESOLVE Non-Hazardous REISSUE#34517009J. PROVIDE PANIC HARDWARE WHERE REQUIRED BY LAW, 3RD FL GYMNASIUM FOUR EXIT DOOR W/O PANIC BARS (TWO ... $0 $0 Nov 16, 2007
Aug 31, 2007 34592923L RESOLVE Non-Hazardous REISSUE #34517011Z. EXIT PASSAGEWAY OR CORRIDOR REQUIRED WIDTH DECREASED BY OBSTRUCTION @ FIRST FL CAFETERIA PASSAGE ... $0 $0 Nov 16, 2007
Aug 31, 2007 34592921H RESOLVE Non-Hazardous WATER PENETRATION THROUGH EXTERIOR WALL INTO STAIRWAY #7 BETWEEN 4TH & 5TH FL. REMEDY: STOP WATER PENETRATION MAKE AL... $0 $0 Nov 16, 2007
Aug 31, 2007 34592925P RESOLVE Non-Hazardous WATER PENETRATION THROUGH ROOF INTO AUDITORIUM @ RIGHT SIDE ABOVE WINDOW NEXT TO BALCONY & @ BASEMENT EXIT VESTIBULES... $0 $0 Nov 16, 2007
Aug 31, 2007 34592924N RESOLVE Non-Hazardous MISSING DOOR @ 2ND FL STAIR "F". REMEDY: REPLACE MISSING DOOR (FPSC). $0 $0 Nov 16, 2007
Mar 29, 2006 34517015X RESOLVE Hazardous RE-ISSUE VIO# 34466467J. NOTED: MISSING DOOR GLASS PANELS AT 2ND FLR CORRIDOR SMOKE STOP DOOR NEAR RM 245 & 2ND FLR E... $0 $0 Jun 2, 2006
Mar 29, 2006 34517008H RESOLVE Hazardous RE-ISSUE VIO.# 34466459J. NOTED: ROOF LEAKING WATER AT EXIT # 7 (WALLS) BETWEEN FIFTH & FOURTH FLR. REMEDY: MAKE ALL ... $0 $0 Jun 2, 2006
Mar 29, 2006 34517009J RESOLVE Hazardous RE-ISSUE VIO.# 34466460R. NOTED: PROVIDE PANIC HARDWARE WHERE REQUIRED BY LAW, 3RD FLR GYMNASIUM FOUR EXIT DOORS W/O ... $0 $0 Jun 2, 2006
Mar 29, 2006 34517010R RESOLVE Hazardous RE-ISSUE VIO# 34466463M. NOTED: 1ST FLR, INNER PLAY-AREA AT EXIT # 5 GLAZED BLOCK WALL HAS AN OPEN VERTICAL CRACK APP... $0 $0 Jun 2, 2006
Mar 29, 2006 34517012K RESOLVE Hazardous NOTED: FIRESTOPPING IS MISSING AROUND PIPES WALL AT ELECTRICAL RM (BASEMENT LEVEL) REMEDY: INSTALL FIRESTOPPING. $0 $0 Jun 2, 2006
Mar 29, 2006 34517013M RESOLVE Hazardous RE-ISSUE VIO. 34466458H. NOTED: ROOF IS LEAKING WATER INTO ALL CLASSRMS AROUND PERIMETER OF BLDG. REMEDY: REPAIR ROOF. $0 $0 Jun 2, 2006
Mar 29, 2006 34517014Y RESOLVE Hazardous RE-ISSUE VIO# 34466466H. NOTED: 2ND FLR STAIR EXIT "F" & 1ST FLR EXIT "B" STAIR ARE MISSING DOORS. $0 $0 Jun 2, 2006
Mar 29, 2006 34517016H RESOLVE Hazardous NOTED: ROOF IS LEAKING WATER AT AUDITORIUM IN VARIOUS PLACES. REMEDY: REPAIR WATER LEAKS $0 $0 Jun 2, 2006
Mar 29, 2006 34517017J RESOLVE Hazardous NOTED: PLASTER IS SPALLING, PEELING AT VARIOUS PLACES AT AUDITORIUM. REMEDY: REPAIR PLASTER. $0 $0 Jun 2, 2006
Mar 29, 2006 34517018L RESOLVE Hazardous NOTED: DOORS ARE DEFECTIVE: LEANING AT 2ND FLR EXIT "F" VESTIBULE. REMEDY: REPAIR/REPLACE DOORS. $0 $0 Jun 2, 2006
Mar 29, 2006 34517019N RESOLVE Hazardous NOTED: AUDITORIUM BALCONY IS BEING USED AS A STORAGE W/BUCKETS, BOXES ELECTRICAL EQUIPMENTS, ETC. REMEDY: REMOVE ALL ... $0 $0 Jun 2, 2006
Mar 29, 2006 34517011Z RESOLVE Hazardous RE-ISSUE VIO# 34466464Y. NOTED: EXIT PASSAGEWAY OR CORRIDOR REQUIRED WIDTH DECREASED BY OBSTRUCTION AT 1ST FLR CAFETE... $0 $0 Jun 2, 2006
Feb 4, 2005 34466460R RESOLVE Non-Hazardous FAILURE TO PROVIDE PANIC HARDWARE WHERE REQUIRED BY LAW NOTED THIRD FLOOR GYMNASIUM FOUR EXIT DOORS WITHOUT PANIC BAR... $0 $0 Mar 18, 2005
Feb 4, 2005 34466461Z RESOLVE Non-Hazardous PANIC HARDWARE INOPERATING NOTED FIRST FLOOR AUDITORIUM REAR MIDDLE DOOR HAS BROKEN PANIC BAR.REMEDY:REPAIR OR REPLAC... $0 $0 Mar 18, 2005
Feb 4, 2005 34466467J RESOLVE Non-Hazardous FAILURE TO MAINTAIN BLDG DEFECTS NOTED:MISSING DOOR GLASS AT FIRST FLOOR MAIN ENTRY VESTIBULE DOOR, SECOND FLOOR CORR... $0 $0 Mar 18, 2005
Feb 4, 2005 34466466H RESOLVE Non-Hazardous FAILURE TO MAINTAIN BUILDING DEFECTS NOTED:SECOND FLOOR, STAIR EXIT F IS MISSING A DOOR. ALSO NOTED:FIRST FLOOR EXIT ... $0 $0 Mar 18, 2005
Feb 4, 2005 34466465X RESOLVE Non-Hazardous FAILURE TO MAINTAIN BLDG DEFECTS NOTED:SECOND FLOOR CORRIDOR SMOKE STOP DOOR NEAR ROOM 222 IS MISSING A DOOR CHECK. R... $0 $0 Mar 18, 2005
Feb 4, 2005 34466456Y RESOLVE Non-Hazardous REISSUE (34424143H)FAILURE TO MAINTAIN BLDG DEFECTS NOTED:FIRST FLOOR CAFETERIA, SOUTHSIDE CORNERS,ONE VERTICAL CRACK... $0 $0 Mar 18, 2005
Feb 4, 2005 34466457X RESOLVE Non-Hazardous REISSUE: (34424144J) FAILURE TO MAINTAIN BUILDING. DEFECT NOTED: BASEMENT BOILER ROOM FOUNDATION SOUTHEAST WALL, CONC... $0 $0 Mar 18, 2005
Feb 4, 2005 34466464Y RESOLVE Hazardous EXIT PASSAGEWAY OR CORRIDOR REQUIRED WIDTH DECREASED BY OBSTRUCTION. NOTED: FIRST FLOOR CAFETERIA PASSAGE TO EXIT 9 B... $0 $0 Mar 18, 2005
Feb 4, 2005 34466458H RESOLVE Non-Hazardous REISSUE: (34385667J) FAILURE TO MAINTAIN BUILDING. DEFECTS NOTED: ROOFLEAKING WATER INTO ALL CLASSROOMS AROUND PERIME... $0 $0 Mar 18, 2005
Feb 4, 2005 34466459J RESOLVE Non-Hazardous FAILURE TO MAINTAIN BUILDING DEFECTS NOTED ROOF LEADING WATER INTO BELOW CLASSROOM 507 @ TWO PLACES ALSO NOTED EXIT 7... $0 $0 Mar 18, 2005
Feb 4, 2005 34466463M RESOLVE Non-Hazardous FAILURE TO MAINTAIN BUILDING. DEFECT NOTED: FIRST FLOOR, INNER PLAYARDAT EXIT 5, GLAZED BLOCK WALL HAS AN OPEN VERTIC... $0 $0 Mar 18, 2005
Feb 4, 2005 34466462K RESOLVE Non-Hazardous FAILURE TO MAINTAIN BUILDING. DEFECT NOTED: THIRD FLOOR CORRIDOR SMOKESTOP DOOR NEAR ROOM 314 IS MISSING A DOOR CHECK... $0 $0 Mar 18, 2005
Jan 7, 2004 34424144J RESOLVE Non-Hazardous REISSUE FAILURE TO MAINTAIN DEFECT NOTED CONCRETE WALL COLLAPSED APPROX 5'X 3' EXPOSING REBAR SURROUNDING WALL NOE BU... $0 $0 Mar 26, 2004
Jan 7, 2004 34424143H RESOLVE Non-Hazardous REISSUE FAILURE TO MAINTAIN DEFECT NOTE CRACKED & MISSING GLAZED BRICKS BRICKS ARE LOOSE & FALLING OUT LOCATION:CAFET... $0 $0 Mar 26, 2004
Feb 27, 2003 34385667J RESOLVE Non-Hazardous FAILURE TO MAINTAIN. DEFECT ROOF LEAKS CAUSING SEVERE WATER DAMAGE TO INTER OF CLASSROOMS. LOCATION ENTIRE PEREMITER ... $0 $0 Jul 18, 2003
Feb 27, 2003 34385666H RESOLVE Non-Hazardous FAILURE TO MAINTAIN. DEFECT GLAZED BRICKS & BLOCKS CRACKED MISSING MORTAR BLOCKS ARE BECOMING LOOSE. VARIOUS AREAS. L... $0 $0 Jul 18, 2003
Feb 27, 2003 34385665X RESOLVE Non-Hazardous FAILURE TO MAINTAIN: DEFECT WATER PENETRATION THRU FOUNDATION WALLS HAS CAUSED CONCRETE WALL TO SPALL BULDGE & COLLAP... $0 $0 Jul 18, 2003
Feb 26, 2002 34316780M RESOLVE Non-Hazardous FAILURE TO PROVIDE PANIC HARDWARE AFTER REQUIRED BY LAW AT 3RD FL GYM REMEDY PROVIDE PANIC HARDWARE $0 $0 May 3, 2002
Feb 26, 2002 34316782X RESOLVE Non-Hazardous USE OF ILLEGAL HARDWARE AT VARIOUS LOCATIONS THROUGHOUT SCHOOL REMEDY REMOVE ILLEGAL HARDWARE $0 $0 May 3, 2002
Feb 26, 2002 34316781Y RESOLVE Non-Hazardous REISSUE FAILURE TO MAINTAIN DEFECT IS WINDOWS ARE DEFECTIVE DUE TO BALANCES THROUGHOUT SCHOOL REMEDY MAKE ALL NECESSA... $0 $0 May 3, 2002
Mar 14, 2001 34282806Z RESOLVE Non-Hazardous FAILURE TO MAINTAIN.DEFECT IS ROOF LEAKS AT HALLWAY 3FL,ADJACENT TO ROOM #349.REM:REPAIR LEAK AT ROOF. $0 $0 Jul 20, 2001
Mar 14, 2001 34282811N RESOLVE Non-Hazardous FAILURE TO MAINTAIN DEFECT IS ROOF LEAKS AND WATER BACKUPS FROM DEFECTIVE LEADERS AND GUTTERS HALLWAY KITCHEN ROOM RO... $0 $0 Sep 21, 2001