Issued Violation Status Severity Description Penalty Balance due Hearing
Apr 18, 2023 39084102P RESOLVE CLASS - 2 EXIT DOOR NOT SELF-CLOSING. NOTED: AT TIME OF INSPECTION - APT ENTRY DOOR OBSERVED NOT SELF CLOSING FOR APTS 1B & 4.,... $312 $0 Jan 29, 2024
Apr 18, 2023 39084101N RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: 1) AT 1ST FLR VESTIBULE LANDING - FLR OBSERVED OFFSET B... $1,250 $0 Jan 29, 2024
Apr 18, 2023 39084100L RESOLVE CLASS - 3 W/O A PERMIT. NOTED: AT 1ST FLR COMMON AREA - SOFFITT BENEATH COMMON INTERIOR STAIRS: WATER & WASTE LINES INSTALLED F... $125 $0 Jan 29, 2024
Apr 18, 2023 39084099N RESOLVE CLASS - 1 ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID C-OF-O. NOTED: ALT 1 JOB #220723545 WHICH PROPOSES TO CONVERT 1 APT... $2,500 $0 Apr 15, 2024
Apr 9, 2019 37014643L RESOLVE CLASS - 2 FAILURE TO COMPLY WITH COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLA ION #32097144L ISSUED ON 6/26/2018 AND TO FILE ... $1,280 $0 Jun 7, 2019
Jun 26, 2018 32097144L RESOLVE CLASS - 2 36. AS PER CLASS2 (B254)28-301.1 FAILURE TO MAINTAIN. (36)BOILER NOT REGISTERED 1 PEERLESS CYCLONTEC SERIAL# 106905A-... $625 $0 Aug 17, 2018
Jun 26, 2018 32097145N RESOLVE CLASS - 1 CEASE USE. 50,51. AS PER CLASS 1 (B154)28-301.1 FAILURE TO MAINTAIN. (51)HAZARDOUS CONDITION. BOILER SEALED 1 PEERLES... $3,125 $0 Aug 17, 2018
Aug 10, 2017 32091509H RESOLVE CLASS - 2 B254,36. 36-AS PER CLASS 254-36 BOILER NOT REGISTER AS PER DOB RECORDSCORRECT ALL VIOLATING CONDITIONS AND SUBMIT A C... $530 $0 Sep 29, 2017
Aug 10, 2017 32091508X RESOLVE CLASS - 2 B254,36. 36-AS PER CLASS 254-36 BOILER NOT REGISTER AS PER DOB RECORDSCORRECT ALL VIOLATING CONDITIONS AND SUBMIT A C... $530 $0 Sep 29, 2017
Aug 10, 2017 32091510P RESOLVE CLASS - 2 36-AS PER CLASS 254-36 BOILER NOT REGISTER AS PER DOB RECORDS CORRECT ALL VIO CONDITION & SUMBIT A CERT OF CORRECTION. $530 $0 Sep 29, 2017
Jul 10, 2014 35097080K RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. DEFECT NOTED: AT FRONT FACADE OF BLDG,EXPOSURE 1 & EXPOSURE 2,LEFT... $250 $0 Aug 29, 2014
Apr 26, 2012 34937033K RESOLVE CLASS - 1 FAILURE TO MAINTAIN INTERIOR BLDG DEFECT AT APT #2 THE DRAIN TRAP IN THE BTRM BROKE THERE IS WATER LEAKS CAUSING DAMA... $1,000 $0 Jun 29, 2012
Aug 27, 2011 32071235L RESOLVE CLASS - 2 B254,15,21C,24B,32A,34B,50A,B,C. 50A- NO 2ND LOW WATER CUT OFF FOUND. 50B- RELIEF VALVE MISSING. 50C- DRAFT REGULATOR... $0 $0 Oct 21, 2011
Mar 25, 2011 32070578Z RESOLVE CLASS - 2 B254/16/48A/50A/50B/50C/50A-SOOT ON BOILER & BURNER/50B-ANTISYPHON & SHUT OFF MISSING ON OIL SUCTION LINE/50C-SUPPORT... $250 $0 May 20, 2011
Mar 17, 2011 34889983K RESOLVE CLASS - 2 FAILURE TO MAINTAIN ADEQUATE HOUSEKEEPING PER SECTION REQUIREMENTS. CONSTRUCTION DEBRIS OBSERVED AT INTERIOR COURTYAR... $0 $0 May 6, 2011
Oct 5, 2010 32069735P RESOLVE CLASS - 2 50A-NO DARKIT ON OIL PUMP 50B-OIL LEAK AT BU;RNER,50C-SOOT ON BURNER,50D-DISCHARAGE ON RELIEF VALVE MUJST BE BRACED,5... $500 $0 Mar 4, 2011
Jun 21, 2010 32069002H RESOLVE CLASS - 2 15 16 32A 48A 50 50ABCD 50-BOILER INOPERATIVE FOUND OIL BURNER RELAY OUT SHUT DOWN BURNER DUE TO IN COMPLETE COMBUSTI... $500 $0 Aug 20, 2010
Feb 14, 2010 34829477N RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. BMT APT (B3) NORTHWEST BEDROOM APPROX 8'X6' CEILING PLASTER RE... $1,000 $0 Jul 9, 2010
Oct 27, 2009 34787567Y RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER DEFECTS NOTED @ VESTIBULE SECTION OF MARBLE WALL (APPROX 4X2) CAME ... $2,500 $0 Dec 18, 2009
Oct 27, 2009 34805193P RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN A CODE COMPLAINT MANNER NOTED (1)@ ENTRANCE FOYER NORTHWALL MARBLE ORNAMENTAL CLADING... $5,000 $0 Dec 18, 2009
Jul 14, 2008 32060255P RESOLVE CLASS - 3 B354,16,21A,32A,50,50A,50B,50C,50D. 50 OIL BURNER MISSING DAR KIT. 50APRESTROL MANIFOLD TO BE INCREASED TO ONE INCH 4... $500 $0 Sep 5, 2008
Feb 27, 2008 32050349R RESOLVE Hazardous 40A,3A,50A,48A.3A-NEED TO REPLACE FLUE PIPE FROM CHIMNEY TO BOILER.50A-NEED TO INSTALL BACKFLOW PREVENTOR ON WATER FE... $400 $0 Jul 18, 2008
Mar 27, 2007 34569699K RESOLVE Hazardous FAILURE TO MAINTAIN EXT BLD WALL.NOTE:AT FRONT FACADE AT PARAPET LEFTSIDE,VERTICAL CRACKS IN BRICK WORK,W/DISPLACED B... $2,000 $0 Sep 28, 2007
Nov 8, 2006 34540487J RESOLVE Hazardous FAILURE TO MAINTAIN BLDG HAZARDOUS EXTERIOR FACADE-EAST PARAPET(FRONT)CRACK APPROX 4'- 0" VERTICLE CRACK SOUTH FACADE... $800 $0 Dec 22, 2006
Jun 28, 2006 34530022K RESOLVE Non-Hazardous FAILURE TO MAINTAIN DEFECTS ARE VERTICAL & STEP CRACKS IN MANY VARIOUSAREAS OF EXTERIOR WALLS THRU OUT STRUCTURE. RUS... $350 $0 Aug 18, 2006
Nov 1, 2004 32046029X RESOLVE Non-Hazardous B4A/B8J/50A/50B/50B/ B8J-FAILURE TO FILE ANNUAL BOILER INSPECTION FOR THE YEAR 2003 50A-PRESSURE RELIEF VALVE NOT PIP... $10,000 $0 Dec 17, 2004
Jan 6, 2003 32040853R RESOLVE Non-Hazardous 36/50A/50B. 50A SAFETY VALVE TO BE PIPED DOWN. 50B SYPITONS PIGTAILS FOR PRESSURE CONTROLS. $5,000 $0 Feb 21, 2003
Nov 28, 2001 32026241P RESOLVE Non-Hazardous 49A-PROVIDE AND INSTALL ON BOILER MANUFACTURERS DATA RATING PLATE FOR PEERLESS BOILER 49B-TO SEAL AROUND FLUE PIPE $0 $0 Jan 18, 2002