ECB violations
3598-3600 Jerome Avenue, Bronx • Block 03329 • Lot 0085
28 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Oct 28, 2025 | 39165132K | RESOLVE | CLASS - 1 | CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO... | $1,250 | $1,250 | Jan 2, 2026 |
| Oct 28, 2025 | 39165149R | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $1,280 | $1,280 | Aug 3, 2026 |
| Oct 28, 2025 | 39165150Y | RESOLVE | CLASS - 1 | ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED IT EQUIPMENT INSTALLED IN AN ELEC... | $0 | $0 | Jul 13, 2026 |
| Oct 28, 2025 | 39165151X | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLEGAL HARDWARE ON MECHANICAL ROOM DOOR. POTENTIAL HAZARD., R... | $1,250 | $630 | Jan 2, 2026 |
| Oct 28, 2025 | 39165148P | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED EXCESSIVE LEAK ON BOILER. POTENTIAL HAZARD., REPAIR A... | $1,250 | $630 | Jan 2, 2026 |
| Oct 28, 2025 | 39165036K | ACTIVE | CLASS - 2 | I FOUND ONE ROCKMILL MP-100 STEAM . BOILER WITH NEW FRESH AIR DUCT NOT FIRE RATED AND A FRESH AIR FAN WITH NO AIR PRO... | $1,250 | $630 | Jan 2, 2026 |
| Sep 21, 2023 | 38274978K | RESOLVE | CLASS - 1 | 81-Y-10C/U; 16-J-1C/U; 21-M-3C/U; 99-M-7; 64-B-7. C/U 81-DAMAGE PISTONSEAT MUST REPLACE IMMEDIATELY TO STOP THE OIL L... | $1,250 | $0 | Dec 1, 2023 |
| May 4, 2023 | 39085505Y | RESOLVE | CLASS - 1 | I OBSERVED IN THE 2ND FLOOR ELECTRICAL CLOSET THE INSTALLATION WIRING,NETWORK AND DATA EQUIPMENT. NO EQUIPMENT OTHER ... | $1,200 | $0 | Jul 21, 2023 |
| May 4, 2023 | 39085503K | RESOLVE | CLASS - 2 | I OBSERVED IN THE KITCHEN THE EQUIPMENT DISCONNECTS FOR THE WARMER OVENS MADE INACCESSIBLE BY THE FIXED APPLIANCES. A... | $0 | $0 | Jul 21, 2023 |
| May 4, 2023 | 39085442X | RESOLVE | CLASS - 2 | AS PER ONE FUEL OIL BURNING, ROCKMILLS MP 100: TWO BAROMETRIC DAMPERS INSTALLED IN FLUE PIPING-FRONT TUBE DOOR CORROD... | $0 | $0 | Jul 21, 2023 |
| May 4, 2023 | 39085506X | RESOLVE | CLASS - 2 | I OBSERVED IN THE BASEMENT FROM THE BOILER ROOM SWITCH JUNCTION BOX THE INSTALLATION OF AN EMT RACEWAY THROUGH THE AD... | $0 | $0 | Jul 21, 2023 |
| May 4, 2023 | 39085504M | RESOLVE | CLASS - 1 | I OBSERVED CONDUITS, WIRING AND DISCONNECT SWITCHES FOR AN EXHAUST FAN, A FOOD PRESS, A STEAM WASHER, GFCI RECEPTACLE... | $0 | $0 | Jul 21, 2023 |
| Mar 20, 2023 | 39081764K | RESOLVE | CLASS - 2 | OBSERVED EXTERIOR WALL AT EXPOSURE # 02 INSTATE OF DISREPAIR CONDITIONS WITH VERTICAL / STEP CRACKS & SPALLING BRICKS... | $0 | $0 | Jun 2, 2023 |
| Sep 24, 2021 | 39048105M | RESOLVE | CLASS - 2 | BURNER ELECTRICAL COVER MISSING-NO DRAIN AT BACK FLOW VALVE-NO BODY DRAIN ON SAFETY VALVE-BROKEN DISCHARGE PIPE ON SU... | $0 | $0 | Nov 19, 2021 |
| Sep 1, 2021 | 39046891J | RESOLVE | CLASS - 1 | DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED (CU). WATER LEAK IN THE PIT. PROVIDE CURRENT ELEVATOR PROVIDE... | $1,250 | $0 | Oct 29, 2021 |
| Aug 26, 2021 | 35592055R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED BASEMENT CELLAR IN BOILER ROOM NO FRESH AIR INTAKER (V... | $312 | $0 | Jun 24, 2022 |
| Jan 5, 2021 | 39034278N | RESOLVE | CLASS - 2 | EXPOSED WIRING AT ELECTRICAL BOX, CONTROL COVER MISSING ON BURNER-LUGS MISSING FROM FRONT TUBE DOOR AND REAR BOILER A... | $0 | $0 | Feb 19, 2021 |
| Apr 25, 2019 | 38269428J | RESOLVE | CLASS - 1 | CEASE USE 05.H.10,70.Z.09,35.M.07;(1 CEASE ITEM 05-H-10)REPAIR AND CONTATC NYC DOB FOR RESTORE TO SERVICE INSPECTION ... | $1,250 | $0 | Jul 12, 2019 |
| Apr 22, 2019 | 35415223J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLD. IN CODE COMPLIANT MANNER.OBSERVED ON THE ROOFGAS PIPING TO ALL MVAC SYSTEMS UNPAINTED AND TH... | $0 | $0 | Jun 7, 2019 |
| Apr 9, 2018 | 35307662N | RESOLVE | CLASS - 2 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND /OR APPROVED AMENDMENTS FOR ALT II JOB#220631813 AT TIME... | $620 | $0 | Jun 15, 2018 |
| Jul 13, 2007 | 38168053J | RESOLVE | Non-Hazardous | 66O2/67O2/68O2/39O2/34R9/59I10/16J1/10H11/17H11/66Z9/25#6/39R9/41Q3/39R9/ 34 IN OUTLET 39 PIPE ACROSS DOOR 39 VENT TO... | $350 | $0 | Dec 7, 2007 |
| Nov 14, 2000 | 38109778R | RESOLVE | Non-Hazardous | 9H12-16H12-18P17-57Y2-73U16 - PROVIDE ACCESS FOR DROPKEY TO STOP OF CAR INCORRECT CITY I.D. # THE CORRECT NUMBER IS 4... | $350 | $0 | Oct 24, 2003 |
| Sep 2, 1997 | 38063477M | RESOLVE | Non-Hazardous | 09H,16H,55M,54U,37U,74M, 74M-PROVIDE CAPACITY PLATE. | $0 | $0 | Oct 24, 1997 |
| Jul 10, 1997 | 34155009Y | RESOLVE | Non-Hazardous | NO EQUIPMENT USE PERMITS FOR 5 MECHANICAL AIR CONDITIONER UNITS LOCATED AT THE REAR OF THE 1ST FLOOR SPACE.(YORK BRAN... | $0 | $0 | Sep 12, 1997 |
| Jul 27, 1995 | 38050470R | RESOLVE | Non-Hazardous | 14M,02L,57O,74#.74-PERFORM PRESURE TOST AND FILE ELEV.3 FORM WITH THIS DEPT. | $0 | $0 | Sep 8, 1995 |
| Jan 14, 1992 | 34067464X | RESOLVE | Non-Hazardous | ALTERED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY ALT94/84. REMEDY:OBTAIN A COFO OR DISCONTINUE ILLE... | $0 | $0 | Jun 19, 1992 |
| Dec 4, 1990 | 34044619J | RESOLVE | Non-Hazardous | FAILURE TO HAVE APPROVED PA PLANS AVAILABLE FOR INSPECTION. REMEDY PROVIDE APPROVED PA PLANS FOR INSPECTION | $115 | $0 | May 24, 1991 |
| Mar 22, 1990 | 34038904H | RESOLVE | Hazardous | FAILURE TO HAVE APPROVED PA PLANS AVIALABLE FOR INSPECTION. REMEDY: PROVIDE APPROVED PA PLANS. | $0 | $0 | May 4, 1990 |