ECB violations

3136 Perry Avenue, Bronx • Block 03345 • Lot 0011

32 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Dec 22, 2025 39171178R ACTIVE CLASS - 1 1) THE GOVERNOR ROPE IS RUBBING THE STRUCTURE IN THE OVERHEAD. 2) THE DOOR ZONE RESTRICTOR IS NOT WORKING (SOMEONE PU... $1,250 $1,250 Mar 6, 2026
Jul 8, 2025 35693998P ACTIVE CLASS - 1 FAILURE TO MAINTAIN BLDG EXTERIOR FACADE AND APPURTENANCES.-NOTE: AT TIME OF INSPECTION I OBSERVED EXP #1 WEST-INADEQ... $5,000 $0 Sep 19, 2025
Feb 19, 2021 39036483L RESOLVE CLASS - 1 CEASE USE VIOLATION ISSUED. ITEMS 1/ CAR DOOR RESTRICTOR , 2/ CAR GOVERNOR CABLE SAFETY SWITCH REMOVE, 3/ CAR FLOOR T... $312 $0 Nov 26, 2021
Feb 4, 2021 39035844N RESOLVE CLASS - 2 EMERGENCY PHONE INOPERATIVE, REPAIR. $0 $0 May 21, 2021
Nov 9, 2020 39031730R RESOLVE CLASS - 2 STOP LEFT ON BAROMETRIC DAMPER-PIPING FOR PRESSURE CONTROLS UNDERSIZED-OIL LEAK AT BURNER-NO SIGN FOR OIL TANK ROOM-C... $310 $0 Jan 15, 2021
Oct 15, 2020 39030434H RESOLVE CLASS - 2 PHONE INOPERATIVE, NO ACCESS TO MACHINE ROOM AND OVERHEAD. $1,562 $0 Dec 4, 2020
Jan 9, 2020 35460802R RESOLVE CLASS - 2 UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. USE IF... $800 $0 Oct 9, 2020
Jan 9, 2020 35460803Z RESOLVE CLASS - 2 ELECTRICAL WORK WITHOUT A PERMIT. THROUGHOUT THE ENTIRE HALLWAY FLOORS 1-6 INSTALLATION OF NEW FIXTURES. REM: OBTAIN ... $800 $0 Oct 9, 2020
Jan 24, 2017 38252643L RESOLVE CLASS - 2 2L10,37P16,40P16,5M7. 5M70CAB DOOR RESTRICTOR IS MISSING(PROVIDE) $0 $0 Mar 17, 2017
Jul 19, 2011 38217485L RESOLVE CLASS - 2 14M11 37T07 56Y13 60Q03 67M07 72M07 37T07-PROVIDE SIGN FOR OVERHEAD SHEAVE ROOM DOOR 67M-PROVIDE COMMUNICATION IN CAR... $500 $0 Nov 22, 2011
Apr 26, 2011 38216206P RESOLVE CLASS - 2 14M07,24X10,37T07,52B14,56Y13,60Q03,72M07.(24X10)REPAIR HALL POSITION INDICATOR.(37T07)PROVIDE SIGN FOR OVERHEAD SHEA... $0 $0 Jun 17, 2011
Feb 8, 2011 38215097K RESOLVE CLASS - 2 08V01 10B07 16M07 24X10 26D06 35Q03 37T07 37Q03 39X10 45Q03 56Y13 60Q03 71X10 71Q03 77X10 99U15. 10B07- PROVIDE ADDIT... $0 $0 Apr 1, 2011
Jan 24, 2011 32070206H RESOLVE CLASS - 2 B254,4A,48A,50A,B,C,D. 50A- OIL LEAK AT BURNER. 50B- FRESH AIR FAN NOTINTERLOCKED W/BURNER. 50C- NO SAIL SWITCH ON FR... $0 $0 Mar 18, 2011
Oct 16, 2010 34884225Z RESOLVE CLASS - 2 FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER TO FILE A C/C W/THE DOB FOR OPEN ECB NOV #S 34851412N,3443309N,32065626H... $800 $0 Jan 14, 2011
Oct 16, 2010 34883624L RESOLVE CLASS - 1 FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY.@ 1ST STORY REAR YARD AIR CONDITIONING UNIT PROTRUDING FROM WINDOW OF... $3,000 $0 Jan 14, 2011
Aug 11, 2010 34851412N RESOLVE CLASS - 1 FAIL TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. AT 1ST FLOOR APT "C" THERE IS AN A/C AT REAR BEDROOM FIRE ESCAPE WINDOW... $0 $0 Oct 1, 2010
Aug 11, 2010 34851414R RESOLVE CLASS - 2 WORK W.O A PERMIT. NOTED: AT REAR OF BLDG A GARDEN WAS CREATED. THE GARDEN IS APPROX 8'X 20' & IS DIRECTLY UNDERNEATH... $400 $0 Nov 12, 2010
Aug 11, 2010 34851413P RESOLVE CLASS - 2 FAIL TO MAINTAIN EXTERIOR OF BLDG. DEFECTS AT EXP 3 NORTH REAR FIRE ESCAPE THE DROP LADDER HAS BEEN UNHOOKED & HAS BE... $250 $0 Nov 12, 2010
Aug 10, 2010 32069145P RESOLVE CLASS - 2 28-301.1 2(B254),50,50A-D.(50)EXCESSIVE SOOT ON BURNER & FLOOR @ FRONT & REAR OF BOILER,SERVICE & ADJUST BURNER FOR M... $500 $0 Nov 12, 2010
May 18, 2010 32067010Z RESOLVE CLASS - 2 34A,50,50A,B,C,D. 50- AIR GAP & DISCHARGE PIPE MISSING OR BACK FLOW PREVENTOR. 50A- DISCHARGE PIPE MISSING OR 530 C V... $250 $0 Jul 16, 2010
Apr 5, 2010 34832957J RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. VERTICAL & HORIZONTAL CRACK OBSERVED AT BOILER ROOM WALL (NORT... $500 $0 Jun 11, 2010
Mar 9, 2010 38209516P RESOLVE CLASS - 1 97X10.97X10 ONLY ELEVATOR IN BLDG IS OUT OF SERVICE THERBY CREATING CONDITION DANGEROUS TO HUMAN LIFE AS PER 1RCNY 11... $5,000 $0 Apr 30, 2010
Feb 23, 2010 38208389R RESOLVE CLASS - 1 97X10.97X10 ONLY ELEVATOR IN BLDG OUT OF SERVICE THEREBY CREATING CONDITION DANGEROUS TO HUMAN LIFE REPAIR IMMEDIATEL... $5,000 $0 Apr 16, 2010
Jan 27, 2009 32065626H RESOLVE CLASS - 3 301.1,B354,50. 50 PRESSURE ROLES MUST BE SEPARATED EACH HAVING ITS OWNPIGTAIL. $500 $0 Mar 20, 2009
Jun 16, 2008 34647402L RESOLVE Hazardous SIDEWALK SHED NOT ADEQUATELY MAINTAINED SIDE DECK ENCLOSURE MISSING. AT TIME OF INSPECTION MISSING SIDE DECK ENCLOSUR... $1,000 $0 Sep 19, 2008
Jun 12, 2008 34647360M RESOLVE Hazardous NO SIDEWALK SHED.SECTION OF SIDEWALK SHED MISSING @ EXPOSURE #1 FRONT/NOT PROTECTING PUBLIC FROM CONSTRUCTION OPERATI... $2,000 $0 Sep 19, 2008
Jan 18, 2008 32050344H RESOLVE Non-Hazardous 34A,50A,B.50A-NEED TO REPLACE FRONT GASKET ON BOILER DOOR ON LEFT SIDE.50B-NEED TO INSTALL PIGTAIL(BRASS) ON ALL CONT... $350 $0 Aug 6, 2009
Jan 11, 2008 32055232X RESOLVE Non-Hazardous 16/ 24B/ 32A/ 34A,B/ 45A,B/ 50/ 50A/ 50B/ 50C/ 50D/ 50E/ 50F/ 50G/ 24BEXTERIOR DOOR MISSING REMOTE CONTROL SWITCH 34A... $350 $0 Aug 6, 2009
Oct 24, 2007 38179276K RESOLVE Non-Hazardous 8V1/27H11/21B11/43H9/43H11/51H11/55Y13/52Y2/32O2/33O2/38O2/38O2/38O2/39O2/66O2/67O2/68O2/67O2/71K11/.27-CAR DOOR ROLL... $0 $0 Aug 6, 2009
May 25, 2004 34433309N RESOLVE Hazardous SIDEWALK SHED DOES NOT MEET DOB SPECIFICATION A) NO LIGHTS PRESENT ON A 100 LF SIDEWALK SHED. REMEDY: CONFORM SHED TO... $1,000 $0 Apr 7, 2006
May 25, 2004 34433310K RESOLVE Non-Hazardous WORK WITHOUT PERMITS: HAVING CONST. AN 100 LF SIDE WALK FOR FACADE REPAIRS. LOCATION: FRONT FACADE. REMEDY: OBTAIN PE... $500 $0 Apr 7, 2006
Mar 1, 2004 34423656Z RESOLVE Non-Hazardous FAILURE TO MAINTAIN EXTERIOR BUILDING WALL DEFECT IS(1)AT THE PARAPET WALL COPING STONE IS SPALLING AND DEFECTIVE THR... $800 $0 May 7, 2004