| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 6, 2026 | 39187487R | ACTIVE | CLASS - 2 | CLASS 2 ITEMS: EMERGENCY TWO-WAY COMMUNICATION SYSTEM IS INOPERATIVE AND DOES NOT PROVIDE COMMUNICATION WITH AN AUTHO... | $625 | $625 | Jan 29, 2027 |
| Dec 16, 2025 | 39170654Y | ACTIVE | CLASS - 1 | RESPONDING ON A 311 ELEVATOR COMPLAINT, UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT -OF -SERVICE , CREATING A HAZA... | $6,250 | $0 | Feb 20, 2026 |
| Aug 13, 2025 | 39157008N | ACTIVE | CLASS - 1 | CLASS 1:FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. U... | $1,250 | $0 | Mar 6, 2026 |
| Jul 18, 2025 | 35718238K | ACTIVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY.-NOTE: AT TIME OF INSPECTION, I OBSERVED OBJECTS OBSTRUCTING FIRE ESC... | $1,250 | $0 | Oct 3, 2025 |
| Jul 18, 2025 | 35718237Z | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG EXTERIOR FACADE AND APPURTENANCES. NOTE: AT TIME OF INSPECTION, I OBSERVED EXP #1 EAST-CRACK... | $5,000 | $0 | Apr 2, 2026 |
| Jun 4, 2025 | 39149976K | RESOLVE | CLASS - 2 | AGGRAVATED II CONDITION: RESPONDENT HAS A HISTORY OF FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDERS. RESPONDENT FAI... | $0 | $0 | Aug 29, 2025 |
| Jun 3, 2025 | 39149698J | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. CLASS 1 ITEM: 1) FIRE SERVICE, BOTH PHASES INOPERATIVE, REPAIR... | $1,250 | $0 | Aug 15, 2025 |
| May 5, 2025 | 39147063R | ACTIVE | CLASS - 1 | RESPONDING TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION, DEVICE IS FOUND OUT OF SERVICE, AS PER 1RCNY 11-02, THIS DEV... | $1,250 | $0 | Jul 18, 2025 |
| Feb 6, 2025 | 39137700L | ACTIVE | CLASS - 1 | CEASE USE ITEMS: F1-10A LINE FUSE AND F7-3A FUSE ARE BYPASSED. CORRECT ISSUES AND REPLACE. CLASS 2 ITEMS IN-CAR COMMU... | $1,250 | $0 | Jul 18, 2025 |
| Jan 27, 2025 | 39136530N | RESOLVE | CLASS - 2 | FOUND A FEDERAL FST90 BOILER MISSING GUARD ON OIL PUMP/BACKFLOW MISSING AIR GAP AND DRAIN PIPE/SAFETY VALVE MISSING B... | $0 | $0 | May 30, 2025 |
| Jan 24, 2025 | 35689829M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG EXTERIOR FACADE AND APPURTENANCES. NOTE: AT TIME OF INSPECTION, I OBSERVED EXP #1 EAST-BROKE... | $2,500 | $0 | May 30, 2025 |
| Jan 24, 2025 | 35689830J | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTE: AT TIME OF INSPECTION, I OBSERVED EXP #1 EAST, #2 SOUTH, #4 NO... | $1,250 | $0 | May 30, 2025 |
| Jun 12, 2024 | 39116606M | ACTIVE | CLASS - 1 | RESPONDING TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION OF SINGLE CAR BUILDING, A CEASE USE VIOLATION ISSUED, 1/ REVE... | $1,250 | $0 | Aug 16, 2024 |
| Apr 30, 2024 | 39113060X | ACTIVE | CLASS - 1 | CEASE USE ITEMS: DAMAGED/INOPERATIVE IN CAR STOP SWITCH. 2) INOEPRATIVE ZONE LOCK RESTRICTOR. CLASS 2 ITEMS: INOEPRAT... | $1,250 | $0 | Jul 5, 2024 |
| Aug 21, 2023 | 39093016N | ACTIVE | CLASS - 2 | FAILURE TO CERTIFY: FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPA... | $1,250 | $0 | Nov 17, 2023 |
| Aug 21, 2023 | 39093024N | ACTIVE | CLASS - 2 | FAILURE TO CERTIFY: FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPA... | $1,250 | $0 | Nov 17, 2023 |
| Jun 26, 2023 | 39089161H | ACTIVE | CLASS - 2 | IN CAR COMMUNICATION INOPERATIVE, REPAIR. PIT DIRTY, CLEAN. PIT LIGHT INOPERATIVE, REPAIR. CAR FLOOR TO LANDING SILL ... | $625 | $0 | Oct 6, 2023 |
| Nov 2, 2022 | 39073218N | RESOLVE | CLASS - 1 | CEASE USE VIOLATION ISSUED ITEMS, 1) CAR DOOR RESTRICTOR ALTERED MAKING NOT TO WORK, 2) ALL ALARM SYSTEM ON DEVICE NO... | $1,250 | $0 | Jan 27, 2023 |
| Nov 23, 2021 | 35635156N | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANCE.NOTE AT THE TIME OF INSPECTION THE EXTERIOR WALL CONDITIONS CERTIFICA... | $500 | $0 | Mar 25, 2022 |
| Oct 17, 2019 | 35365710Y | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY.NOTE:NORTH ELEVATION FIRE ESCAPE HAS OBJECTS AND PLANTS ON THE 3RD,4T... | $1,250 | $0 | Feb 14, 2020 |
| Jun 28, 2017 | 38254044Z | RESOLVE | CLASS - 2 | 2X10,59M5,68B7. 2-INOPERATIVE OUTSIDE COMMUNICATION REPAIR; 59-BRAKE SERVICE NOT PERFOMED MUST PERFORM AND FILE ON MC... | $0 | $0 | Aug 18, 2017 |
| Apr 30, 2015 | 35123179R | RESOLVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE. BLDG HALLW... | $400 | $0 | Sep 25, 2015 |
| Apr 30, 2015 | 35123177N | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS BSMT SERVICE GROUND CONDUCTOR: NO WATER MAIN GROUND PROVIDED. PLEASE NOTE. THE G... | $4,800 | $0 | Sep 29, 2015 |
| Apr 30, 2015 | 35123178P | RESOLVE | CLASS - 2 | FAILURE TO PROPERLY BOND ELECTRICAL SYSTEMS. BSMT SERVICE SWITCH: ONE OF THE 400AMP SERVICE NEAUTRAL BAR IS NOT BONDE... | $750 | $0 | Sep 29, 2015 |
| Mar 25, 2015 | 38235207K | RESOLVE | CLASS - 2 | 70O02,71X10,73O02,74O02,05M10,05L10,67M07,68M07,68B07,56O02,56Y10,15M07,39O02,39Y02. 05M10-PROVIDE CAR DOOR RESTRICTO... | $250 | $0 | May 15, 2015 |
| Oct 24, 2013 | 38228765J | ACTIVE | CLASS - 1 | 8V1,9H10,29B1,15I10,3UT,68B7,69M7,64U7,99BB5,21B1,24B10,10U7,32H11,38I11,39O2,40O2,73O2,74O2,75O2,77O2,97O2. 8-CEASE ... | $1,000 | $0 | Jan 24, 2014 |
| Aug 15, 2012 | 38223041L | RESOLVE | CLASS - 2 | 08V01,15I11,20I11,20M07,56Y13,67M07,68B07,69M07,70O02,70Z02,77B07,99BB05: 20I11;REPLACE DAMAGE 3RD FLR HOISTWAY DOOR ... | $500 | $0 | Oct 5, 2012 |
| Jan 25, 2011 | 34897583L | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ THE COMM ORDER TO FILE A CERT OF CORRECTION W/ THE DOB FOR OPEN ECB NOV#34868766L REM: COMPLY W/... | $800 | $0 | Apr 8, 2011 |
| Oct 12, 2010 | 38212933N | ACTIVE | CLASS - 1 | 05L10,98U05,99U05,41T07,56Y13,29Q03,35Q03,20M10,16L10,52M07,42G11,08V10,70O02. CEASE USE. 05L- EXCESSIVE GAP CAR DOOR... | $1,000 | $0 | Dec 3, 2010 |
| Oct 8, 2010 | 34872122H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BLDG EAST ELEV.(NORTH END)OBSERVED EXTENSIVE CRACKS & DISPLACEMENT IN PARAPET & LINTEL F... | $500 | $0 | Dec 3, 2010 |
| Sep 30, 2010 | 34868766L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG WALLS (OR APPURTENANCES).NOTED:@ 4 FLR STORY,EXPOSURE 1,ABOVE FROM MAIN ENTRANCE TO BLDG BRI... | $1,000 | $0 | Nov 19, 2010 |
| Mar 9, 2010 | 38209518Z | RESOLVE | CLASS - 2 | 98BB5.99U05.35Q3.77O6.35 ELECTRIC WIRING EXPOSED TOP OF CAR FROM JUNCTION BOX TO DOOR OPERATOR 77 JUNCTION BOX COVER ... | $2,500 | $0 | Apr 30, 2010 |
| Dec 7, 2009 | 38207568H | RESOLVE | CLASS - 1 | 97X10.97X17.98BB5.70O2.56Y2.97X10 ONLY ELEVATOR IN BLDG IS OUT OF SERVICE THERBY CREATING CONDITIONS DANGEROUS TO HUM... | $1,000 | $0 | Feb 5, 2010 |
| Aug 5, 2009 | 38204846P | RESOLVE | CLASS - 2 | 15I10,24X10,70O02,98U05,56Y10,41M10,16L10,77Q03,77D06. 16L- 5TH FL HOISTWAY DOOR STICKS (NOT SELF CLOSING) ON FILE HA... | $500 | $0 | May 14, 2010 |
| Nov 5, 2008 | 38192444R | RESOLVE | CLASS - 2 | 97X10.97X10 ONLY ELEVATOR INBLDG OUT OF SERVICE RESTORE TO SERVICE | $0 | $0 | Jan 9, 2009 |
| Nov 23, 2005 | 38155214Z | RESOLVE | Hazardous | 05L10/44U15/05K10/66O02/12X10/15I10/86U05/39M07. 05L10-REPAIR CAR DOORFOR PROPER CLOSING (DOOR HAS TO PULLED BY HAND ... | $0 | $0 | Jan 6, 2006 |
| Jul 27, 2005 | 38154033P | RESOLVE | Non-Hazardous | 14I07/15M07/38O02/66O02/39P16. 14-I-07-PROVIDE CAR MIRROR. 15-M-07-PROVIDE CERTIFICATE FRAME. 38-O-02-CAR TOP DIRTY. ... | $180 | $0 | Oct 7, 2005 |
| Apr 20, 2005 | 38152159L | RESOLVE | Non-Hazardous | CEASE USE/HAZARDOUS/ CU 51I10/51H10/15I10/21Q03/20I10/34Q03/38Q03/51H10/38Y02/43H10/ CU-HOIST CABLE READY TO BREAK AT... | $500 | $0 | Jun 3, 2005 |
| Aug 21, 2000 | 38107777X | RESOLVE | Non-Hazardous | 03M7 8V1 11Q3 17I12 18L11 31Q3 35M12 35Y11 50Y11 51B7 37G12 75U5 3M7=CAPACITY PLATE 17I12=4TH FL 18L11=7TH FL 31Q3 CA... | $0 | $0 | Apr 20, 2001 |
| Jun 9, 1999 | 38086522Y | RESOLVE | Non-Hazardous | 10Q3,14M7,75M5,30O2,36P17,57O2. -30 CLEAN CAR TOP SHAFTWAY | $0 | $0 | Sep 24, 1999 |
| Feb 22, 1999 | 38084852H | RESOLVE | Non-Hazardous | 3M7,5A12,8V1,9H12,11Q3,17A12,14M7,18R11,22L6,22O2,47B15,27Q3,50Y11, 51B7,73U16. 3-CAPACITY PLATE. 5-VISION PANEL MUST... | $180 | $0 | Apr 9, 1999 |
| Apr 24, 1998 | 38073618X | RESOLVE | Non-Hazardous | 14M50Y54U37U75U31D35O05A17A08V20I18R23U34D34Q09H09M05J #54 U 16=CITY I.D. NUMBER #31 D CONTROLLER WIRING #05 A & 17 A... | $0 | $0 | Jun 12, 1998 |
| Dec 15, 1993 | 38039451Y | RESOLVE | Non-Hazardous | 50Y,50F,08V,28H,14M,11Q,73O,17R,73M. 17 PROVIDE APPROVED TYPE GUARDS. 73 OPERATION OF ELEVATOR WITHOUT A EQUIPMENT US... | $550 | $0 | Aug 24, 1995 |
| Mar 29, 1993 | 38031952X | RESOLVE | Non-Hazardous | 08V,14I,37R, 37-FILE & SECURE A PERMIT FOR INSTALLATION OF NEW CONTROLLER | $350 | $0 | Jan 21, 1999 |
| May 18, 1992 | 38019499P | RESOLVE | Non-Hazardous | 73#,37R,57O,35O, (73)- PERFORM 5YR TEST, PROPRLY TAG DEVICE & FILE ELV-3 FORM. 37-PROPERLY FUSE CONTROLL. | $0 | $0 | Jul 10, 1992 |