ECB violations
Olmstead Avenue, Bronx • Block 03609 • Lot 0016
81 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 4, 2026 | 35732159N | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRE-STOPPING PER BC 712.3; 27-345. NOTED: IN THE GAS METER... | $1,250 | $0 | Jun 5, 2026 |
| May 4, 2026 | 35732158L | ACTIVE | CLASS - 2 | RE-ISSUE #35688891Z. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: CLASSROOM DOORS DO NOT SELF-CLOSE ... | $3,125 | $0 | Jun 5, 2026 |
| Jul 18, 2025 | 35721077X | RESOLVE | CLASS - 2 | REISSUE #35688891Z DATE OF ISSUE: 09-19-2024. EXIT DOOR NOT SELF-CLOSING PROPERLY AT THE TIME OF INSPECTION AT THE TI... | $625 | $0 | Aug 29, 2025 |
| Jul 18, 2025 | 35721080R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS P... | $1,250 | $0 | Aug 29, 2025 |
| Sep 19, 2024 | 35688889J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES.NOTED:AT GYM LUNCHROOM ROOFTOP,PARAPET IS NOT 42"HEIGHT AS REQUI... | $1,250 | $0 | Nov 29, 2024 |
| Sep 19, 2024 | 35688891Z | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT 3RD FLOOR CORRIDOR DOOR NEXT TO ROOM#307 DO NOT CLOSE ... | $625 | $0 | Nov 29, 2024 |
| Sep 19, 2024 | 35688890R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES.NOTED:AT ROOFTOP BRICK CHIMNEY WITH 10'VERTICAL CRACK.REM:MAKE N... | $1,250 | $0 | Nov 29, 2024 |
| Aug 29, 2024 | 39531986L | ACTIVE | CLASS - 2 | CRANE OPERATIONS WITH MISSING FLAG PERSON MONITOR TRAFFIC DURING LIFTS INTERSECTION LAFAYETTE AND PUGSLEY AVE,FIELD C... | $2,400 | $0 | Nov 15, 2024 |
| Jul 7, 2023 | 35674240H | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE AN ADEQUATE CURING BOX AT CONSTRUCTION SITE: AS NOTED AT TIME OF MY INSPECTION OBSERVED (1) CURING... | $2,500 | $0 | Jan 19, 2024 |
| Jul 7, 2023 | 35674239K | RESOLVE | CLASS - 2 | FAILURE TO PERFORM PROPER CONCRETE WASHOUT PROCEDURES AND COLLECTION AND CONTAINMENT: AS NOTED AT TIME OF MY INSPECTI... | $2,500 | $0 | Jan 19, 2024 |
| Jul 7, 2023 | 39518886H | RESOLVE | CLASS - 1 | AT A INCIDENT THAT OCCURRED AT A 3 STORY BUILDING WHERE CONCRETE WAS BEING POURED AT ROOF LEVEL. FORMWORK AND SHORING... | $5,000 | $0 | Sep 20, 2024 |
| Jun 20, 2023 | 39518004R | RESOLVE | CLASS - 1 | IN RESPONSE TO INCIDENT WHERE WORKER GOT INJURED IT WAS REPORTED THAT WORKER WAS STANDING ON UNSECURED PLYWOOD THAT G... | $0 | $0 | Feb 16, 2024 |
| Oct 26, 2022 | 39508238K | RESOLVE | CLASS - 2 | AT TIME OF INSPECTION ON ACTIVE 3 STORY NB JOBSITE CURRENTLY UNDER FOUNDATION/ EARTHWORK, I OBSERVED RAMP OR RUNWAY I... | $625 | $0 | Apr 3, 2023 |
| Oct 26, 2022 | 39508240J | RESOLVE | CLASS - 2 | AT TIME OF INSPECTION ON ACTIVE 3 STORY NB JOBSITE CURRENTLY UNDER FOUNDATION/ EARTHWORK, I OBSERVED TREES IN PLACE A... | $625 | $0 | Apr 3, 2023 |
| Oct 26, 2022 | 39508233L | RESOLVE | CLASS - 1 | AT TIME OF INSPECTION ON ACTIVE 3 STORY NB JOBSITE CURRENTLY UNDER FOUNDATION/ EARTHWORK, I OBSERVED EXCAVATED AREA O... | $2,500 | $0 | Apr 3, 2023 |
| Oct 26, 2022 | 39508236R | RESOLVE | CLASS - 1 | AT TIME OF INSPECTION ON ACTIVE 3 STORY NB JOBSITE CURRENTLY UNDER FOUNDATION/ EARTHWORK, I OBSERVED IN PLACE AT EXP#... | $2,500 | $0 | Apr 3, 2023 |
| Jul 27, 2021 | 35584198Y | RESOLVE | CLASS - 2 | REISSUE#35502103K FAIL TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER IILLUMINATE NOTED:AT VARIOUS LOCATION EMERGENCY ... | $1,562 | $0 | Nov 19, 2021 |
| Jul 7, 2020 | 35502105Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: OBSERVED AT TRANPORTABLE"T1"AT NORTH ELEVATION,METAL CLADDING... | $1,250 | $0 | Oct 2, 2020 |
| Jul 7, 2020 | 35502103K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS PER BC 1... | $625 | $0 | Oct 2, 2020 |
| Jul 7, 2020 | 35502101R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NOTED: OBSERVED THEFOLLOWING ROOM DOORS ARE NOT CLOSING PROPERLY A... | $625 | $0 | Oct 2, 2020 |
| Jul 7, 2020 | 35502102Z | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING. NOTED: FIRE PROOF SELF CLOSING BDOORS AT 1ST FL STAIR'A' CAFETERIA BY EXIT 4,GYMNASIUM EX... | $625 | $0 | Oct 2, 2020 |
| Jul 7, 2020 | 35502104M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: USE OF PROHIBITED DOOR &/OR HARDWARE PER BC 1008.1.8;27-371(J). NO... | $625 | $0 | Oct 2, 2020 |
| Aug 7, 2019 | 39007274M | RESOLVE | CLASS - 1 | AT TIME OF INSPECTION FOUND TUBES LEAKING ON TOP AND BOTTOM. SEAL BOILER AT SITE. | $0 | $0 | Aug 12, 2019 |
| Jun 22, 2017 | 35271169H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS PER BC 10... | $2,500 | $0 | Aug 18, 2017 |
| Jun 22, 2017 | 35271168X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS PER BC100... | $2,500 | $0 | Aug 18, 2017 |
| Sep 22, 2015 | 35127882R | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES.NOTE:CHIMNEY @ROOF (VORTICLE) CRACKS VISIBLE.REM:COMPLY W/NOV | $0 | $0 | Jan 8, 2016 |
| Sep 22, 2015 | 35127884K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:CORRIDOR WIDTH NOTE:@STAIR 6 EXIT B DEBRIS,TABLES,EXT 11 ROOM B... | $0 | $0 | Jan 8, 2016 |
| Sep 22, 2015 | 35127898L | RESOLVE | CLASS - 2 | REISSUE #34957748M FAIL MAINTAIN BLDG COMPLIANT MANNER:FIRE STOPPING NOTE:FIRE STOPPING MISSING AT GAS METER ROOM, CO... | $0 | $0 | Jan 8, 2016 |
| Sep 22, 2015 | 35127883Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:CORRIDOR WIDTH NOTE:@CELLAR COMBUSTIBLE MATERIALS IN CORRODORS,... | $0 | $0 | Jan 8, 2016 |
| Aug 28, 2014 | 35107745M | RESOLVE | CLASS - 2 | REISSUE #35017076P.CELLAR-COMBUSTIBLE MATERIAL IN CORRIDORS B-8 B-11,BOOKS CLOTHINGS CARDBOARD BOXES STORAGE.REM:MAIN... | $0 | $0 | Oct 31, 2014 |
| Aug 28, 2014 | 35108029X | RESOLVE | CLASS - 2 | REISSUE #35017075M.INTERIOR DOOR HARDWARE NOT SELF CLOSING T-1,T-2,T-3& T-4.REM:REPIAR/REPLACE. | $0 | $0 | Oct 31, 2014 |
| Aug 28, 2014 | 35107746Y | RESOLVE | CLASS - 3 | REISSUE #35016749X.ROOF CHIMMEY-NORTH & WEST EXPOSURE VERTICAL CRACKS.REM:REPAIR DEFECTS NOTED. | $0 | $0 | Oct 31, 2014 |
| Aug 28, 2014 | 35107744K | RESOLVE | CLASS - 2 | REISSUE #35017078Z.STAIR 6 EXIT B-DEBRIS NURSES TABLES.EXIT 11 ROOM B-1,SPRINKLER ROOM-STORGAE PARTIALLY BLOCKING EGR... | $0 | $0 | Oct 31, 2014 |
| Apr 29, 2013 | 35017079K | RESOLVE | CLASS - 2 | FUEL OIL TANK ROOM - REAR RIGHT SIDE (POSSIBLE WATER) PENETRATION OF LIQUID DOWN WALL AND AT FLR. REMEDY: MAINTAIN OI... | $0 | $0 | Jun 21, 2013 |
| Apr 29, 2013 | 35017077R | RESOLVE | CLASS - 2 | 1ST FLR GIRLS AND BOYS BATHROOM PIPING (PLUMB) LEAKING INTO BOILER ROOM. REMEDY: REPAIR/REPLACE PIPES AS PER CODE. | $0 | $0 | Jun 21, 2013 |
| Apr 29, 2013 | 35016748Y | RESOLVE | CLASS - 2 | EXTERIOR RAMPS AND STAIRS ROTTING OUT - MATERIAL: WOOD. REMEDY: MAINTAIN EXTERIOR BLDG WALLS OR APPURTENANCES - EXTER... | $0 | $0 | Jun 21, 2013 |
| Apr 29, 2013 | 35016749X | RESOLVE | CLASS - 3 | REISSUE 34957746Z. ROOF CHIMNEY - NORTH & WEST EXP VERTICAL CRACKS. REMEDY: MAINTAIN BLDG AS PER CODE. | $0 | $0 | Jun 21, 2013 |
| Apr 29, 2013 | 35017076P | RESOLVE | CLASS - 2 | CELLAR - COMBUSTIBLE MATERIAL IN CORRIDORS, B-8, B-11, BOOKS, CLOTHINGCARDBOARD BOXES, STORAGE. REMEDY: MAINTAIN CELL... | $0 | $0 | Jun 21, 2013 |
| Apr 29, 2013 | 35017075N | RESOLVE | CLASS - 2 | INTERIOR DOOR HARDWARE NOT SELF-CLOSING - T-1, T-2, T-3, T-4. REMEDY: REPAIR/REPLACE. | $0 | $0 | Jun 21, 2013 |
| Apr 29, 2013 | 35017078Z | RESOLVE | CLASS - 2 | - STAIR 6 EXIT B - DEBRIS, NURSES TABLES, WINDOWS, CHAIN LINK FENCE. -EXIT 11 ROOM B-1, SPRINKLER ROOM - STORAGE PART... | $0 | $0 | Jun 21, 2013 |
| Apr 27, 2012 | 34957747K | RESOLVE | CLASS - 1 | MISC. FURNITURE, FILE CABINETS, ETC: OBSTRUCTIONS IN STAIR ENCLOSURES & PUBLIC CORRIDORS. AT: BASEMENT PUBLIC CORRIDO... | $0 | $0 | Jul 20, 2012 |
| Apr 27, 2012 | 34957748M | RESOLVE | CLASS - 2 | FIRE STOPPING MISSING AT GAS METER ROOM CONDUIT PIPE PENETRATION TO EXIT 11 VESTIBULE. REMEDY: PROVIDE FIRE STOPPING. | $0 | $0 | Jun 15, 2012 |
| Apr 27, 2012 | 34957746Z | RESOLVE | CLASS - 3 | RE-ISSUE #34926825P CRACKED BRICK CHIMNEY AT ROOF CHIMNEY CRACKED VERTICALLY NORTH & WEST EXPOSURES. REMEDY: REPAIR D... | $0 | $0 | Jun 15, 2012 |
| Apr 27, 2012 | 34957745R | RESOLVE | CLASS - 2 | RE-ISSUE #34921899P WATER PENETRATING FOUNDATION WALLS AT BASEMENT BOILER ROOM PIT AREA. REMEDY: REPAIR DEFECT NOTED ... | $0 | $0 | Jun 15, 2012 |
| Aug 4, 2011 | 34921899P | RESOLVE | CLASS - 2 | REISSUE #34861664Z WATER PENETRATION THROUGH FOUNDATION WALLS AT BOILER ROOM PIT AREA. REMEDY: PROVIDE WATER PROOFING... | $0 | $0 | Sep 16, 2011 |
| Aug 4, 2011 | 34926826R | RESOLVE | CLASS - 2 | DOORS NOT CLOSING. AT 3RD STORY HALLWAY SMOKE CORRIDOR DOORS,AT 2ND STORY ROOM 220,AT 1ST STORY AUDITORIUM STAGE EXIT... | $0 | $0 | Sep 16, 2011 |
| Aug 4, 2011 | 34926825P | RESOLVE | CLASS - 3 | CRACKED BRICK CHIMNEY. VERTICAL CRACKS APPROX 12 LF NORTH & WEST EXPOSURES OF CHIMNEY AT ROOF LEVEL. REMEDY: REPAIR C... | $0 | $0 | Sep 16, 2011 |
| Aug 4, 2011 | 34926828K | RESOLVE | CLASS - 3 | FLOOR BUCKLING AT TRANSPORTABLE CLASSROOM T3 NEAR NEAR ENTRY DOOR. REMEDY: REPAIR FLOOR. | $0 | $0 | Sep 16, 2011 |
| Jun 24, 2010 | 34861665K | RESOLVE | CLASS - 2 | REISSUE: 34761469P OBSERVED @ CMU REAR AUDITORIUM WALL 6' LONG STEP CRACK REMEDY: MAINTAIN BLDG | $0 | $0 | Sep 17, 2010 |
| Jun 24, 2010 | 34861664Z | RESOLVE | CLASS - 2 | REISSUE: 34761468N FAILURE TO MAINTAIN OBSERVED: @ BOILER ROOM PIT AREA FOUNDATION WALL HAS BECOME POUROUS ALLOWING W... | $0 | $0 | Sep 17, 2010 |