| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Dec 31, 2025 | 39172136N | RESOLVE | CLASS - 2 | OBSERVED IN THE BASEMENT GAS LINES IN THE ELEVATOR MACHINE ROOM. GAS LINES LOCATED LESS THEN 1 FOOT FROM ELECTRICAL M... | $0 | $0 | Mar 6, 2026 |
| Dec 30, 2025 | 39171854N | RESOLVE | CLASS - 2 | CLASS 2: MAINTENANCE LOG RECORDS OUTDATED, CONDUCT ROUTINE SERVICE AND UPDATE THE LOG. OVERHEAD MACHINERY ROOM DOOR S... | $0 | $0 | Mar 6, 2026 |
| Apr 7, 2025 | 39144122Y | RESOLVE | CLASS - 2 | CLASS 2 ITEMS: IN-CAR COMMUNICATION INOPERATIVE. PROVIDE ELEVATOR COMPANY LOGO INFORMATION IN ELEVATOR MACHINE ROOM. ... | $0 | $0 | Jun 20, 2025 |
| Dec 3, 2024 | 39131815Y | RESOLVE | CLASS - 1 | RESPONDING, TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION OF DEVICE, CEASE USE WAS ISSUED FOR, ALTERED CAR DOOR RESTRI... | $1,250 | $0 | Apr 4, 2025 |
| Sep 13, 2024 | 39124864P | RESOLVE | CLASS - 1 | RESPONDING TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION ON A SINGLE UNIT A. CEASE USE VIOLATION WAS ISSUED FOR ALTERE... | $3,125 | $3,125 | Jan 13, 2026 |
| Mar 21, 2024 | 39109506J | RESOLVE | CLASS - 1 | I OBSERVED IN THE SERVICE DISCONNECTS LABELED #1, #2 AND #3 WITH DIFFERENT SIZED FUSES OF 225AMP AND 300 AMPS,, PROVI... | $4,800 | $4,800 | May 8, 2025 |
| Mar 5, 2024 | 39107817H | RESOLVE | CLASS - 2 | DURING INSPECTION OF SWS, PREMISES HAS SIDEWALK SHED ON MULTIPLE EXPOSURES WITH PARAPET INFORMATION PANEL ONLY PROVID... | $1,250 | $0 | May 17, 2024 |
| Mar 5, 2024 | 39107802P | RESOLVE | CLASS - 2 | AT TIME OF INSPECTION, I OBSERVED SIDEWALK SHED ERECTED AT EXPOSURES # 1,2,&4. SHED IS EQUIPPED WITH LIGHTING AND LIG... | $0 | $0 | May 17, 2024 |
| Jan 16, 2024 | 38275509M | RESOLVE | CLASS - 1 | 59-L-10, 5-A-10. 59=DEFECTIVE BROKE RIGHTSIDE BROAKE SHOE COMPLETELY OFF THE DRUM MUST REPAIR AND TEST WITH 125% CAPA... | $1,280 | $0 | Mar 29, 2024 |
| Dec 15, 2023 | 39524134X | RESOLVE | CLASS - 2 | ACTIVE JOBSITE WITH WORKERS PERFORMING BRICK INSTALLATION WORK AT ROOF LEVEL. UPON REQUEST FOR DOCUMENTS SUCH AS SUSP... | $1,250 | $1,250 | Jul 26, 2024 |
| Dec 15, 2023 | 39524133Y | RESOLVE | CLASS - 1 | ACTIVE JOBSITE WITH WORKERS PERFORMING BRICK INSTALLATION WORK AT ROOF LEVEL. I OBSERVED INADEQUATE SAFETY MEASURES. ... | $5,000 | $5,000 | Jul 26, 2024 |
| Aug 15, 2022 | 39068108X | RESOLVE | CLASS - 2 | AT EXPOSURE # 3,FIRE ESCAPE LADDERS, ANCHORS ON THE FACADE SHOW CRACKING FROM THE ANCHOR POINT TO THE WINDOWS. IT IS ... | $1,250 | $0 | Dec 2, 2022 |
| Aug 11, 2022 | 39067857Z | RESOLVE | CLASS - 1 | DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED(CU). IN CAR PHONE OR INTERCOM NOT WORKING. | $1,250 | $0 | Mar 7, 2024 |
| Aug 11, 2022 | 39067875M | RESOLVE | CLASS - 1 | I OBSERVED IN THE BASEMENT THE WATER BOOST PUMP HAS A DRIVE MOTOR CONTROL WIRED WITH EXPOSED AND ENERGIZED CONDUCTORS... | $1,600 | $0 | Jun 5, 2023 |
| May 3, 2022 | 35644369L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED IN BASEMENT/CELLAR WOOD 2X4 SUPPORTING OS & WYE VALVE ... | $0 | $0 | Jul 29, 2022 |
| May 3, 2022 | 39061513H | RESOLVE | CLASS - 2 | AT 6TH FL TO, FIRST FL, A&B SIDE (SIGNS), AT FIRST FL, OFFICES (SIGNS& EMERGENCY LIGHT), CELLAR LEVEL UTILITIES ROOM ... | $0 | $0 | Jun 17, 2022 |
| May 3, 2022 | 39061514J | RESOLVE | CLASS - 2 | AT ROOF LEVEL, PARAPET WALLS, CRACKED, MISSING MORTAR, LEANING WALLS IN DIFFERENTES LOCATIONS ALSO, ELEVATOR ROOM, CR... | $3,125 | $0 | Sep 9, 2022 |
| Jul 21, 2021 | 35582196L | RESOLVE | CLASS - 1 | FGC 408.2 I OBSERVED IN BASEMENT/CELLAR 2 FUTURE GAS CONNECTIONS ON THE BULL OF THE FITTING AND ALSO ON THE RUN OF TH... | $2,500 | $0 | Nov 3, 2022 |
| Jul 21, 2021 | 35582477H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES.NOTED:OBSERBED AT ROOF'S PARAPET LEVEL AT ENTRANCE COURTYARD LO... | $3,125 | $0 | Nov 19, 2021 |
| Oct 6, 2020 | 39029866N | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS PER 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. REMEDY; INSTALL... | $1,250 | $0 | Apr 16, 2021 |
| Oct 30, 2019 | 39012053P | RESOLVE | CLASS - 2 | NOTED: OBSERVED THROUGHOUT EXPOSURE #1 ENTRANCE COURTYARD, SPALLING, MISSING CEMENT AT BRICK JOINTS, PARAPET WALL LEA... | $3,125 | $0 | Feb 28, 2020 |
| Jul 2, 2019 | 35423325K | RESOLVE | CLASS - 1 | OCCUPANCY CONTRARY TO THAT ALLOWED BY CERT OF OCCUPANCY#44469 LEGAL USE OPEN PARKING CURRENT USE TIRE REPAIR SHOP STR... | $0 | $0 | Aug 16, 2019 |
| May 3, 2019 | 39002555X | RESOLVE | CLASS - 2 | BODY DRAINS MISSING FROM SAFETY VALVE-UNCAPPED WATER PIPE AT BACK OF BOILER-BOILER NUMBER NOT DISPLAYED. | $0 | $0 | Jun 21, 2019 |
| Apr 30, 2019 | 35414667X | RESOLVE | CLASS - 1 | OCCUPANCY CONTRARY TO THAT ALLOWED BY C OF O #44469 LEGAL USE OPEN PARKING (NO RESPONSE) CURRENT USE TIRE REPAIR SHOP... | $0 | $0 | Jun 21, 2019 |
| Apr 9, 2019 | 38268923M | RESOLVE | CLASS - 1 | CU5A10,3D6,20I10. 5A10-DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITHDISABLED. THIS IS A SAFETY DEVICE TO ENSURE PASS... | $1,250 | $0 | Jun 14, 2019 |
| Dec 20, 2018 | 35359758M | RESOLVE | CLASS - 1 | UNLAWFUL ACTS.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.IN NOVEMBER 15,2018,TWO ELECTRICAL VIOLATION WAS IS... | $2,500 | $0 | Feb 15, 2019 |
| Nov 14, 2018 | 35372511R | RESOLVE | CLASS - 1 | FAILURE TO PROPERLY LABEL DISCONNECTS.OBSERVED ELECTRICAL SERVICE SWITCHES LABLES S.S. WITHOUT A PROPER DESIGNATION.T... | $250 | $0 | Jan 14, 2019 |
| Nov 14, 2018 | 35372513K | RESOLVE | CLASS - 1 | FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE TO SECTION.OBSERVED GROUNDING ELECTRODE CONDUCTOR INST... | $4,800 | $0 | Jan 14, 2019 |
| Nov 14, 2018 | 35372514M | RESOLVE | CLASS - 2 | UNAPPROVED,UNSUITABLE/UNSAFE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS,DEVICES,APPLIANCES,AND OR WIRING IN USE.OBSERVE... | $0 | $0 | Jan 4, 2019 |
| Nov 14, 2018 | 35372214K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES. NOTED: OBSERVED THROUGHOUT THE EAST,WEST,SOUTH AND NORTH ELEVATI... | $1,250 | $0 | Feb 1, 2019 |
| Nov 14, 2018 | 35372512Z | RESOLVE | CLASS - 2 | FAILURE TO PROPERLY SECURE/SUPPORT ELECTRICAL METALLIC TUBING (EMT)OBSERVED THROUGHOUT BASEMENT AREA EMT CONDUITS,UNS... | $250 | $0 | Jan 14, 2019 |
| Feb 28, 2018 | 38261199Z | RESOLVE | CLASS - 2 | 24M7,41I11. 24M7 MISSING RADIATOR ON 3RD FL WALL STATION,PROVIDE.41I11DOOR KNOB & LOCK ARE BROKEN,REPLACE. | $0 | $0 | Apr 20, 2018 |
| May 16, 2017 | 35258816Z | RESOLVE | CLASS - 2 | TEMPORARY CONSTRUCTION EQUIPMENT ON SITE-EXPIRED PERMIT. NOTED: AT TIME OF INSPECTION PERMIT FOR THE SIDEWALK SHED EX... | $400 | $0 | Oct 6, 2017 |
| Nov 18, 2016 | 35221491K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. AT THE TIME OF MY INSPECTION 11:25AM ON 11-18-16 AT THE ABOVE PLAC... | $0 | $0 | Jan 6, 2017 |
| Nov 18, 2016 | 35221492M | RESOLVE | CLASS - 2 | FAIL TO MAINTAIN BLDG IN CODE COMPLIANT MANNER RE: INSTALLATION MAINTENANCE OF PLUMBING MATERIALS/EQUIPMENT PER PC 10... | $0 | $0 | Jan 6, 2017 |
| Jun 23, 2016 | 35195556X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING CODE COMPLIANT. NOTED:THE CROSS CORRIDOR DOORS ARE DEFECTIVE THROUGHOUT. DOORS HAVE SEPA... | $250 | $0 | Aug 19, 2016 |
| May 11, 2015 | 38236157X | RESOLVE | CLASS - 2 | 14M10,11X10,02X10,67X10. 11-ELEV NOT RESPONDING TO 2ND FLOOR CAR BUTTON;02-ISNOT WORKING FOR CAR BUTTON STATION ALARM... | $0 | $0 | Jul 10, 2015 |
| Mar 10, 2011 | 38215617P | RESOLVE | CLASS - 2 | 15M07 37T07 37W07 41W07 52M07 60Q03 70Z02 81M07. 37T07-PROVIDE SIGN FOR OVERHEAD SHEAVE ROOM DOOR. 37W07-PROVIDE LOCK... | $0 | $0 | Apr 29, 2011 |
| Jun 8, 2009 | 38203954H | RESOLVE | CLASS - 2 | 100M7.15M7.14M7.100M7 TOE GUARD IS MISSING PROVIDE TOE GUARD | $0 | $0 | Aug 7, 2009 |
| May 20, 2009 | 38202271Y | RESOLVE | CLASS - 2 | 37I10.59M7.9H11.16B1.37 REPAIR WALLS IN OVERHEAD 59 INSTALL RIGHT IN OVERHEAD 16 REPAIR LOBBY DOOR | $250 | $0 | Jul 10, 2009 |
| Sep 11, 2008 | 34696280N | RESOLVE | CLASS - 1 | RESIDENCE ALTERED FOR OCCUPANCY AS A DWELLING FOR MORE THAN THE LEGALLY APPROVED NUMBER OF FAMILIES. I CARDS FROM H.P... | $1,200 | $0 | Feb 13, 2009 |
| Sep 11, 2008 | 34696279X | RESOLVE | CLASS - 2 | WORK WITHOUT A PERMIT. IN CELLAR OF PREMISES EAST SIDE. FULL PARTITION ARE ERECTED TO CREATE SEPERATE ROOMS KITCHEN C... | $800 | $0 | Dec 5, 2008 |
| Jul 25, 2008 | 34683099X | RESOLVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BUILDING DEPARTMENT RECORDS. BASEMENT APT AT WE... | $1,200 | $0 | Nov 7, 2008 |
| May 11, 2006 | 34524514X | RESOLVE | Hazardous | WORK W/O A PERMIT. HAZARDOUS WORK NOTED:APT B3 BEING SUBDIVIDED ORIGINAL KITCHEN PLUMBING FIXTURES ENCLOSED BEHIND SH... | $800 | $0 | Oct 27, 2006 |
| Sep 22, 2004 | 38148994N | RESOLVE | Non-Hazardous | 14M07 15M07 03D06 05E10 10H10 84M07 83O02 36O06 36O02 86U05 21Q03 71K10 66O02 66Z09 40D06 55Y13 39B07 03-RETURN POST ... | $0 | $0 | Nov 5, 2004 |
| Sep 26, 2001 | 38119229N | RESOLVE | Non-Hazardous | 14M07-17M07-03O02-06Q03-74L11-40U16-40Q03-46U16-10X11-05J11-57O02-35P17-74P17-33P17. 17-LOBBY VISION PANEL . 03-CAR T... | $0 | $0 | Nov 16, 2001 |
| Sep 11, 2000 | 38107865X | RESOLVE | Non-Hazardous | 75U05,50Y11,52O02,50O02,74M07,09Q03,05J01,08M07,01X11.52-CLEAN OIL.74-REINSTALL MISSING TO A GUARD.03-CAN TOP DOOR OP... | $500 | $0 | Dec 28, 2001 |
| Aug 7, 1995 | 38051051R | RESOLVE | Non-Hazardous | 14M,20I,33P,35P,57O. | $0 | $0 | Oct 27, 1995 |
| Nov 3, 1993 | 38038903L | RESOLVE | Hazardous | 08V 01X 14M 35P 74M 74O 74 PROVIDE CAR TOP LIGHT 74 CLEAN CAR TOP 01 CEASE USE OF ELEVATOR UNTIL ITEM #01 IS COMPLIED... | $0 | $0 | Jan 20, 1994 |
| Apr 18, 1991 | 38010555J | RESOLVE | Non-Hazardous | 08V,13L,39#,74D,74Q,74M 39)FILE A BN+OBTAIN A PERMIT FOR INSTALLATION OF NEW TRACTION SHEAVE. 74)PROPERLY SECURE INTE... | $0 | $0 | Mar 24, 1994 |