Issued Violation Status Severity Description Penalty Balance due Hearing
Apr 8, 2025 37034783L RESOLVE CLASS - 2 FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 9C REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... $0 $0 Jul 18, 2025
Jun 6, 2024 39116210X RESOLVE CLASS - 2 RESPONDING TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION OF SINGLE DEVICE IN A BUILDING VIOLATION WAS ISSUED FOR THE F... $310 $0 Aug 16, 2024
Aug 5, 2022 39067490L RESOLVE CLASS - 1 CLASS 1 VIOLATION ISSUED, DLM IMPROPERLY INSTALLED ON THIS DEVICE. NO FIREMAN SERVICE PRESENT IN CONTROLLER, INSTALL ... $1,563 $1,563 Sep 30, 2022
May 12, 2022 39062045K RESOLVE CLASS - 1 CLASS 1 VIOLATION ISSUED , DLM IMPROPERLY INSTALLED IN CONTROLLER. INSTALL FIREMAN SERVICE SO DLM IS IN COMPLIANCE WI... $0 $0 Jul 1, 2022
Dec 29, 2021 39053583N RESOLVE CLASS - 1 DLM WAS INSTALLED AS MANDATED BY CODE A17.1 APPENDIX K3 3.10.12. BUT NOT IN COMPLIANCE WITH THE CODE FIREMAN SERVICE ... $625 $625 Jun 10, 2022
Mar 3, 2021 35527168M RESOLVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35374670N ISSUED ON 1/9/2019 AND TO FI... $3,125 $2,679 May 21, 2021
Dec 31, 2020 35523524L RESOLVE CLASS - 2 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35374670N ISSUED ON 01/09/19 & TO FILE A CERT OF CORREC... $625 $0 Apr 16, 2021
Oct 13, 2020 35521886J RESOLVE CLASS - 2 FAILLURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35374670N ISSUED ON 01-09-19 AND TO F... $3,125 $0 Dec 18, 2020
Jan 4, 2020 35515017R RESOLVE CLASS - 2 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35374670N ISSUED ON 01-09-19 & TO FILE A C OF C PURSUAN... $3,125 $0 Feb 21, 2020
Nov 15, 2019 35431203M RESOLVE CLASS - 2 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35374670N ISSUED ON 01-09-19 & TO FILE A C OF C PURSUAN... $3,125 $0 Jan 3, 2020
Sep 17, 2019 35452328Z RESOLVE CLASS - 3 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.AT TIME OF INSPECTION OBSERVED AT APT#3D CEILING WATER DAMAGE A... $250 $0 Nov 1, 2019
Sep 16, 2019 35428735X RESOLVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION#35374670N ISSUED ON 1/19/19 AND TO FILE... $3,125 $0 Nov 1, 2019
Jul 18, 2019 35401338M RESOLVE CLASS - 2 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35374670N ISSUED ON 01-09-19 & TO FILE A C OF C PURSUAN... $0 $0 Jan 24, 2020
Jun 11, 2019 38270138J RESOLVE CLASS - 1 C/U CEASE USE ITEM,CAR DOOR RESTRICTOR.REPAIR AND CONTACT NYC DOB FOR RESTORE TO SERVICE INSPECTION,GAP IN CAR DOOR O... $1,250 $0 Aug 2, 2019
May 9, 2019 35399050N RESOLVE CLASS - 2 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35374670N ISSUED ON 01-09-19 & TO FILE A C OF C PURSUAN... $1,250 $0 Nov 8, 2019
Mar 9, 2019 35395223Y RESOLVE CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VVIOLATION #35374670N ISSUED ON 01/09/19 AND TO ... $0 $0 Sep 24, 2019
Jan 9, 2019 35374669X RESOLVE CLASS - 2 WORK WITHOUT A PERMIT.AT THE TIME OF INSPECTION IT WAS OBSERVED AT CELLAR LEVEL CREATED WITH FULL HEIGHT PARTITION 4 ... $0 $0 Sep 24, 2019
Jan 9, 2019 35374670N RESOLVE CLASS - 1 OCCUPANCY CONTRARY TO THAT ALLOWED BY CERTIFICATE OF OCCUPANCY OR BLDGDEPT RECORDS.NOTE:REOCRDS INIDCATES PREMISES LE... $2,500 $0 Sep 24, 2019
Nov 19, 2018 35352379K RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. I OBSERVED IN CELLAR GAS UNION ON GAS LINE OFF THE SUPER METER... $1,250 $0 Jan 18, 2019
May 3, 2017 38254562Z RESOLVE CLASS - 1 CU-45I10, 67X10,15M07,52O02,70O02,70Z09,71I11. 45I10-GOVERNOR IN OVERHEAD DAMAGED AND NOT WORKING PROPERLY CAR DOESN'... $1,000 $0 Jun 30, 2017
Apr 25, 2017 38254738N RESOLVE CLASS - 2 71M07,59H11,02X10,70O02,09U05. 71M07-PIT NEEDS TO HAVE CAGE LIGHT; 59H11-BRAKE NEEDS TO BE REPLACED-WORN; 02X10-CAR P... $1,250 $0 Jun 16, 2017
Mar 2, 2016 38240687P RESOLVE CLASS - 1 08V01,02X10,56Y10,70O02,70Z09,80M07,40M07,37M07. 08-FLOOR STOPS OFF LEVEL MUST REPAIR IMMEDIATELY; 02-COMMUNICATION I... $1,000 $0 Apr 29, 2016
May 9, 2013 34957221X RESOLVE CLASS - 2 WORK W/O PERMITS. NOTE: AT APTS 4G AND 3J ILLEGAL FULL HEIGHT PARTITIONS ERECTED TO CREATE ADDITIONAL ROOMS W/I EACH ... $400 $0 Jul 5, 2013
Mar 5, 2012 32071834N RESOLVE CLASS - 2 21A 32A 34B 48A 50ABC 50A-MISSING PULLY GUARD @ TRANSFER PUMP 50B- MISSING VALVE LEVER 50C-WATER LINKE LEAK REPAIR/ R... $0 $0 Apr 20, 2012
Jan 15, 2012 36018300L RESOLVE CLASS - 2 FAILURE TO FILE AN ACCEPTABLE SIXTH ROUND TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS:PERIODIC INSPECTION OF ... $800 $0 Aug 17, 2012
Sep 19, 2011 32071298Z RESOLVE CLASS - 2 B254 15 32A 50A 50B 50C. 50A-FLUE CLOGGED W/SOOT. 50B-STAGNANT WATER FLOODS AREA OF BOILER ROOM. 50C-VISIBLE PLUMBING... $0 $0 Mar 30, 2012
Jul 2, 2011 32070768J RESOLVE CLASS - 2 B254,32A,50A,B,C,D,E. 50A- OIL LEAK AT SUPPLY PUMP. 50B- COVER MISSINGFOR BELT ON SUPPLY PUMP. 50C- SEAL AROUND BASE ... $250 $0 Aug 19, 2011
Apr 26, 2011 38215493M RESOLVE CLASS - 2 40R9,60B10,81T15,71M7,72M7,8V1,16T15,1M7,70O2. 40- REMOVE NON-ELEVATOREQUIPMENT. 1- PROVIDE STOP SWITCH IN OVERHEAD. $0 $0 Jun 17, 2011
Jul 17, 2010 36013640P RESOLVE CLASS - 2 FAILURE TO FILE AN ACCEPTABLE 6TH ROUND TECHNICAL REPORT IN COMPLIANCEWITH CODE PROVISIONS:PERIODIC INSPECTION OF EXT... $4,000 $0 Sep 3, 2010
Jul 17, 2010 34861760Z RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG WALL & APPURTENANCES.1-A/C UNITS SUPPORTED BY:WOOD (FL 2,4,5)CAN (FL 6)2.STONE ENTRANCE-VERT... $500 -$500 Jan 28, 2011
Jul 12, 2010 36014180H RESOLVE CLASS - 2 FAILURE TO FILE AN ACCEPTABLE 6TH ROUND TECHNICAL REPORT IN COMPLIANCEWITH CODE PROVISIONS:PERIODIC INSPECTION OF EXT... $2,000 $0 Feb 28, 2011
Jan 6, 2010 38207842L RESOLVE CLASS - 2 70Z9.70O2.15M7.11B11.40O2.73O2.74O2 11 REPLACE LOBBY BUTTON $2,500 $0 Mar 5, 2010
Nov 27, 2009 36010691L RESOLVE CLASS - 2 FAILURE TO FILE AN ACCEPTABLE SIXTH ROUND TECHNICAL REPORT IN COMPLIANCE W/CODE PROVISIONS:PERIODIC INSPECTION OF EXT... $800 $0 Apr 12, 2010
Aug 25, 2009 36009721P RESOLVE CLASS - 2 FAIL TO FILE AN ACCEP 6TH ROUND TECH REPORT IN COMPLIANCE WITH CODE PROVSIONS:PERIODIC INSP OF EXT WALLS AND APPURTEN... $800 $0 Mar 5, 2010
Feb 6, 2009 36008397H RESOLVE CLASS - 2 FAILURE TO SUBMIT AN ACCEPTABLE SIXTH ROUND TECHNICAL REPORT IN COMPLIANCE W/CODE PROVISIONS:PERIODIC INSPECTION OF E... $0 $0 Sep 4, 2009
Nov 19, 2008 32060920X RESOLVE CLASS - 3 B354 40.50 50-CLEAN OUT DOOR TO CHIMNEY BASE MUST BE REPAIRED OR REPLACED $0 $0 Jan 16, 2009
Oct 6, 2008 32060474P RESOLVE CLASS - 3 B354 32A040.50A.50B.50C.50D.50E 50A OIL LEAK AT SUPPLY PUMP 50B NEED CHECK VALVE FOR BACKFLOW PREVENTOR 50C OIL LEAK ... $100 $0 Dec 5, 2008
May 20, 2008 38183948X RESOLVE Non-Hazardous 36H10.15M7.26T15.8V1.27H11.84B10.51H14.66Z9. 36 REPLACE WORN SHEAVE BEARINGS $0 $0 Jul 18, 2008
May 9, 2007 32049689P RESOLVE Non-Hazardous B4A/16/28A/32A/38/48A/50/50A/50B/50C/50D/50E/50F/50G/.50-MISSING BLOW DOWN PIPING ON SAFETY VALVES.50A-COLD WATER REL... $180 $0 Jul 6, 2007
Mar 25, 2000 38095718K RESOLVE Non-Hazardous 51F11. $0 $0 May 12, 2000
May 17, 1999 38087139X RESOLVE Non-Hazardous 9H12,17A12,17A12,22L6,23U16,25Q3,33P17,35O2,39H11,48B15,60M7. -17 CAR,-17 HOISTWAY DOORS MUST BE WIRE GLASS, -35 NOT ... $180 $0 Jul 9, 1999
Jul 27, 1998 38077551Z RESOLVE Non-Hazardous 35P17,33P17,25Q3,75U5,. 35=PROVIDE MEANS OF ACCESS TO MACHINE ROOM. 33=PROVIDE MEANS OF ACCESS TO OVERHEAD DELECTOR S... $0 $0 Sep 11, 1998
Oct 21, 1997 38065050M RESOLVE Non-Hazardous 50Y57Z57O28H18L #18 INTERLOCK BASEMENT FLOOR PULL DOOR CAR STOPS. $0 $0 Dec 26, 1997