ECB violations
Bronx Sch For Better Learning I, Bronx • Block 04916 • Lot 0001
88 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jan 28, 2015 | 35119677H | RESOLVE | CLASS - 2 | REISSUE NOV#35101282H WATER PENETRATING FOUNDATION. AT BOILER ROOM VARIOUS LOCATIONS THROUGHOUT AT BOILER ROOM VARIOU... | $0 | $0 | Mar 20, 2015 |
| Jul 24, 2014 | 35101282H | RESOLVE | CLASS - 2 | RE-ISSUE ECB # 35022930L WATER PENETRATING BLDG ENVELOPE / FOUNDATION.AT CELLAR BOILER ROOM VARIOUS LOCATIONS THROUGH... | $0 | $0 | Oct 3, 2014 |
| Jul 24, 2014 | 35101284L | RESOLVE | CLASS - 2 | RE-ISSUE ECB # 35022934Z WATER PENETRATING ROOF VARIOUS LOCATIONS THROUGHOUT DAMAGING WALLS & CEILINGS. REMEDY: MAKE ... | $0 | $0 | Oct 3, 2014 |
| Jul 24, 2014 | 35101283J | RESOLVE | CLASS - 2 | DOORS NOT CLOSING AT 1ST STORY CROSS CORRIDOR DOORS ADJACENT TO ROOM 131. REMEDY: REPAIR AND / OR REPLACE DOORS | $0 | $0 | Oct 3, 2014 |
| Jun 4, 2013 | 35022934Z | RESOLVE | CLASS - 2 | REISSUE 34926203K ROOF LEAKING. WATER PENETRATION THROUGH ROOF AT VARIOUS LOCATIONS DAMAGE TO WALLS AND CEILINGS IN C... | $0 | $0 | Aug 16, 2013 |
| Jun 4, 2013 | 35022930L | RESOLVE | CLASS - 2 | REISSUE 34981624K WATER PENETRATION FOUNDATION WALLS/FLOOR AT VARIOUSLOCATIONS THROUGHOUT THE BOILER ROOM IN BASEMENT... | $0 | $0 | Aug 16, 2013 |
| Jun 4, 2013 | 35022931N | RESOLVE | CLASS - 2 | AT ROOF - 4 HOODS FOR THE MECHANICAL VENTS ARE DEFECTIVE, NOT BOLTED, MISSING, DENTED, FRAMING RUSTED. RMDY: MAINTAIN... | $0 | $0 | Aug 16, 2013 |
| Jun 4, 2013 | 35022933R | RESOLVE | CLASS - 2 | SMOKE CORRIDORS, NEAR ROOM B32 IN BASEMENT CORRIDOR - OVER DOOR HEADERONE BLOCK MISSING MORTAR AND CRACKED. RMDY: IMM... | $0 | $0 | Aug 16, 2013 |
| Jun 7, 2012 | 34981900H | RESOLVE | CLASS - 2 | WATER PENETRATING BLDG ENVELOPE. AT 1ST STY CAFETERIA ABOVE KITCHEN ENTRY DOORS. REMEDY: REPAIR DEFECTS NOTED. MAINTA... | $0 | $0 | Aug 17, 2012 |
| Jun 7, 2012 | 34981624K | RESOLVE | CLASS - 2 | WATER PENETRATING FOUNDATION WALLS AT VARIOUS LOCATIONS THROUGHOUT BOILER ROOM. REMEDY: REPAIR DEFECT NOTED. MAINTAIN... | $0 | $0 | Aug 17, 2012 |
| Jun 7, 2012 | 34981901J | RESOLVE | CLASS - 2 | WATER DAMAGED CEILINGS & WALLS. AT: ROOM #10. REMEDY: REPAIR DEFECTS NOTED. | $0 | $0 | Aug 17, 2012 |
| Jun 7, 2012 | 34981902L | RESOLVE | CLASS - 2 | ROOF LEAKS. AT TEMP CLASSROOM BLDG ABOVE ROOM 10. REMEDY: REPAIR ROOF. | $0 | $0 | Aug 17, 2012 |
| Aug 19, 2011 | 34926203K | RESOLVE | CLASS - 2 | WATER PENETRATION THRU ROOF OF MINI SCHOOL VARIOUS LOCATIONS THROUGHTOUT. REMEDY: PROVIDE/MAINTAIN WATER PROOF INTEGR... | $0 | $0 | Oct 21, 2011 |
| Aug 19, 2011 | 34926204M | RESOLVE | CLASS - 2 | WATER DAMAGED CEILING & WALLS AT 1ST STORY CLASSROOMS DESIGNED RM A&B RM 10 AND RM12. REMEDY: REPLACE DAMAGED CEILING... | $0 | $0 | Oct 21, 2011 |
| Aug 19, 2011 | 34926201R | RESOLVE | CLASS - 2 | RE-ISSUE # 34863560N. WATER PENETRATION FOUNDATION A WALL VARIOUS LOCATIONS THROUGHOUT BOILER ROOM. REMEDY: WATER PRO... | $0 | $0 | Oct 21, 2011 |
| Aug 19, 2011 | 34926202Z | RESOLVE | CLASS - 2 | WATER PENETRATION THOUGH GYMNASIUM ROOF AT NORTH EAST AND SOUTH WEST CORNER. REMEDY: REPAIR ROOF TO PREVENT WATER PEN... | $0 | $0 | Oct 21, 2011 |
| Jul 15, 2010 | 34863560N | ACTIVE | CLASS - 2 | EXTERIOR FOUNDATION WALL HAS BECOME POROUS & ALLOWING RAIN INTO THE BLDG CAUSING INTERIOR DAMAGES IN THE BOILER ROOM ... | $0 | $0 | Sep 17, 2010 |
| Jul 15, 2010 | 34863561P | RESOLVE | CLASS - 2 | THE GAS METER ROOM IS LACKING FIRESTOPPING AROUND THE PIPE PENETRATION@ THE CELLAR LEVEL.REM:PROVIDE/MAINTAIN FIRE ST... | $0 | $0 | Sep 17, 2010 |
| Mar 11, 2009 | 34761783N | RESOLVE | CLASS - 3 | REISSUE #34638528M. FAILURE TO MAINTAIN: NOTED: CRACKS IN WALL & CEILING LOCATION: GYM ABOVE WATER FOUNTAIN. REMEDY: ... | $0 | $0 | May 15, 2009 |
| Mar 11, 2009 | 34761786Z | RESOLVE | CLASS - 2 | WORK W/O PERMIT. NOTED: ERECTED LARGE STORAGE ROOM W/SHEETROCK WALLS &METAL STUDS. (1) 7' X 2'6" DOOR, SIZE APPROX 20... | $0 | $0 | May 15, 2009 |
| Mar 11, 2009 | 34761785R | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN. NOTED: BROKEN CONCRETE (FLOOR TILES) AT SADDLES IN FRONT OF EXIT DOORS. LOCATION: EXIT #2 @ BASE... | $0 | $0 | May 15, 2009 |
| Mar 11, 2009 | 34761784P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN. NOTED: DEFECTIVE SMOKE/EXIT DOORS, BENT FRAMES & DOORS, NOT OPENING & CLOSING PROPERLY JAMMING. ... | $0 | $0 | May 15, 2009 |
| Apr 10, 2008 | 34638525R | RESOLVE | Non-Hazardous | REISSUE: 34592692N VERTICAL CRACKS IN THE WALLS LOCATED IN ROOM B50 ON BASEMENT LEVEL & ROOM 104 ON THE 1ST FLR LEVEL... | $0 | $0 | Jun 13, 2008 |
| Apr 10, 2008 | 34638526Z | RESOLVE | Non-Hazardous | EXIT DOOR AT REAR CLASSROOM EXIT WITH A SLIDING DEAD BOLT LOOK LOCATED IN ROOM B9 ON BASEMENT LEVEL. REMEDY: REMOVE/I... | $0 | $0 | Jun 13, 2008 |
| Apr 10, 2008 | 34638527K | RESOLVE | Non-Hazardous | EXIT PASSAGE OR CORRIDOR. REQUIRED WIDTH DECREASED BY OBSTRUCTION. NOTED: FILE CABINET IS BEING STORED NEXT TO THE EX... | $0 | $0 | Jun 13, 2008 |
| Apr 10, 2008 | 34638528M | RESOLVE | Non-Hazardous | WALL ABOVE THE SINK IN THE GYMNASIUM ON THE 1ST FLR IS CRACKED. REMEDYREPAIR/REPLACE CRACKS IN WALL. | $0 | $0 | Jun 13, 2008 |
| Apr 10, 2008 | 34638529Y | RESOLVE | Non-Hazardous | EXTERIOR ROOF ABOVE THE GYMNASIUM HAS BECOME POROUS AND ALLOWING RAIN TO ENTER THE BUILDING CAUSING INTERIOR DAMAGES ... | $0 | $0 | Jun 13, 2008 |
| Apr 10, 2008 | 34638530L | RESOLVE | Non-Hazardous | EXIT DOOR. FRONT & REAR EXIT DOORS HAS ILLEGAL SLIDING DEAD BOLT LOCKS IN A LOCK POSITION. IN THE TRANSPORTABLE. REME... | $0 | $0 | Jun 13, 2008 |
| Aug 22, 2007 | 34592692N | RESOLVE | Hazardous | VERTICAL CRACKS IN THE WALL LOCATED IN ROOMS B50 ON BASEMENT LEVEL & ROOM 104 ON THE 1ST LEVEL APPROXIMATELY 3 FEET L... | $0 | $0 | Nov 16, 2007 |
| Aug 22, 2007 | 34592694R | RESOLVE | Hazardous | ROOF HAS BECOME POROUS AND ALLOWING RAIN WATER ENTER THE BLDG CAUSING INTERIOR DAMAGE IN ROOM 12B. REMEDY: WATER - PR... | $0 | $0 | Nov 16, 2007 |
| Aug 22, 2007 | 34592693P | RESOLVE | Hazardous | INTERIOR PLASTER ON THE CEILING IS SPALLING LOCATED IN THE CORRIDOR HALLWAY NEXT TO ROOM 102 ON THE 1ST FLOOR LEVEL. ... | $0 | $0 | Nov 16, 2007 |
| Feb 11, 2002 | 34316561M | RESOLVE | Hazardous | FAILRUE TO MAINTAIN EXTERIOR BUILDING WALL NOTED ; AT REAR PLAY YARD RETAINING WALL LEADING CRACKED & MISSING STONES ... | $0 | $0 | Apr 19, 2002 |
| Feb 11, 2002 | 34316562Y | RESOLVE | Non-Hazardous | FAILURE TO USE PANIC HARDWARE WHERE REQUIRED BY LAW. NOTED ; AT CAFETERIA & GYMNASIUM NO PANIC HARDWARE INSTALLED REM... | $0 | $0 | Apr 19, 2002 |
| Jun 18, 2001 | 34280232J | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE EMERGENCY LIGHT FIXTURE WITHIN STAIR 1,2,3 ON FLOOR1 TO 3 ALSO WITHIN STAIR #4 & #5. INCLUDING VES... | $0 | $0 | Aug 17, 2001 |
| Apr 5, 2001 | 34283988N | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL DEFECT IS: AT INNER COURT-YARD PLY AREA, THE RETAINING WALL HAS CLETERIORA... | $0 | $0 | Sep 21, 2001 |
| Mar 30, 2000 | 34240582N | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN: DEFECT IS: A-BROKEN ,LEANING , DEFECTIVE INTERIOR DOORS VARIOUS LOCATION : WATER PENETRATION OVE... | $0 | $0 | Jun 9, 2000 |
| Nov 8, 1997 | 38066055X | RESOLVE | Non-Hazardous | 02D75U37D 02-REPAIR & SECURE ALRAM BELL UNDER CAR 75-PERFORM ANUAL TEST 37-PROPERLY SECURE MS SWITCH IN CONTROLLER. | $2,500 | $0 | Dec 29, 1997 |
| Dec 2, 1994 | 38045143N | RESOLVE | Non-Hazardous | WHEN STOP SWITCH ENGAGED ALARM MUST RING LIGHT IN ELEVATOR MUST STAY ON AT ALL TIMES. | $0 | $0 | Mar 3, 1995 |