| Mar 20, 2022 | 38273863X | RESOLVE | CLASS - 1 | C/U;97B17,97B15,100M7:CEASED USE PENDING THE OUTCOME OF THE ACCIDENT INVESTIGATION. YOU CAN CONTACT THE DOB AT EIR@BU... | $0 | $0 | Aug 19, 2022 |
| Jul 8, 2019 | 38270423Z | RESOLVE | CLASS - 1 | C/U 05L10,17H11,35M07,26B11,02X10,80M07,71X10,59BB07,52O02,53O02; CEASE USE ITEMS (05-L-10 REPAIR CAR DOOR RESTRICTOR... | $1,250 | $0 | Aug 30, 2019 |
| Jul 8, 2019 | 38270424K | RESOLVE | CLASS - 1 | C/U 05L10,17H11,35M07,02X10,58Y10,59BB07,26B11; CEASE USE ITEM(05-L)REPAIR RESTRICTOR,(17-H)REPLACE 12 FLOOR DOOR(HOI... | $3,125 | $0 | Aug 30, 2019 |
| Dec 13, 2016 | 35216348L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.IMPROPER EXIT/EXIT ACCESS DOORWAY ARRAGEMENTS PER BC1014.2(2008 COD... | $500 | $0 | Mar 31, 2017 |
| Jun 23, 2016 | 35202162X | RESOLVE | CLASS - 1 | UNLAWFUL ACTS.FAILURE TO COMPLY W.AN ORDER OF THE COMMISSIONER.IN MARCH 4,2016 4ELECTRICAL VIOLATIONS WAS ISSUED TO T... | $0 | $0 | Aug 19, 2016 |
| Mar 4, 2016 | 35158941J | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O A PERMIT. BASEMENT BOILER AND ELECTRICAL ROOM:I=1-KW,1-75KW CO. GENERATION, 2 400 AMPS, 2-SET OF ... | $0 | $0 | Jul 1, 2016 |
| Mar 4, 2016 | 35158942L | RESOLVE | CLASS - 1 | ELECTRICAL WORK DOES NOT CONFORM TO APPROVED SUBMITTAL DOCUMENT/AMEND MENTS. BSMT BOILER AND ELECTRICAL ROOM: NO ADVI... | $0 | $0 | Jul 1, 2016 |
| Mar 4, 2016 | 35158943N | RESOLVE | CLASS - 1 | SEPARATELY DERIVED SYSTEMS. SEPARATELY DERIVED SYSTEMS, AS COVERED IN 250.20(A) OR (B), SHALL BE GROUNDED AS SPECIFIE... | $0 | $0 | Jul 1, 2016 |
| Mar 4, 2016 | 35158944P | RESOLVE | CLASS - 1 | TRANSFER SWITCH SHALL NOT LOCATE IN THE SAME ROOM WITH UTILITY.BASEMENT ELECTRICAL ROOM: THE TRANSFER SWITCH IS NOT S... | $0 | $0 | Jul 1, 2016 |
| Oct 7, 2014 | 35080337X | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN. DEFECT IS: IMPROPER DRAINAGE & POOLING WATER AT VARIOUS LOCATIONS OF TERRACES INCLUDING APT 22W.... | $0 | $0 | Nov 21, 2014 |
| Sep 29, 2014 | 35039337L | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O A PERMIT.THE ENTIRE BLDG HALLWAYS:REPLACING LIGHTING FIXTURES"NOT ON FILE"REM:OBTAIN PERMIT: | $8,000 | $0 | Nov 21, 2014 |
| Jul 7, 2014 | 35092970J | RESOLVE | CLASS - 1 | FAILURE TO HAVE SITE SAFETY MANAGER/COORDINATOR PRESENT AS REQUIRED "PARTIAL STOP WORK ORDER" ON ALL EXTERIOR WORK IS... | $1,200 | $0 | Aug 29, 2014 |
| May 13, 2013 | 35009616R | RESOLVE | CLASS - 2 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND/OR APPROVED AMENDMENTS. PLAN CALLS FOR BENCHWORK ON WINS... | $0 | $0 | Jul 5, 2013 |
| Sep 5, 2003 | 34411887H | RESOLVE | Non-Hazardous | WORK W/O PERMIT WORK NOTED CONSTRUCTED PARTITIONS WALLS TO CREATE VESTIBALE BEDROOM ORGINALLY STUDIOS APT NOW 1 BEDRO... | $0 | $0 | Oct 24, 2003 |
| Sep 5, 2003 | 34411886X | RESOLVE | Non-Hazardous | WORK W/O PRMIT WORK NOTED HAVING DEMOLISHED WALLS BETWEEN APTS TO COMBINE 3APS INTO ONE APPR # 200802275 HAS BEEN DIS... | $0 | $0 | Oct 24, 2003 |
| Aug 21, 2003 | 34397266R | RESOLVE | Non-Hazardous | WORK W/O PERMIT WORK NOTED CONSTRUCTED PARTITIONS METAL STUD SHEET ROCK TO CREATE A BEDROOOM FOYER ALSO NOTE RAN EXTR... | $500 | $0 | Oct 24, 2003 |
| Aug 4, 2003 | 34397267Z | RESOLVE | Non-Hazardous | WORK W/O PERMIT WORK NOTED REMOVAL PARTITIONS WALLS TO COMBINE 3 APTS APP # 200802275 HAS BEEN DISAPPROVAL LOCATION A... | $200 | $0 | Oct 3, 2003 |
| Jul 8, 2003 | 38139885J | RESOLVE | Non-Hazardous | 85,LI,O5 | $0 | $0 | Aug 22, 2003 |
| Feb 19, 2003 | 38136136Z | RESOLVE | Non-Hazardous | 81U05 | $180 | $0 | Apr 4, 2003 |
| Nov 25, 2002 | 38135452X | RESOLVE | Non-Hazardous | 81U05. 81-DATE OF TAG 5/30/97. | $180 | $0 | Jan 17, 2003 |
| Nov 20, 1999 | 38091241Y | RESOLVE | Non-Hazardous | 75U5,28B1. 75-PERFORM TEST AND TAG TOP OF CAR. | $350 | $0 | Mar 10, 2000 |
| Apr 10, 1999 | 38085090P | RESOLVE | Non-Hazardous | 22D6,30O2,15O2,54T16,18Q3. | $350 | $0 | Sep 8, 2000 |
| Aug 28, 1998 | 38077618Y | RESOLVE | Non-Hazardous | 44D,18M,57O. 44- WIRE CABLES ON TOP OF GENERATOR ARE NOT SECURED. 18- INTER LOCKS COVER MISSING. 57- PIT DIRTY. | $0 | $0 | Oct 23, 1998 |
| Aug 28, 1998 | 38077619X | RESOLVE | Non-Hazardous | 57O,18M,50M. 57- PIT DIRTY. 18- INTER LOCK COVER MISSING. 50- MISSING CITY ID TAG MACHINE. | $0 | $0 | Oct 23, 1998 |
| Aug 18, 1998 | 38078261P | RESOLVE | Non-Hazardous | 40Z07, 40-STATIC CONTROFFER YOU MUST HAVE A TRIPPING SW UP DIRECTION ANSI A17-1987 RULE 206.4A. | $350 | $0 | Nov 13, 1998 |
| Aug 18, 1998 | 38078260N | RESOLVE | Non-Hazardous | 40A07, 40-YOU MUST INSTALL TRIPPING SW ELECT UP DIRECTION ANSI A17- 1987 RULE 206.4A. | $350 | $0 | Nov 13, 1998 |
| Aug 18, 1998 | 38078259X | RESOLVE | Non-Hazardous | 40A07, 40-STATE CONTROLLER ANSI A17-1987 RULE 206.4A UP TRIPPING SW ELECT. | $350 | $0 | Nov 13, 1998 |