ECB violations
2 Johnson Street, Brooklyn • Block 00140 • Lot 0010
54 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 20, 2021 | 35555719H | RESOLVE | CLASS - 2 | REISSUE 35490629J FAILURE TO MAINTAIN BLDG IN CODE COMPLIANCE MANNER. NOTED: AT ROOMS 415,356,347,307,305,257,255,249... | $1,562 | $0 | Sep 22, 2021 |
| Mar 2, 2021 | 39036991H | RESOLVE | CLASS - 1 | RESTORE TO SERVICE AND CONTACT NYCDOB BY EMAILING EIR@BUILDINGS.NYC.GOV SO THAT A PROPER INSPECTION OF THE DEVICE CAN... | $3,125 | $0 | Apr 16, 2021 |
| Apr 16, 2020 | 35490629J | RESOLVE | CLASS - 2 | REISSUE#35423401N-NOTED:AT ROOMS 415,356,347,307,305,257,255,249,247,242-2,242-1,213,151,149,147,119C,B45 AND B53:THE... | $1,562 | $0 | Oct 14, 2020 |
| Apr 16, 2020 | 35490630R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:NO FIRE STOPPINGPER BC212.3,27-345.NOTED:AT THE BASEMENT ELECTR... | $1,250 | $0 | Oct 14, 2020 |
| Apr 16, 2020 | 35490628H | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING.REISSUE#35423405H.NOTED:AT THE 5TH FLOOR STAIR C,4TH FLOOR STAIR B,3RD FLOOR SMOKE BY 322 ... | $1,562 | $0 | Oct 14, 2020 |
| May 24, 2019 | 35423401N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT THE 1STFLR,ROOMS(147,149,151)2ND FLR,ROOMS(242-1,247,2... | $0 | $0 | Oct 7, 2019 |
| May 24, 2019 | 35423403R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT THE MAIN ENTRANCE TO THE BUILDING,HANDICAP RAMPS ARE M... | $0 | $0 | Oct 7, 2019 |
| May 24, 2019 | 35423405K | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING.NOTED:AT THE CAFETERIA MAIN ENTRANCE(105-2)AND THE KITCHEN,3RD FLOOR BY ROOM 337,EXIT DOOR... | $0 | $0 | Oct 7, 2019 |
| May 24, 2019 | 35423404Z | RESOLVE | CLASS - 2 | EMERGENCY SIGNS AT ELEVATOR CALL STATIONS MISSING,DETECTIVE OR NON COMPLIANT WITH SECTION REQUIREMENTS.NOTED:AT THE 3... | $0 | $0 | Oct 7, 2019 |
| May 24, 2019 | 35423402P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT THE 5THFLR,STAIRWAY B,MISSING TILES ON THE WALLS,EXPOS... | $0 | $0 | Oct 7, 2019 |
| Mar 6, 2015 | 35127614K | RESOLVE | CLASS - 2 | REISSUE #35085609N EXIT PASSAGE IS OBSTRUCTED AT 2ND FLR LIBRARY WITHFILE CABINETS, BOOK CASES. RMDY: REMOVE OBSTRUCT... | $0 | $0 | May 4, 2015 |
| Apr 8, 2014 | 35085609N | RESOLVE | CLASS - 2 | REISSUE 35019596H EXIT PASSAGE IS OBSTRUCTED AT 2 FLOOR LIBRARY WITH FILE CABINETS, BOOK CASES. REMEDY : REMOVE OBSTR... | $0 | $0 | Jun 2, 2014 |
| Apr 8, 2014 | 35085610K | RESOLVE | CLASS - 2 | EXIT PASSAGEWAT OBSTRUCTED AT BASEMENT WITH CUSTODIAN EQUIPMENT AND REAR ALLEYWAY WITH EXCESSIVE DEBRIS. REMEDY: REMO... | $0 | $0 | Jun 2, 2014 |
| May 30, 2013 | 35019597J | RESOLVE | CLASS - 2 | 6TH FLR GYMNASIUM IS PARTIALLY OBSTRUCTING THE EXIT #630 W/EXERCISE FLR MATS. REMEDY: REMOVE OBSTRUCTION. | $0 | $0 | Jul 15, 2013 |
| May 30, 2013 | 35019596H | RESOLVE | CLASS - 2 | REISSUE: 34954526N - EXIT PASSAGEWAY IS PARTIALLY OBSTRUCTED BY FILE CABINET & BOOK CASES LOCATED AT THE 2ND FLR LIBR... | $0 | $0 | Jul 15, 2013 |
| Apr 20, 2012 | 34954529Z | RESOLVE | CLASS - 2 | SEC. 27-369; 28-301.1. EXCESSIVE COMBUSTIBLES IN CORRIDORS. PAPER SIGNS, ART WORK ON WALLS AND BALLOONS HANGING FROM ... | $0 | $0 | Jun 18, 2012 |
| Apr 20, 2012 | 34954526N | RESOLVE | CLASS - 2 | 1017;27-361: EXIT CORRIDOR PARTIALLY OBSTRUCTED BY TABLES & CHAIR AT 1ST FLR & FILE CABINETS AT CELLAR ALSO LIBRARY D... | $0 | $0 | Oct 15, 2012 |
| Apr 20, 2012 | 34954527P | RESOLVE | CLASS - 2 | EXIT DOORS NOT SELF CLOSING. DOORS 455,457 AND 117C. DOORS ARE RACKED PREVENTING THEM FROM FULLY CLOSING. REMEDY: REP... | $0 | $0 | Jun 18, 2012 |
| Apr 20, 2012 | 34954528R | RESOLVE | CLASS - 2 | EXIT LIGHTING DEFECTIVE. EXIT LIGHT IN LIBRARY AT DOORS 213 NOT WORKING. REMEDY: REPAIR/REPLACE EXIT LIGHT. | $0 | $0 | Jun 18, 2012 |
| Jun 23, 2011 | 34918595Z | RESOLVE | CLASS - 2 | ELECTRIC ROOM STORAGE @ CELLAR LEVEL ELECTRIC ROOM STORAGE OF SCHOOL MATERIAL, IE:METAL LOCKERS,BOXES ROOM CLEARLY MA... | $0 | $0 | Aug 1, 2011 |
| Jun 23, 2011 | 34918594R | RESOLVE | CLASS - 2 | PARTIAL CORRIDOR OBSTRUCTION. 1ST FLR CORRIDOR PARTIALLY OBSTRUCTED W/LARGE TABLE,CHAIRS,TV & STACKS OF BOXES CELLAR ... | $0 | $0 | Aug 1, 2011 |
| Jun 9, 2010 | 34856152Z | RESOLVE | CLASS - 2 | CORRIDOR HALLWAY WAS PARTIALLY OBSTRUCTED W/ TABLES CHAIRS BBQ GRILL LOCATED BY THE EXIT PASSAGEWAY LEADING TO THE CO... | $0 | $0 | Sep 13, 2010 |
| Jun 9, 2010 | 34856153K | RESOLVE | CLASS - 2 | NO CURRENT PLACE OF ASSEMBLY AT THE 6TH FLOOR GYMNASIUM AT TIME OF INSP REM: OBTANI A PLACE OF ASSEMBLY CERT OF OPERA... | $0 | $0 | Sep 13, 2010 |
| Mar 19, 2009 | 34772582K | RESOLVE | CLASS - 2 | EXIT PASSAGE OR CORRIDOR REQUIRED WIDTH DECREASED BY OBSTRUCTION. NOTERESIDUAL CONSTRUCTION MATERIAL SUCH AS WALL BAS... | $0 | $0 | Jul 6, 2009 |
| Oct 31, 2008 | 34711108Y | RESOLVE | CLASS - 1 | PROVISION OF LAW 28-201.1 FAILURE TO STORE COMBUSTIBLE MATERIAL AS PER CODE. NOTED AT EXTERIOR GASES IN PROPERLY STOR... | $1,600 | $0 | Jun 24, 2009 |
| Oct 31, 2008 | 34711107M | RESOLVE | CLASS - 1 | FAILURE TO SAFEGUARD ALL PERSONS & PROPERTY AFFECTED BY CONSTRUCTION OPERATIONS. NOTED AT CELLAR LEVEL WITH SCHOOL IN... | $2,400 | $0 | Jun 24, 2009 |
| Oct 13, 2008 | 34711109X | RESOLVE | CLASS - 2 | MISSING STAIRWAY SMOKE DOORS 3 FLR STAIR C & D 4 DOORS. REMEDY: INSTALL DOORS. | $0 | $0 | Dec 15, 2008 |
| Jul 29, 2008 | 34684882M | RESOLVE | CLASS - 2 | ONLY WORKERS WITH CERTIFICATE OF(COMPLETION) 32 HR TRAINING PROGRAM CAN ERECT, MODIFY SCAFFOLDS ABOVE 10'H ERECTION S... | $0 | $0 | May 4, 2009 |
| Jul 29, 2008 | 34684884X | RESOLVE | CLASS - 2 | SEC. 3314.3.2 WORK DOES'T CONFORM TO APPROVED PLANS THERE ARE 5 FULLY PLANKED LEVELS ON SCAFFOLDS INSTEAD OF 1 BY APP... | $400 | $0 | May 4, 2009 |
| Jul 29, 2008 | 34684883Y | RESOLVE | CLASS - 2 | SEC. 3314.13.1 SCAFFOLDS DOESN'T MEET BUILDING CODE STANDARDS 1) MISSING DIAGONAL BRACING ON EXPOSURE 2 REMEDY: CONFO... | $400 | $0 | May 4, 2009 |
| Jan 24, 2002 | 34296439N | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL DEFECT NOTED:GROUT LINE IS MISSING & WATER IS LEAKING THROUGH @ FRONT FACA... | $0 | $0 | Mar 11, 2002 |
| Jan 24, 2002 | 34296438L | RESOLVE | Hazardous | NO PERMIT FOR SIDEWALK SHED:WORK NOTED;A SHED WAS ERECTED AT FRONT OFBUILDING APPROX 84'X16'X10' HIGH WITH A SCAFFOLD... | $0 | $0 | Mar 11, 2002 |
| Nov 1, 1999 | 38091371M | RESOLVE | Non-Hazardous | 73, RETURN DEVICE TO SERVICE SO THAT A COMPLETE INSPECTION CAN BE MADE BY THIS DEPARTMENT. | $2,500 | $0 | Dec 20, 1999 |
| Mar 1, 1999 | 38083738J | RESOLVE | Non-Hazardous | 07X 74M 74 MISSING HAND RAIL | $0 | $0 | Apr 19, 1999 |
| Mar 1, 1999 | 38083739L | RESOLVE | Non-Hazardous | 09H 16H 07X 74M 74 MISSING HAND RAIL | $0 | $0 | Apr 19, 1999 |
| Jan 9, 1998 | 38068759N | RESOLVE | Non-Hazardous | 75M73M35D 35-FLOOR GRATINGS | $2,500 | $0 | Mar 2, 1998 |
| Jan 9, 1998 | 38068761M | RESOLVE | Non-Hazardous | 75M73M35D 35-FLOOR GRATINGS. | $2,500 | $0 | Mar 2, 1998 |
| Jan 9, 1998 | 38068762Y | RESOLVE | Non-Hazardous | 75M73O35D 35-FLOOR GRATINGS. | $2,500 | $0 | Mar 2, 1998 |
| Jan 9, 1998 | 38068763X | RESOLVE | Non-Hazardous | 75M73M35D 35-FLOOR GRATINGS 73-CITY ID TAGS. | $2,500 | $0 | Mar 2, 1998 |
| Jan 9, 1998 | 38068765J | RESOLVE | Non-Hazardous | 75M73M35D 73-CITY ID TAGS 35-FLOOR GRATINGS | $2,500 | $0 | Mar 2, 1998 |
| Jan 9, 1998 | 38068764H | RESOLVE | Non-Hazardous | 75M73M35D73-CITY ID TAGS 35-FLOOR GRATINGS. | $2,500 | $0 | Mar 2, 1998 |
| Jan 9, 1998 | 38068758L | RESOLVE | Non-Hazardous | 37M35D75M73M 37-COVER CONTROLLERS 35-FLOOR GRATINGS. 73 CITY ID TAGS. | $2,500 | $0 | Mar 2, 1998 |
| Jan 9, 1998 | 38068760K | RESOLVE | Non-Hazardous | 75M73M35D 35-FLOOR GRADINGS. | $2,500 | $0 | Mar 2, 1998 |
| Feb 14, 1996 | 38053895X | RESOLVE | Non-Hazardous | 73X,73X.RETURN TO SERVICE FOR COMPLETE INSPECTION OR /FILE FOR REMOVAL | $5,000 | $0 | May 13, 1996 |
| Mar 24, 1995 | 38047527L | RESOLVE | Non-Hazardous | 73L. 73-RESTORE ELEVATOR 3F5237 TO FULL SERVICE OR PROPERLY DISMANTLESAME AND FILE WITH THIS DEPARTMENT. | $5,000 | $0 | May 8, 1995 |
| Mar 24, 1995 | 38047528N | RESOLVE | Non-Hazardous | 57Z9, 3L12. REPLACE MISSING CAB FLOOR TILE. | $0 | $0 | Jun 26, 1995 |
| Mar 24, 1995 | 38047526J | RESOLVE | Non-Hazardous | 40L.40-STOP CAR FROM RELEVELING INTO FLOORS AND BLOWING OVEROLAD. | $1,000 | $0 | May 8, 1995 |
| Feb 2, 1994 | 38039225X | RESOLVE | Non-Hazardous | 09H,35#, 35 STOP WATER LEAK FROM ROOF INTO MACHINERY ROOM TO PREVENT DAMAGE TO EQUIPMENT. | $1,000 | $0 | Mar 21, 1994 |
| Feb 2, 1994 | 38039224Y | RESOLVE | Non-Hazardous | 73X RETURN TO SERVICE ELEVATOR. | $5,000 | $0 | Mar 21, 1994 |
| Mar 3, 1993 | 38030598H | RESOLVE | Non-Hazardous | 08V 44Q 57O 73U 44 WIRING ON GENERATORS ARE MISSING THE COVERS | $1,000 | $0 | Apr 19, 1993 |