ECB violations
1 Hoyt Street, Brooklyn • Block 00157 • Lot 0009
103 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 20, 2026 | 37036920H | ACTIVE | CLASS - 2 | FAILURE TO FILE ACCEPTABLE CYCLE 9B REPORT INDICATING CORRECTION OF UNSAFE CONDITION DESCRIBED IN INITIAL FACADES REP... | $1,250 | $1,250 | Aug 12, 2026 |
| Oct 22, 2025 | 39164346L | ACTIVE | CLASS - 2 | CLASS 2: MAINTENANCE LOG NOT UP TO DATE, CONDUCT ROUTINE SERVICE AND UPDATE THE RECORDS. SOME FLOORS BRAILLE TAGS MIS... | $3,125 | $3,125 | Nov 30, 2026 |
| Oct 22, 2025 | 39164545Y | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $6,250 | $6,250 | Nov 30, 2026 |
| Oct 22, 2025 | 39164347N | ACTIVE | CLASS - 1 | CLASS 1 CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. RE... | $6,250 | $6,250 | Nov 30, 2026 |
| Oct 22, 2025 | 39164506L | ACTIVE | CLASS - 2 | OBSERVED IN BASEMENT GAS LINE IN FIRE PUMP ROOM. BUILDING WIDE NO OPEN ENDED TOILET SEATS, MISSING STANDPIPE CAPS. SE... | $6,250 | $6,250 | Nov 24, 2026 |
| Apr 1, 2025 | 39538571L | RESOLVE | CLASS - 2 | AT 6:15AM OBSERVED 8 STORY BUILDING WITH SWS IN PLACE SEVERAL BULBS AT EXP#1 WAS NOT ILLUMINATED AS STIPULATED IN BC3... | $2,400 | $0 | Mar 23, 2026 |
| Dec 10, 2024 | 39132484N | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING DOORS THROUGHOUT BASEMENT. POTENTIALLY FIRE OR SMOKE HAZARD., R... | $625 | $625 | Sep 8, 2025 |
| Dec 10, 2024 | 39132483L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $2,500 | Mar 9, 2026 |
| Dec 10, 2024 | 39132485P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1 (2014 COD... | $312 | $312 | Mar 9, 2026 |
| Dec 9, 2024 | 39132475L | ACTIVE | CLASS - 2 | OBSERVED NO FRESH AIR VENTILATION IN THE GAS METER ROOM LOCATED IN THE BASEMENT/CELLAR. AS PER E 4 OF THE FUEL GAS CO... | $312 | $312 | May 7, 2026 |
| Dec 9, 2024 | 39132668H | RESOLVE | CLASS - 2 | I OBSERVED IN THE LAUNDRY ROOMS ON ALL FLOORS THE IMPROPER TERMINATION OF THE POWER CORD TO THE DRYER UNITS WITHOUT A... | $0 | $0 | Mar 17, 2025 |
| Dec 9, 2024 | 39132472X | RESOLVE | CLASS - 2 | OBSERVED ACTIVE WATER LEAK ON THE O,S AND WYE VALVE IN THE STAIRWAY ON THE 8TH FLOOR. AS PER 102.3 OF THE PLUMBING CO... | $655 | $655 | Dec 3, 2026 |
| Dec 9, 2024 | 39132667X | RESOLVE | CLASS - 1 | I OBSERVED (2) ELECTRICAL CLOSETS ON THE 12TH AND 2ND FLOORS WITH EXCESSIVE STORAGE OF CLOTHING, AND OFFICE EQUIPMENT... | $1,200 | $1,200 | Aug 11, 2025 |
| Dec 9, 2024 | 39132473H | RESOLVE | CLASS - 2 | OBSERVED UNSUPPORTED SPRINKLER BRANCH PIPING LOCATED IN THE MECHANICAL ROOM ON THE 8TH FLOOR. AS PER 308.4 OF THE PLU... | $0 | $0 | Mar 17, 2025 |
| Dec 9, 2024 | 39132476N | RESOLVE | CLASS - 1 | NO DOOR OBSERVED IN THE ENTRANCE OF THE GAS METER ROOM LOCATED IN THE BASEMENT/CELLAR. THIS IS A HAZARDOUS CONDITION ... | $1,280 | $1,280 | Dec 3, 2026 |
| Dec 9, 2024 | 39132474J | RESOLVE | CLASS - 2 | OBSERVED EXCESSIVE COMBUSTIBLE STORAGE IN THE BOILER ROOM LOCATED ( TRASH, OFFICE TABLE, EXERCISE BIKE, MICROWAVE) IN... | $655 | $655 | Dec 3, 2026 |
| Jul 11, 2024 | 39530424P | RESOLVE | CLASS - 2 | RESPONDING A COMPLAINT OBSERVED: SIDEWALK SHED INSTALLED AT EXPO# 1-4. NO UNDERSIDE LIGHTING INOPERABLE LIGHT BULBS, ... | $5,000 | $5,000 | Nov 5, 2026 |
| Jun 20, 2024 | 39117301X | RESOLVE | CLASS - 1 | CLASS 1 ITEMS: F12 3AMP CONTROLLER FUSE BYPASSED. DOOR ZONE RESTRICTOR INOPERATIVE. CLASS 2 ITEMS: IN-CAR COMMUNICATI... | $3,125 | $3,125 | Aug 24, 2026 |
| Jun 17, 2024 | 39117028Y | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39097092N ISSUED ON 10/03/2023 AND TO ... | $0 | $0 | Apr 14, 2026 |
| Jun 13, 2024 | 39116733P | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDER AS STATED IN ECB#39097095Z ISSUED ON 10/03/2023 AND FILE A... | $0 | $0 | Nov 12, 2025 |
| Jun 13, 2024 | 39116732N | RESOLVE | CLASS - 1 | I OBSERVED IN THE ROOFTOP ELEVATOR MOTOR ROOM THE BX CABLING SUPPLYING POWER TO THE FAN IMPROPERLY TERMINATED WITH EX... | $4,000 | $4,000 | Nov 12, 2025 |
| Jun 12, 2024 | 39116581P | RESOLVE | CLASS - 1 | ELECTRIC SAFETY EDGE NOT WORKING(CU). DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED(CU). REPAIR MACHINE ROO... | $0 | $0 | Apr 14, 2026 |
| Jan 29, 2024 | 39104578X | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39086367J ISSUED ON 5/1... | $0 | $0 | Apr 14, 2026 |
| Jan 29, 2024 | 39104576M | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39086363M ISSUED (MISCE... | $0 | $0 | Apr 14, 2026 |
| Jan 29, 2024 | 39104583K | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39096418J ISSUED ON 10/... | $0 | $0 | Apr 14, 2026 |
| Dec 11, 2023 | 35674312H | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE ADEQUATE SAFETY MEASURES, SUCH AS NETTING, SIDE WALK SHED, FENCE ETC. WHERE REQUIRED TO PROTECT AN... | $12,500 | $12,500 | Sep 16, 2024 |
| Oct 4, 2023 | 39096396H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSP... | $1,250 | $0 | Dec 13, 2023 |
| Oct 3, 2023 | 39097092N | RESOLVE | CLASS - 1 | I OBSERVED ON ALL FLOORS THE LIGHTING ALONG THE PATH AND AT THE POINTS OF EGRESS SWITCH CONTROLLED SO AS TO BE ABLE T... | $12,500 | $12,500 | Feb 18, 2027 |
| Oct 3, 2023 | 39097101X | RESOLVE | CLASS - 2 | I OBSERVED THE VIOLATING CONDITIONS LISTED IN ECB# 39086367J STILL IN EFFECT WITH NO CORRECTIVE ACTION AS REQUIRED BY... | $3,125 | $3,125 | Feb 18, 2027 |
| Oct 3, 2023 | 39096420Z | RESOLVE | CLASS - 2 | DOOR DOES NOT CLOSE LOCATED IN STAIRCASE A., REPAIR/REPLACE DOOR | $0 | $0 | May 7, 2026 |
| Oct 3, 2023 | 39097099X | RESOLVE | CLASS - 2 | I OBSERVED THE VIOLATING CONDITIONS DETAILED IN ECB# 39086362K, THE IMPROPERLY SUPPORTED BX CABLING CORRECTED AND NO ... | $3,125 | $3,125 | Feb 18, 2027 |
| Oct 3, 2023 | 39096427L | RESOLVE | CLASS - 2 | OBSERVED SPRINKLER HEAD ESCUTCHEON IN LAUNDRY ROOM LOCATED ON THE 5TH FLOOR HAS JOINT COMPOUND ON IT. THIS CAN OBSTRU... | $625 | $625 | May 7, 2026 |
| Oct 3, 2023 | 39097093P | RESOLVE | CLASS - 2 | I OBSERVED THE VIOLATING CONDITIONS LISTED IN ECB# 39086366H STILL IN EFFECT WITH NO CORRECTIVE ACTION AS REQUIRED BY... | $3,125 | $3,125 | Feb 18, 2027 |
| Oct 3, 2023 | 39096419L | RESOLVE | CLASS - 1 | GAS/PROPANE POWERED TOOLS FOUND INSIDE CELLAR, ( IF THIS COMBUSTIBLE MATERIAL IGNITES INSIDE THE BUILDING, IT WILL EN... | $0 | $0 | May 7, 2026 |
| Oct 3, 2023 | 39096418J | RESOLVE | CLASS - 1 | ILLEGAL HARDWARE (SLIDING LATCH LOCK) IN STALLED ON BOTTOM OF FRONT DOOR LOCATED AT GROUND LEVEL. (ENDANGERING LIFE, ... | $0 | $0 | May 7, 2026 |
| Oct 3, 2023 | 39096429P | ACTIVE | CLASS - 2 | OBSERVED NO VENTILATION IN THE GAS METER ROOM. GAS METER ROOM SHALL BE VENTED AND FREE OF STORAGE., REPAIR AND/OR REP... | $625 | $625 | May 7, 2026 |
| Oct 3, 2023 | 39097091L | RESOLVE | CLASS - 2 | I OBSERVED NO C OF C SUBMITTED TO DOB RECORDS FOR ECB# 39086364Y ISSUED ON 05/15/2023. THE VIOLATING CONDITIONS WERE ... | $3,125 | $3,125 | Feb 18, 2027 |
| Oct 3, 2023 | 39097098Y | RESOLVE | CLASS - 2 | I OBSERVED THE VIOLATING CONDITIONS NOTED IN ECB#39086365X, NO GFCI PROTECTION PROVIDED, CORRECTED WITH NO C OF C SUB... | $3,125 | $3,125 | Feb 18, 2027 |
| Oct 3, 2023 | 39097094R | RESOLVE | CLASS - 2 | I OBSERVED THE VIOLATING CONDITIONS LISTED IN ECB# 39086366H , NO REMOTE SHUT-DOWN FOR THE GAS FIRED SYSTEMS. AS PER ... | $5,000 | $5,000 | Feb 18, 2027 |
| Oct 3, 2023 | 39097097M | RESOLVE | CLASS - 2 | I OBSERVED THE VIOLATING CONDITIONS LISTED IN ECB # 39086368L, THE USE OF LIGHTS AS A RACEWAY, CORRECTED WITH NO C OF... | $3,125 | $3,125 | Feb 18, 2027 |
| Oct 3, 2023 | 39097100Y | RESOLVE | CLASS - 2 | I OBSERVED THE REMOVAL OF BX CABLING AND THE INSTALLATION OF EMT CONDUIT IN THE 8TH FL. MECHANICAL ROOM, THE INSTALLA... | $0 | $0 | Nov 14, 2024 |
| Oct 3, 2023 | 39096425H | ACTIVE | CLASS - 2 | OBSERVED ON THE ROOF AC CHILLER PROFUSELY LEAKING WATER. AS PER 102.3 OF THE PC MAINTENANCE. INSTALLATIONS, BOTH EXIS... | $3,125 | $3,125 | Dec 13, 2023 |
| Oct 3, 2023 | 39096426J | RESOLVE | CLASS - 2 | OBSERVED IN THE MECHANICAL ROOM ON THE 8TH FLOOR WATER LINES ARE BEING SUPPORTED BY THE OVERHEAD SPRINKLE LINE AND WI... | $625 | $625 | May 7, 2026 |
| Oct 3, 2023 | 39096421K | RESOLVE | CLASS - 2 | MAJOR HOLE PENETRATION, UNFINISHED AND EXPOSED WALLS LOCATED 7 & 8TH FLOORS MECHANICAL ROOMS, UNPERMITTED FOAM USED T... | $0 | $0 | May 7, 2026 |
| Oct 3, 2023 | 39097095Z | RESOLVE | CLASS - 1 | I OBSERVED ON THE ROOFTOP THE RACEWAY FITTINGS SUPPLYING POWER TO THE HVAC UNIT OPEN WITH EXPOSED AND ENERGIZED CONDU... | $1,600 | $0 | Nov 12, 2025 |
| Oct 3, 2023 | 39097096K | RESOLVE | CLASS - 2 | I OBSERVED NO C OF C SUBMITTED FOR ECB# 39086763M REGARDING FAILURE TO PROVIDE ACCESS TO BUILDING OVERCURRENT DEVICES... | $3,125 | $3,125 | Feb 18, 2027 |
| Oct 3, 2023 | 39096424X | RESOLVE | CLASS - 2 | OBSERVED IN THE BASEMENT/CELLAR IN THE SPRINKLER ROOM CAPPED BALL DRIP. WHEN THE BALL DRIP IS CAPPED THIS PREVENTS DR... | $625 | $625 | May 7, 2026 |
| May 15, 2023 | 39086334N | RESOLVE | CLASS - 2 | NO FIRE STOP IN ELECTRICAL CLOSET LOCATED 7TH FLOOR, (B-SIDE)., PROVIDE/MAINTAIN FIRE STOPPING; PROVED/MAINTAIN FIRE ... | $0 | $0 | Apr 14, 2026 |
| May 15, 2023 | 39086333L | RESOLVE | CLASS - 2 | ILLEGAL LATCH LOCK LOCATED 4TH FLOOR DINNING ROOM., PROVIDE LEGAL HARDWARE; PROVIDE LEGAL HARDWARE | $0 | $0 | Apr 14, 2026 |
| May 15, 2023 | 39086364Y | RESOLVE | CLASS - 2 | I OBSERVED ON THE 8TH FLOOR REAR STAIRWELL A PANEL BEING USED AS A SPLICED BOX WITH LIVE CONDUCTORS ACCESSIBLE TO THE... | $2,000 | $2,000 | Nov 16, 2026 |