ECB violations
307-311 Hoyt Street, Brooklyn • Block 00437 • Lot 0001
152 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Oct 3, 2016 | 35213661Y | RESOLVE | CLASS - 2 | 27-766. REISSUE 35148431K FRESH AIR IN GAS METER ROOM RS16/R115.4 NOFRESH AIR VENT/INLET IN THE GAS METER ROOM. RMDY:... | $0 | $0 | Feb 6, 2017 |
| Oct 3, 2016 | 35213662X | RESOLVE | CLASS - 2 | REISSUE 35148202 OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BLDG DEPT USE OF CLASSROOMS IN... | $0 | $0 | Feb 6, 2017 |
| Oct 9, 2015 | 35148431K | RESOLVE | CLASS - 2 | 27-766 REISSUE#35128989L NO FRESH AIR VENT IN GAS METER ROOM.REM COMPLY W/ NOV | $0 | $0 | Jan 4, 2016 |
| Oct 9, 2015 | 35148432M | RESOLVE | CLASS - 3 | REISSUE 35102038K FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTE SETTLEMENT CRACKS (INGLAZED) WALL TILES IN P... | $0 | $0 | Jan 4, 2016 |
| Oct 9, 2015 | 35148430Z | RESOLVE | CLASS - 2 | REISSUE#351289885 FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES.NOTESTEP CRACKS IN PARAPET AREA ON UNION ST,PRESIDE... | $0 | $0 | Jan 4, 2016 |
| Oct 9, 2015 | 35148202R | RESOLVE | CLASS - 2 | REISSUE#35102039M OCCUPANCY CONTRARY TO C OF O#132282.NOTE C OF O INDICATES #132282 STORAGE BOILER LUCKERS ART CELLAR... | $0 | $0 | Jan 4, 2016 |
| Jun 2, 2015 | 35128989L | RESOLVE | CLASS - 2 | 27-MISC,28&BC,REISSUE #3510204J ON 7/15/14.NO FRESH AIR VENT IN GAS METER ROOM.DUCT WORK GOES THROUGHT GAS METER ROOM... | $0 | $0 | Aug 3, 2015 |
| Jun 2, 2015 | 35128988J | RESOLVE | CLASS - 2 | VIOLATION # REISSUE 35018130L,35018129Y ISSUE ON 7/15/14.FAILURE TO MAINTAIN BLDG WALL(S)OR APPURTENANCES.FOR DEFECTI... | $0 | $0 | Aug 3, 2015 |
| Jun 2, 2015 | 35128990Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLAINT MANNER.NOTE:EMERGENCY EXIT DOORS LOCATED @ THE MAIN ENTRANCE/EXIT ON HOYT ... | $0 | $0 | Aug 3, 2015 |
| Jun 2, 2015 | 35128987H | RESOLVE | CLASS - 2 | REISSUE #35102038K ON 7/15/14.FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.FOR CRACKED GLAZED BLOCK WALLS FOUND ... | $0 | $0 | Aug 3, 2015 |
| Jun 2, 2015 | 35128986X | RESOLVE | CLASS - 2 | REISSUED #35102039M ON 7/19/14 OCCUPANCYU CONTRARY TO THAT ALLOWED BY CERT OF OCCUPANCY OR BLDG DEPT.FOR @ CELLAR VAR... | $0 | $0 | Aug 3, 2015 |
| Jun 2, 2015 | 35128991K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER LACK OF EMERGENCY LIGHTING FOR EXITS,EXIT DISCHARGER & PUBLIC CORRI... | $0 | $0 | Aug 3, 2015 |
| May 14, 2015 | 35129115P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EMERGENCY LIGHTING FOR EXITS.NOTE:EMERGENCY EXIT LIGHTS ARE DEFECTIVE IN TRANSPORTABLE #T13,T4, &... | $0 | $0 | Aug 3, 2015 |
| May 14, 2015 | 35129114N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES.NOTE:WOODEN DECK,STAIRS & RAILING LEADING TO TRANSPORTABLES ARE WAR... | $0 | $0 | Aug 3, 2015 |
| May 14, 2015 | 35129116R | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING.NOTE:ALL INTERIOR SHARED EXIT DOORS IN BETWEEN THE TRANSPORTABLE CLASSES ARE NOT SELF-CLOS... | $0 | $0 | Aug 3, 2015 |
| Jul 15, 2014 | 35102038K | RESOLVE | CLASS - 2 | REISSUE # 35018127K CRACKED GLAZED BLOCK WALLS FOUND AT EXIT 4, EXIT 8GYM WALLS, 2ND FL CORRIDOR ADJACENT TO ROOM 205... | $0 | $0 | Sep 29, 2014 |
| Jul 15, 2014 | 35102036R | RESOLVE | CLASS - 2 | REISSUE # 35018130L & 35018129Y FAILURE TO MAINTAIN BLDG WALLS DEFECTIVE EXTERIOR BRICK / MORTAR AT PARAPET LEVEL AT ... | $0 | $0 | Sep 29, 2014 |
| Jul 15, 2014 | 35102042N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN GAS METER ROOM IS BEING USED TO STORE BOXES. REMEDY : DISCONTINUE PROHIBITED USE-REMOVE STORAGE | $0 | $0 | Sep 29, 2014 |
| Jul 15, 2014 | 35102041L | RESOLVE | CLASS - 2 | USE OF PROHIBITED DOOR HARDWARE VARIOUS DOORS HELD OPEN BY MECHANICAL MEANS ( HOOK & EYE HARDWARE ) ATTACHED TO WALLS... | $0 | $0 | Sep 29, 2014 |
| Jul 15, 2014 | 35102037Z | RESOLVE | CLASS - 2 | REISSUE # 35018128M CRACKED CONCRETE WALL CMU AT BOILER ROOM CRACKED AT WALL. REMEDY : REPAIR CELLAR MASONRY WALL | $0 | $0 | Sep 29, 2014 |
| Jul 15, 2014 | 35102040J | RESOLVE | CLASS - 2 | 27-766 RE-ISSUE 34950529K NO FRESH AIR VENT IN GAS METER ROOM. DUCT WORK GOES THROUGH GAS METER ROOM ONLY - NO VENT I... | $0 | $0 | Sep 29, 2014 |
| Jul 15, 2014 | 35102039M | RESOLVE | CLASS - 2 | RE-ISSUE 35018126Z OCCUPANCY CONTRARY TO CERTIFICATE OF OCCUPANCY # 132282 AT CELLAR VARIOUS STORAGE ROOMS HAVE BEEN ... | $0 | $0 | Sep 29, 2014 |
| May 10, 2013 | 35018129Y | RESOLVE | CLASS - 2 | REISSUE #34950530H DEFECTIVE BRICK FACADE AT 2ND STORY SOUTH EAST CORNER,STEP CRACKING IN EXTERIOR BRICK MASONRY FACA... | $0 | $0 | Jul 15, 2013 |
| May 10, 2013 | 35018128M | RESOLVE | CLASS - 2 | REISSUE #34950531J CRACKED CONCRETE WALL AT BOILER ROOM,HORIZONTAL IN CONCRETE TO CMU BLOCK WALL. REMEDY: REPAIR CELL... | $0 | $0 | Jul 15, 2013 |
| May 10, 2013 | 35018130L | RESOLVE | CLASS - 2 | REISSUE #34926560Z DEFECTIVE EXTERIOR BRICK AT LEFT & RIGHT COURT YARDSTAIRS ALONG PRESIDENT STREET,MISSING & LOOSE M... | $0 | $0 | Jul 15, 2013 |
| May 10, 2013 | 35018131N | RESOLVE | CLASS - 2 | DEFECTIVE GLAZED BLOCK AT GYM,NUMEROUS MORTAR JOINTS MISSING W/LOOSE GLAZED BLOCK AT VARIOUS AREAS THROUGHOUT,IE: ADJ... | $0 | $0 | Jul 15, 2013 |
| May 10, 2013 | 35018127K | RESOLVE | CLASS - 2 | REISSUE #34950532L CRACKED GLAZED BLOCK AT 2ND FL CORRIDOR ADJACENT TOROOM 205,CRACKED BULLNOSE GLAZED TILE W/AREA HA... | $0 | $0 | Jul 15, 2013 |
| May 10, 2013 | 35018126Z | RESOLVE | CLASS - 2 | REISSUE #34954450X OCCUPANCY CONTRARY TO C/O AT CELLAR,CLASSROOMS IN USE,C/O #132282 INDICATES LOCKER ROOM,STORAGE,& ... | $0 | $0 | Jul 15, 2013 |
| May 10, 2013 | 35018132P | RESOLVE | CLASS - 2 | DEFECTIVE FLOOR AT TRANSPORTABLE UNIT #T3,VINYL TILE CRACKED W/PIECES MISSING,SUB FLOORING ROTTEN & SPONGY. REMEDY: R... | $0 | $0 | Jul 15, 2013 |
| Mar 27, 2012 | 34950531J | RESOLVE | CLASS - 2 | REISSUE: 34856348K CONCRETE WALL BELOW THE SPLIT LEVEL IS CRACKED AT THE CELLAR LEVEL. REMEDY: REPAIR &/OR REPLACE CR... | $0 | $0 | Jun 4, 2012 |
| Mar 27, 2012 | 34954450X | RESOLVE | CLASS - 2 | REISSUSE: 34856339Z.OCCUPANCY CONTRARY TO CERTIFICATE OF OCCUPANCY. NOTED: CERTIFICATE OF OCCUPANCY #132282 INDICATES... | $0 | $0 | Jun 4, 2012 |
| Mar 27, 2012 | 34950529K | RESOLVE | CLASS - 2 | SEC. 28-301.1;27-766 REISSUE 34926565H THE GAS METER ROOM IS LACKING FRESH AIR VENTILATION AT BASEMENT LEVEL. REMEDY:... | $0 | $0 | Jun 4, 2012 |
| Mar 27, 2012 | 34950530H | RESOLVE | CLASS - 2 | REISSUE: 34926564X EXTERIOR BRICK FACADE IS CRACKED LOCATED ADJACENT TO PRESIDENT STREET @ 2ND FLOOR LEVEL. REMEDY: R... | $0 | $0 | Jun 4, 2012 |
| Mar 27, 2012 | 34950532L | RESOLVE | CLASS - 2 | THE (BULL NOSE) TOP GLAZED WALL TILES IS CRACKED LEAVING SHARP EDGES LOCATED ON THE 2ND FLOOR LEVEL BY ROOM 205. REME... | $0 | $0 | Jun 4, 2012 |
| Aug 26, 2011 | 34926570M | RESOLVE | CLASS - 2 | MOISTURE PENETRATION AT T5 UNIT THE EXTERIOR WALL HAS BECOME POROUS ALLOWING RAIN WATER TO ENTER REM: WATER PROOF EXT... | $0 | $0 | Oct 17, 2011 |
| Aug 26, 2011 | 34926563Y | RESOLVE | CLASS - 2 | MISSING DOORS THE FIRE PROOF SELF CLOSING DOORS WERE REMOVED ADJACENT TO 1FL ROOM 100 & 133 REM: REPLACE DOORS | $0 | $0 | Oct 17, 2011 |
| Aug 26, 2011 | 34926562M | RESOLVE | CLASS - 2 | RACKED DOOR AT NORTH BULKHEAD THE FIRE PROOF SELF CLOSING DOOR IS RACKED TO FRAME AND WILL NOT CLOSE REM: REPLACE DOOR | $0 | $0 | Oct 17, 2011 |
| Aug 26, 2011 | 34926561K | RESOLVE | CLASS - 2 | REISSUE 34856339Z OCCUPANCY CONTRARY TO C/O CELLAR LVL ROOM BLVD ARRANGED AND OCCUPIED AS A CLASSROOM CONTRARY TO CER... | $0 | $0 | Oct 17, 2011 |
| Aug 26, 2011 | 34926565H | RESOLVE | CLASS - 2 | 27-766 NO FRESH AIR VENT AT GAS METER ROOM NO FRESH AIR VENTILATIONS REM: PROVIDE FRESH AIR VENT | $0 | $0 | Oct 17, 2011 |
| Aug 26, 2011 | 34926567L | RESOLVE | CLASS - 2 | MISSING FIRE STOP AT ELECTRIC ROOM W/ NEW ELECTRIC SERVICE UNDER RECENT PERMIT NO FIRE STOP AT SEVERAL CONDUIT PENETR... | $0 | $0 | Oct 17, 2011 |
| Aug 26, 2011 | 34926569P | RESOLVE | CLASS - 1 | DEFECTIVE GUARD RAIL HANDRAILS AT ALL T UNITS T1 - T14 THE WOOD POSTS AND GUARD RAILS ARE ROTTEN OFFERING LITTLE SUPP... | $0 | $0 | Oct 17, 2011 |
| Aug 26, 2011 | 34926571Y | RESOLVE | CLASS - 2 | DEFECTIVE FLOORING AT T12 UNIT ROTTEN SUBFLOORING W/ HOLE LEFT OF ENTRY APPX 8" REM: REPAIR FLOORING | $0 | $0 | Oct 17, 2011 |
| Aug 26, 2011 | 34926560Z | RESOLVE | CLASS - 2 | REISSUE # 34856390Y LOOSE MISSING MORTAR JOINTS AT SOUTH EAST STOOP OF COURT YARD LOOSE AND MISSING MORTAR JOINTS IN ... | $0 | $0 | Oct 17, 2011 |
| Aug 26, 2011 | 34926568N | RESOLVE | CLASS - 2 | WORK W/O PERMIT DIVIDED STORAGE SPACE BEHIND STAGE INTO 3ROOMS UNDER APPLICATION #302561092 APPROVED 5/13/11 WORK COM... | $0 | $0 | Oct 17, 2011 |
| Aug 26, 2011 | 34926566J | RESOLVE | CLASS - 2 | UNAUTHORIZED STORAGE AT CELLAR GAS METER ROOM STORAGE OF A/C UNITS AND EQUIPEMENT REM: REMOVE ALL ITEMS MAINTAIN SERV... | $0 | $0 | Oct 17, 2011 |
| Aug 26, 2011 | 34926564X | RESOLVE | CLASS - 2 | CRACKED BRICK FRAME AT EAST CORNER ALONG PRESIDENT STREET AT 2STY STEP CRACKED OF BRICK FACADE REM: REPAIR BRICK MASONRY | $0 | $0 | Oct 17, 2011 |
| Apr 12, 2010 | 34856344N | RESOLVE | CLASS - 2 | USE OF PROHIBITED HARDWARE PER BC1008.1.8!.NOTED:STORAGE ROOM @ GYM FOUND WITH SLIDE BOLT LOCK & PADLOCK INSTALL ON T... | $0 | $0 | Sep 13, 2010 |
| Apr 12, 2010 | 34856339Z | RESOLVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY COFO ON DOB RECORDS!ROOM B140 ISARRANGED & OCCUPIED AS CLASSROOM CONTRARY TO NY... | $0 | $0 | Sep 13, 2010 |
| Apr 12, 2010 | 34856345P | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY!NOTED:ON THE,2ND FLR,SOUTH CORRIDOR FOUND WITH THE STORAGE OF CABINET... | $0 | $0 | Sep 13, 2010 |
| Apr 12, 2010 | 34856348K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN INTERIOR BLDG IN CODE COMPLIANT MANNER!CRACKED CONCRETE WALL BELOW SPLIT LEVEL FLR BOILER ROOM-CE... | $0 | $0 | Sep 13, 2010 |