ECB violations
139-147 33 Street, Brooklyn • Block 00680 • Lot 0054
28 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Nov 27, 2023 | 39100063Z | RESOLVE | CLASS - 2 | OBSERVED IN THE WATER HEATER ROOM LOCATED ON ROOF COUPLINGS SEVERELY RUSTED AND CORRODED. AS PER 102.3 MAINTENANCE. I... | $310 | $0 | Feb 7, 2024 |
| Nov 27, 2023 | 39100094L | RESOLVE | CLASS - 2 | ALARM ON THE CAR STATION INOPERATIVE, REPAIR. FIRE SERVICE JEWEL ON THE CAR STATION LIT UP WHEN FIRE SERVICE IS NOT A... | $310 | $0 | Feb 7, 2024 |
| Nov 22, 2023 | 39099948K | RESOLVE | CLASS - 2 | I OBSERVED THE VIOLATING CONDITIONS STATED IN ECB# 39083863P STILL IN EFFECT. NO CORRECTION AS REQUIRED BY COMMISSION... | $625 | $0 | Jun 21, 2024 |
| Nov 22, 2023 | 39099943L | RESOLVE | CLASS - 2 | I OBSERVED THE VIOLATING CONDITIONS STATED IN ECB# 39083862N STILL IN EFFECT. NO CORRECTION AS REQUIRED BY COMMISSION... | $1,250 | $0 | Feb 7, 2024 |
| Nov 22, 2023 | 39100046R | RESOLVE | CLASS - 1 | LARGE SECTION OF GLASS AWNING IS SHATTER AND BROKEN, WITH PIECES OF GLASS STILL ON GROUND LOCATED AT FRONT DOOR ENTRA... | $1,250 | $0 | Feb 7, 2024 |
| Nov 22, 2023 | 39099942J | ACTIVE | CLASS - 2 | I OBSERVED IN THE LL STAIRWELL LEADING TO THE 1ST FLOOR THE IMPROPERLY INSTALLED LIGHTING. THIS IS A MAJOR SHOCK HAZA... | $625 | $0 | Feb 7, 2024 |
| Nov 22, 2023 | 39099946R | RESOLVE | CLASS - 2 | I OBSERVED THE VIOLATING CONDITIONS STATED IN ECB# 39083861L STILL IN EFFECT. NO CORRECTION AS REQUIRED BY COMMISSION... | $1,250 | $0 | Feb 7, 2024 |
| Nov 22, 2023 | 39099944N | RESOLVE | CLASS - 1 | I OBSERVED THE DOOR TO THE ELECTRICAL ROOM AND THE EMERGENCY GENERATOR POWER OPEN DUE TO NO LATCHING SYSTEM AS IS REQ... | $6,250 | $0 | Sep 20, 2024 |
| Nov 22, 2023 | 39099945P | RESOLVE | CLASS - 1 | I OBSERVED ON ALL FLOORS THE ROOM LABELED " EMPLOYEES ONLY" THE EXCESSIVE STORAGE IN THE ELECTRICAL STORAGE. THIS IS ... | $6,000 | $0 | Sep 20, 2024 |
| Nov 22, 2023 | 39100047Z | RESOLVE | CLASS - 2 | IMPROPER STORAGE OF GARBAGE AND LUGGAGE CARTS IN FRONT CANOPY ENTRANCE, BLOCKING THE FRONT DOOR EGRESS/EMERGENCY EXIT... | $312 | $0 | Feb 7, 2024 |
| Nov 22, 2023 | 39099947Z | RESOLVE | CLASS - 2 | I OBSERVED ON THE ROOF THE MECHANICAL ROOM FOR THE GAS FIRED SYSTEMS WITHOUT A REMOTE SHUT-DOWN AS REQUIRED PER MC 10... | $3,125 | $0 | Feb 7, 2024 |
| Apr 14, 2023 | 39083863P | RESOLVE | CLASS - 1 | I OBSERVED ON ALL FLOORS THE ELECTRICAL CLOSET MARKED EMPLOYEES ONLY WITH EXCESSIVE STORAGE. THIS IS AN IMMEDIATE FIR... | $1,200 | $0 | Jul 17, 2023 |
| Apr 14, 2023 | 39083861L | RESOLVE | CLASS - 2 | I OBSERVED ON THE ROOF THE UNMARKED MECHANICAL ROOM WITH THE GAS-FIRED WATER HEATERS. THERE WAS NO REMOTE SHUT-DOWN A... | $1,250 | $0 | Jul 17, 2023 |
| Apr 14, 2023 | 39083860J | RESOLVE | CLASS - 1 | I OBSERVED ON THE ROOF THE GENERATOR OFFLINE AND IN FAULT MODE. THIS IS AN IMMEDIATE HAZARD AS THE GENERATOR IS AN IN... | $1,600 | $0 | Jul 17, 2023 |
| Apr 14, 2023 | 39083862N | RESOLVE | CLASS - 2 | I OBSERVED IN THE 1ST FLOOR STAIRWELL AND THE LOWER LEVEL EMPLOYEE RESTROOM IMPROPERLY INSTALL LIGHTING. THIS IS A MA... | $250 | $0 | Jul 17, 2023 |
| Feb 16, 2023 | 39079861J | RESOLVE | CLASS - 1 | 97-X-17 ELEVATOR OUT OF SERVICE. REPAIR AND CALL THE DOB ELEVATOR DIVISION AT (212)393-2144 FOR A RE-INSPECTION. | $312 | $0 | Oct 23, 2023 |
| Dec 6, 2021 | 39052322K | RESOLVE | CLASS - 1 | UPON INSPECTION DEVICE WAS FOUND OUT OF SERVICE. THIS IS THE ONLY ELEVATOR IN THE BUILDING. RESTORE TO SERVICE IMMEDI... | $1,250 | $0 | Apr 13, 2022 |
| Jun 2, 2021 | 39042075N | RESOLVE | CLASS - 1 | 1. SHORTEN GOVERNOR ROPES ( CEASE USE ) 2. PUT A SEAL ON THE HYDRAULIC VALVE WITH PRESSURE INFORMATION . 3. PROVIDE A... | $1,250 | $0 | Oct 6, 2021 |
| Jan 6, 2020 | 39015324L | RESOLVE | CLASS - 1 | CLASS 1 CEASE USE ITEMS...... ELECTRIC EYE INOPERATIVE ON LOBBY DOOR. EXCESSIVE RE-LEVELING ON THE UPPER FLOORS CASIN... | $1,250 | $0 | Oct 25, 2021 |
| Feb 6, 2018 | 38261141X | RESOLVE | CLASS - 1 | 45N10;05X10;70O02;39Q03;40B09:CEASE USE ITEM;BYPASSED/INOPERATIVE GOV SWITCH;MAIN DOOR ZONE LOCK RESTRICTOR;RELPLACE ... | $1,000 | $0 | Jun 27, 2018 |
| Mar 1, 2017 | 38252602P | RESOLVE | CLASS - 1 | CU-1X10,2X10. CU-1X10-IN CAR STOP SWITCH INOPERATIVE 2X10-IN CAR ALARM BELL INOPERATIVE. | $0 | $0 | Jun 5, 2017 |
| Feb 21, 2017 | 35228814H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 2-21-17 AT ABOVE ADDRESS NO UP TO DATE BOILER RECORDS ... | $0 | $0 | Apr 24, 2017 |
| Feb 21, 2017 | 35228821X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 2-21-17 IN SPRINKLER CONTROL ROOM O,S,& Y VALVES ARE I... | $500 | $0 | Jun 28, 2017 |
| Oct 5, 2009 | 34807296R | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE/POST SIGNS @ JOB SITE PURSUANT TO SUBSECTION.NO VALID FENCE PERMIT POSTED @ CONSTRUCTION SITE @ TH... | $0 | $0 | Nov 30, 2009 |
| Oct 3, 2006 | 32051949P | RESOLVE | Non-Hazardous | 50A/ 50B/ 50C/ FULTON V.T. BOILER, 15HP, NB 57614, GAS 1991 50(A) NO SECONDARY SCREW TYPE (SLOW) VALVE IS INSTALLED O... | $2,500 | $0 | Nov 20, 2006 |
| Oct 5, 2004 | 32046062H | RESOLVE | Non-Hazardous | 6A/32A 48B/38 50A/50B 50C/50D 50E/50F 44C 1982 FULTON NATL BD 41023 50A ADD A SLOW OPENING VALVE ON THE BOTTOM BLOW D... | $2,500 | $0 | Mar 21, 2005 |
| Aug 31, 1998 | 32016093N | RESOLVE | Non-Hazardous | 36 49 INSTALLED BOILER WITHOUT PERMITS GLASS IN STEAM GAGE MISSING BOILER ROOM TO BUILD | $1,000 | $0 | Apr 12, 1999 |
| Aug 31, 1998 | 32016094P | RESOLVE | Non-Hazardous | 36 49 INSTALLED BOILER WITHOUT PERMIT 10H.P. | $1,000 | $0 | Feb 8, 1999 |