ECB violations
349-365 38 Street, Brooklyn • Block 00700 • Lot 0045
40 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Nov 5, 2025 | 39165912L | RESOLVE | CLASS - 2 | OBSERVED THROUGHOUT THE BUILDING SPRINKLER HEADS OBSTRUCTED WHICH IS CONTRARY TO CODE SECTION BC 903.3.3, REPAIR AND/... | $1,250 | $1,250 | Jan 28, 2026 |
| Nov 3, 2025 | 39165829K | RESOLVE | CLASS - 2 | CLASS 2: PISTON OIL LEAKAGE, REPAIR. CLEAN OIL FROM TOP OF CAR AND THE PIT. C LEVEL HALL BUTTON LIGHT INOPERATIVE, RE... | $312 | $312 | Jan 14, 2026 |
| Mar 5, 2025 | 39140533K | RESOLVE | CLASS - 2 | FAILURE TO CERTIFY CORRECTIONS FOR VIOLATION NUMBER 39134219L, FILE A CERTIFICATE OF CORRECTION | $0 | $0 | May 14, 2025 |
| Jan 2, 2025 | 39134220Z | RESOLVE | CLASS - 2 | I OBSERVED IN THE WATER METER ROOM THE USE OF AN EXTENSION CORD SUPPLYING POWER TO THE CONDENSATE PUMP FOR THE A.C. U... | $0 | $0 | May 5, 2025 |
| Jan 2, 2025 | 39134219L | RESOLVE | CLASS - 1 | I OBSERVED THE INSTALLATION OF ELECTRICAL WIRING AND COMPONENTS FROM THE ELECTRICAL ROOM TO THE MEZZANINE WITH NO LIC... | $0 | $0 | May 5, 2025 |
| Jan 2, 2025 | 39134218J | RESOLVE | CLASS - 2 | I OBSERVED THE INSTALLATION OF BRANCH CIRCUIT WIRING, OVERCURRENT PROTECTION AND BREAKER ENCLOSURE TO SUPPLY POWER TO... | $0 | $0 | May 5, 2025 |
| Jan 2, 2025 | 39134214M | RESOLVE | CLASS - 1 | UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. OBSERVED UNSAFE STORAGE UNDERNERTH STAIRCASE A LEADING TO CELLA... | $2,500 | $2,500 | Feb 16, 2027 |
| Jan 2, 2025 | 39134213K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $2,500 | Feb 16, 2027 |
| Mar 27, 2023 | 39082329K | RESOLVE | CLASS - 2 | OBSERVED OBSTRUCTED SPRINKLER HEAD ON THE 2ND FLOOR. SPRINKLER HEAD ON THE 2ND FLOOR CEILING OBSTRUCTED BY CAP., REPA... | $0 | $0 | Jun 7, 2023 |
| Mar 27, 2023 | 39082327R | RESOLVE | CLASS - 2 | -FIRE STOP NEEDED AROUND STAND PIPES PENETRATION LOCATED AT STAIR CASE (A) 5TH FLOOR, ELAVATOR, AND ELECTRICAL ROOMS.... | $0 | $0 | Jun 7, 2023 |
| Mar 27, 2023 | 39082326P | RESOLVE | CLASS - 2 | -ILLEGAL LATCH BOLT LOCKS ON DOORS LOCATED THROUGHOUT FIRST FLOOR AND CELLAR LEVEL STAIR CASE(B) CLOSET., PROVIDE LEG... | $0 | $0 | Jun 7, 2023 |
| Mar 27, 2023 | 39082325N | RESOLVE | CLASS - 2 | -EMERGENCY DOOR DOES NOT CLOSE OR SHUT PROPERLY LOCATED AT STAIR CASE (B) ON ROOF LEVEL., REPAIR/REPLACE DOOR; REPAIR... | $0 | $0 | Jun 7, 2023 |
| Feb 25, 2020 | 39018287P | RESOLVE | CLASS - 2 | NOTED: OBSERVED STEP CRACKS AT EXTERIOR OF WATER HEATER ROOM AND STEP CRACKS ON PARAPET'S CMU WALL NEAR WATER HEATER ... | $0 | $0 | Jul 1, 2020 |
| Feb 25, 2020 | 35473152R | RESOLVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE.I OBSERVED ... | $400 | $0 | Jul 1, 2020 |
| Feb 25, 2020 | 39018289Z | RESOLVE | CLASS - 2 | NOTED: BOTH EXTERIOR EXIT DOORS THAT LEADS OUT TO EXPOSURE #2 (SOUTHWEST ELEVATOR) DO NOT SELF CLOSE, DOORS REMAIN IN... | $625 | $0 | Jul 1, 2020 |
| Feb 25, 2020 | 39018288R | RESOLVE | CLASS - 3 | NOTED: OBSERVED ON LEFT SIDE OF STAIRS GOING UP TO THE FIRST FLOOR IS EXTREMELY LOOSE AND ON THE VERGE OF BECOMING DE... | $0 | $0 | Jul 1, 2020 |
| Sep 24, 2019 | 38271784Z | RESOLVE | CLASS - 2 | 1L10,2L10,16L10,39B10:(1,L,10)EMERGENCY STOP SWITCH WORKS BUT NO BUZZER. (2,L,10)ALARM BELL DOES NOT WORK NO BUZZER. ... | $310 | $0 | Feb 26, 2020 |
| Aug 30, 2019 | 39008737Y | RESOLVE | CLASS - 1 | I OBSERVED IN THE ELECTRICAL EQUIPMENT ROOM THE INSTALLATION OF AN A/C DUCT SYSTEM FROM THE WATER METER ROOM TO THE E... | $1,600 | $0 | Oct 23, 2019 |
| Aug 30, 2019 | 39008736M | RESOLVE | CLASS - 2 | I OBSERVED THE INSTALLATION OF ROMEX FROM THE ELECTRICAL ROOM TO THE WATER METER ROOM TO SUPPLY POWER FOR A A/C UNIT.... | $1,200 | $0 | Oct 21, 2019 |
| Aug 30, 2019 | 39008738X | RESOLVE | CLASS - 2 | I OBSERVED THE COMPLETION OF WORK AND THE SUBMITTAL OF C OF C'S FOR ECB SUMMONSES ISSUED ON 08/27/2018. NO ELECTRICAL... | $625 | $0 | Oct 23, 2019 |
| Aug 30, 2019 | 39008739H | RESOLVE | CLASS - 2 | I OBSERVED THE INSTALLATION OF GFCI OUTLETS ON 1ST FLOOR MEZZANINE AND AN EQUIPMENT GROUNDING CONDUCTOR FOR ROOFTOP A... | $400 | $0 | Oct 23, 2019 |
| Feb 21, 2019 | 38268327X | RESOLVE | CLASS - 2 | 97L10 HYDRAULIC ELEVATOR, WHEN GOING TO FLOOR STOPS UP OR DOWN CAB JERKS HARD AND BOUNCES, REPAIR. | $1,562 | $0 | Jun 3, 2019 |
| Dec 27, 2018 | 38267090M | RESOLVE | CLASS - 1 | 1B10,2B10, CU44L10, 67X10. 1B10-EMERGENCY STOP SWITCH BUZZER WORKS SOMETIMES; 2B10-ALARM BELL INSUFFICIENT BUZZER WOR... | $1,280 | $0 | Apr 1, 2019 |
| Aug 27, 2018 | 35347255M | RESOLVE | CLASS - 2 | 350.60-FAILURE TO INSTALL EQUIPMENT GROUNDING CONSUCTOR.OBSERVED ON ROOFTOP AREA NO EQUIPMENT GROUNDING CONDUCTOR INS... | $0 | $0 | Dec 10, 2018 |
| Aug 27, 2018 | 35347256Y | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE GROUND FAULT CIRCUIT INTERUPPTION (GFCI)PROTECTION AS REQUIRED.OBSERVED ON 1ST FLOOR MEZZANINE ARE... | $0 | $0 | Dec 10, 2018 |
| Aug 27, 2018 | 35347257X | RESOLVE | CLASS - 2 | ELECTRICAL WORK WITHOUT A PERMIT.OBSERVED ON ROOFTOP AREA AND ALONG EXTERIOR WALL THE REMOVAL OF AN ILLUMINATED SIGN ... | $0 | $0 | Dec 10, 2018 |
| Nov 8, 2017 | 35274190X | RESOLVE | CLASS - 1 | AN UNLAWFUL ACT FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.FAILURE TO CORRECT & CERTIFY THE FOLLOWING ECB'S ... | $0 | $0 | Jan 26, 2018 |
| Sep 21, 2017 | 38257955N | RESOLVE | CLASS - 1 | 97X17 THE ONLY ELEVATOR IN THE BUILDING IS OUT OF SERVICE. UPON INSPECTION, THE DEVICE IS FOUND TOB E OUT OF SERVICE.... | $1,000 | $0 | Nov 6, 2017 |
| Jul 28, 2017 | 35287074L | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE(GFCI)GROUND FAULT CIRCUIT INTERRUPETER AS REQUIRED.OBSERVED ON ROOF TOP DEFECTIVE GFCI RECEPTACLE ... | $1,200 | $0 | Sep 18, 2017 |
| Jul 28, 2017 | 35287073J | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O A PERMIT. OBSERVED FEEDER CONDUCT & WIRING TO GENERATOR SYSTEM ON ROOF TOP & (AFS) SYSTEM FOR P/P... | $800 | $0 | Sep 18, 2017 |
| Feb 21, 2017 | 35229203N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: AT BLDG FRONT LEFT SIDE OF BLDG ENTRANCE DOOR,VERTICLE CRACK ... | $250 | $0 | Jun 12, 2017 |
| Feb 21, 2017 | 35229117R | RESOLVE | CLASS - 1 | MISC VIOL: UNPAINTED GAS PIPING NOT PROTECTED FROM THE ELEMENTS. AT THE TIME OF MY INSPECTION I OBSERVED ON THE ROOF ... | $400 | $0 | May 22, 2017 |
| Jan 27, 2017 | 38252653P | RESOLVE | CLASS - 2 | 5J1 ADJUST FRONT DOOR (EXCESSIVE GAP) | $0 | $0 | Apr 17, 2017 |
| Aug 19, 2011 | 38217882P | RESOLVE | CLASS - 2 | 48BB05,42G11,34M07,26D06,45V15,34Q03,05X10.(48BB)PRESSURE TEST TAG.(42G)UNREADABLE FUSES.(34M)RETURN LINE.(26D)SECURE... | $0 | $0 | Oct 3, 2011 |
| Aug 4, 2010 | 38210606R | RESOLVE | CLASS - 2 | 05B10,68M07,81M07,73B10,98U05,99U05,77U11. 05B- CAR DOORS NOT CLOSING STAY OPEN. 73B- RAILS AT 3RD FL LEVEL. 77U- NYC... | $0 | $0 | Dec 8, 2010 |
| Feb 12, 2009 | 34755426Y | RESOLVE | CLASS - 1 | "STOP ALL WORK".FAILURE TO SAFEGUARD ALL PERSON & PROPERTY AFFECTED BYCONSTRUCTION OPERATIONS.NOTED:CONSTRUCTION FENC... | $0 | $0 | Aug 9, 2010 |
| Jul 2, 2001 | 34295921R | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL: DEFECT IS: DEFECTINE EXTERIOR FACADE WALLS HAVE VERTICAL & HORIZONTAL CRA... | $0 | $0 | Oct 1, 2001 |
| Mar 19, 2001 | 34280477H | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN DEFECTS NOTED:HOLES IN WALLS AND FLOOR OF UNOCCUPIED 2ND FLOOR AREA AND EXTERIOR CRACKS IN FRONT ... | $2,500 | $0 | Jun 24, 2002 |
| Aug 3, 1999 | 38089088Y | RESOLVE | Non-Hazardous | 75U5,18Q3,74I11. 18-LOCK COVERS. 74-STEP TO MACHINE RM. | $180 | $0 | Jan 3, 2000 |
| Jan 6, 1998 | 38068890Z | RESOLVE | Non-Hazardous | 01M,18M,11D,11Q,28H,36T,36W,73X-RETURN TO SERVICE FOR COMPLETE INSPECTION BY THIS DEPT. 212-312-8740 | $500 | $0 | Feb 24, 1998 |