Skip to content

ECB violations

435-437 39 Street, Brooklyn • Block 00705 • Lot 0061

19 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Sep 17, 2025 39160770M RESOLVE CLASS - 2 OBSERVED ON THE FIRST FLOOR IN THE HOT WATER HEATER ROOM EXHAUSTED DISCHARGE VENT IS NOT SEALED AND USING INCORRECT F... $0 $0 Nov 26, 2025
Sep 17, 2025 39160761K RESOLVE CLASS - 2 CLASS 2 ITEMS: PIT LIGHT INOPERATIVE, REPAIR. PROVIDE UPDATED MAINTENANCE LOG $655 $0 Nov 26, 2025
Oct 15, 2024 39127790P RESOLVE CLASS - 1 I OBSERVED IN THE MAIN ELECTRICAL ROOM THE INSTALLATION OF DATA EQUIPMENT THAT COMPLETELY BLOCKS THE INCOMING ELECTRI... $250 $0 Aug 22, 2025
Oct 15, 2024 39127791R RESOLVE CLASS - 1 I NOTED THE FACILITATION OF THE RESPONDENT TO HAVE UNLICENSED ELECTRICAL WORK COMPLETED, IN THE WATER HEATER ROOM, TH... $4,800 $0 Aug 22, 2025
Oct 15, 2024 39127451K RESOLVE CLASS - 2 OBSERVED 2 PAINTED SPRINKLER HEADS IN THE WATER HEATER ROOM LOCATED ON THE SECOND FLOOR. AS PER 102.3 OF THE PLUMBING... $0 $0 Jan 8, 2025
Oct 15, 2024 39127561L RESOLVE CLASS - 1 EXCESSIVE STORAGE PLACED UNDERNEATH STAIRCASE LEADING BASEMENT LEVEL. UNSAFE STORAGE AND COMBUSTIBLE MATERIALS( TORCH... $1,250 $0 Aug 28, 2025
Oct 15, 2024 39127562N RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... $2,500 $0 Aug 28, 2025
Oct 15, 2024 39127792Z RESOLVE CLASS - 1 I OBSERVED IN THE MAIN ELECTRICAL ROOM THE INSTALLATION OF THE DISCONNECT SWITCH FOR THE EMERGENCY POWER AS PER BC 27... $625 $0 Aug 22, 2025
Oct 15, 2024 39127793K RESOLVE CLASS - 1 I OBSERVED IN THE WATER HEATER ROOM, IN A STORAGE ROOM UNDER THE STAIRS, AND IN THE MAIN ELECTRIC (FOR THE A.C), THE ... $1,200 $0 Aug 22, 2025
Oct 15, 2024 39127794M RESOLVE CLASS - 1 I OBSERVED IN THE WATER HEATER ROOM THE FLEXIBLE CORDS SUPPLYING POWER TO THE WATER HEATERS NOT TERMINATED WITH THE E... $400 $0 Aug 22, 2025
Oct 15, 2024 39127795Y RESOLVE CLASS - 1 I OBSERVED IN THE HALLS THROUGHOUT THE BUILDING THE FAILURE TO INSTALL TAMPER RESISTANT OUTLETS AS REQUIRED FOR AREAS... $400 $0 Aug 22, 2025
Oct 15, 2024 39127796X RESOLVE CLASS - 1 I OBSERVED THE INSTALLATION OF WIRING UNDER THE STAIRS, IN THE WATER HEATER ROOM AND THE MAIN ELECTRICAL ROOM, TO INS... $800 $0 Aug 22, 2025
Oct 15, 2024 39127789H RESOLVE CLASS - 2 I OBSERVED DEFECTIVE GROUND FAULT CIRCUIT INTERRUPTER OUTLETS ON THE ROOF (BEHIND THE DOOR) AND THE FOOD SERVICE AREA... $1,200 $0 Aug 22, 2025
Nov 22, 2016 35221975R RESOLVE CLASS - 2 WORK W/O A PERMIT. OBSERVED 2 ILLUMINATED ACCESSORY BUSINESS SIGNS. 1)FRONT YARD PARKING LOT APPROX 15FEET ABOVE GROU... $0 $0 Jan 9, 2017
Apr 9, 2008 34630242K RESOLVE Hazardous FAILED TO POST REQUIRED CONTRACTOR SIGN. NOTED: PARTIAL CMU WALLS HAVE BEEN BUILT UNDER PERMIT # 302295969 FOR ALT 1 ... $250 $0 Jun 2, 2008
Apr 9, 2008 34630243M RESOLVE Hazardous FAILURE TO SAFEGUARD PUBLIC & PROPERTY AFFECTED BY CONSTRUCTION OPERATIONS. NOTED: PARTIAL CMU WALLS CONSTRUCTED UNDE... $1,000 $0 Jun 2, 2008
Jun 9, 2003 34405857X RESOLVE Hazardous MECH. DEMOLITION WITHOUT PERMIT. AT TIME OF INSPECTION HOUSE IS UNDER DEMO. EXCAVATOR IS BEING USED TO DEMOLISH HOUSE... $2,000 $0 May 3, 2004
Jun 9, 2003 34405858H RESOLVE Hazardous FAILURE TO SAFEGUARD PUBLIC AND PROPERTY. AT TIME OF INSPECTION DEMO WAS IN PROCESS AND DEMO SITE IS NOT PROPERLY ENC... $1,500 $0 Jul 28, 2003
Jun 9, 2003 34405859J RESOLVE Hazardous FAILURE TO POST CONTRACTOR'S SIGN. AT TIME OF INSPECTION DEMO WAS IN PROGRESS AND NO CONTRACTOR'S SIGN POSTED. REMEDY... $500 $0 Mar 1, 2004