ECB violations
247-255 49 Street, Brooklyn • Block 00772 • Lot 0053
51 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Nov 13, 2025 | 39166816X | RESOLVE | CLASS - 2 | OBSERVED THROUGHOUT THE BUILDING SPRINKLER HEADS OBSTRUCTED BY PAINTED CAPS. ON THE ROOF SPRINKLER LINE COMING OUT OF... | $625 | $625 | Feb 25, 2026 |
| Nov 13, 2025 | 39166871Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $0 | $0 | Jan 21, 2026 |
| Mar 7, 2025 | 39140921M | RESOLVE | CLASS - 2 | FAILURE TO CERTIFY FOR CORRECTION FOR VIOLATION #39135325J, FILE A CERTIFICATE OF CORRECTION | $1,250 | $0 | Apr 27, 2026 |
| Mar 7, 2025 | 39140922Y | RESOLVE | CLASS - 2 | FAILURE TO CERTIFY FOR CERTIFICATE OF CORRECTION FOR VIOLATION #39135326L, FILE A CERTIFICATE OF CORRECTION | $1,250 | $0 | Apr 27, 2026 |
| Mar 7, 2025 | 39140920K | RESOLVE | CLASS - 2 | FAILURE TO CERTIFY CORRECTION FOR VIOLATION #39135314Y, FILE A CERTIFICATE OF CORRECTION | $625 | $0 | May 14, 2025 |
| Jan 13, 2025 | 39135315X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED PAINTED SPRINKLER CAPS THROUGHOUT BUILDING. POTENTIAL... | $1,250 | $1,250 | Apr 21, 2026 |
| Jan 13, 2025 | 39135314Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $625 | $0 | Apr 21, 2026 |
| Jan 13, 2025 | 39135322Y | RESOLVE | CLASS - 2 | I OBSERVED IN THE ELEVATOR MOTOR ROOM THE UNPERMITTED USE OF EMT THROUGH CONCRETE WITHOUT PROTECTION FROM DAMAGING AG... | $0 | $0 | Oct 17, 2025 |
| Jan 13, 2025 | 39135326L | RESOLVE | CLASS - 1 | I OBSERVED THE DISCONNECTION OF ELECTRICAL POWER FROM THE EXISTING WATER HEATERS ON THE 3RD AND 4TH FLOORS. NO PERMIT... | $4,800 | $0 | Oct 6, 2025 |
| Jan 13, 2025 | 39135323X | RESOLVE | CLASS - 2 | I OBSERVED ALONG THE EXTERIOR OF THE PROPERTY DEFECTIVE LIGHTING. ALL EXTERIOR LIGHTING ALONG THE EGRESS SHALL BE MAI... | $0 | $0 | Oct 6, 2025 |
| Jan 13, 2025 | 39135324H | RESOLVE | CLASS - 2 | I OBSERVED IN THE ROOFTOP ELEVATOR MOTOR ROOM A DEFECTIVE GFCI IN USE. UPON TESTING THE OUTLET, THE RESET BUTTON ISSU... | $0 | $0 | Oct 6, 2025 |
| Jan 13, 2025 | 39135325J | RESOLVE | CLASS - 1 | I OBSERVED IN THE HOT WATER HEATER ROOM THE DISCONNECTION OF THE POWER FOR THE PREVIOUS HOT WATER HEATER AND THE IMPR... | $1,600 | $0 | Oct 17, 2025 |
| Jan 13, 2025 | 39135320K | RESOLVE | CLASS - 1 | I OBSERVED ON THE FIRST FLOOR THE UNPERMITTED USE OF FLEXIBLE CORDS, I NOTED EXTENSION CORDS PASSING THROUGH THE OFFI... | $1,600 | $0 | Oct 17, 2025 |
| Jan 13, 2025 | 39135316H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1 (2014 COD... | $1,250 | $1,250 | Apr 21, 2026 |
| Jan 13, 2025 | 39135313M | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING DOOR AT GAS METER ROOM. POTENTIAL FIRE HAZARD., REPAIR/REPLACE ... | $625 | $0 | May 5, 2025 |
| Jan 13, 2025 | 39135321M | RESOLVE | CLASS - 2 | I OBSERVED IN THE THE ELEVATOR CAB LIGHTS SWITCH AND THE HALLWAYS AIR HANDLER SWITCH THE IMPROPER TERMINATION OF THE ... | $2,400 | $0 | May 5, 2025 |
| Nov 15, 2023 | 39099403K | RESOLVE | CLASS - 2 | BOX HOLE CUT OUT OF CEILING IN THE WATER METER MECHANICAL ROOM, HOLES PENETRATIONS FOUND WITH I.T. (CABLE/PHONE/INTER... | $625 | $0 | Jun 24, 2024 |
| Nov 15, 2023 | 39099400P | RESOLVE | CLASS - 2 | OBSERVED NO VENTILATION IN THE GAS METER ROOM LOCATED IN THE BASEMENT/CELLAR. AS PER FGC E4 THE AREA IN WHICH THE MET... | $655 | $0 | Jun 24, 2024 |
| Mar 16, 2022 | 39058146H | RESOLVE | CLASS - 2 | I OBSERVED ON ALL FLOORS AT THE ENTRANCE OF THE MECHANICAL ROOMS NO REMOTE SHUT DOWN AS REQUIRED IN MC 1006.8.1; MC 1... | $625 | $0 | Jul 20, 2022 |
| Dec 6, 2021 | 39052259R | RESOLVE | CLASS - 1 | ELECTRICAL BRAKE MONITORING SWITCH NOT WORKING HAZARDOUS CONDITION (CU). | $1,250 | $0 | Apr 13, 2022 |
| Aug 10, 2020 | 39026657N | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $1,250 | $0 | Dec 16, 2020 |
| Jun 25, 2019 | 35423800K | RESOLVE | CLASS - 1 | UNLAWFUL ACT, FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. RECORDS INDICATE NO APPLICATION FILED TO CORRECT, ... | $0 | $0 | Mar 9, 2020 |
| May 14, 2019 | 35422414H | RESOLVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT IN USE. OBSERVED PTAC WALL MOUNTED HEATING / COOLING UNITS WITH AN ... | $1,630 | $0 | Aug 26, 2019 |
| Apr 23, 2019 | 35358978J | RESOLVE | CLASS - 1 | UNLAWFUL ACT. FAILURE TO COMPLY W/ AN ORDER OF THE COMMISSIONER. RECORDS INDICATE NO APPLICATION FILED TO CORRECT,CER... | $2,500 | $0 | Nov 6, 2019 |
| Feb 26, 2019 | 35383802K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALL(S)OR APPURTENANCES.NOTED:OBSERVED ON THEROOF BELOW THE PARAPET WALL,LOOSE,DETACHED & MI... | $640 | $0 | Sep 4, 2019 |
| Feb 26, 2019 | 35386552K | RESOLVE | CLASS - 1 | CONDUCTORS OF THE CIRCUIT ARE INSTALLED IN SEPERATE RACEWAYS. I OBSERVED IN SERVICE SWITCH #1 THE NEUTRAL UNGROUNDED ... | $815 | $0 | Sep 4, 2019 |
| Feb 26, 2019 | 35386551Z | RESOLVE | CLASS - 1 | UNSAFE ELECTRICAL EQUIPMENT UN USE. I OBSERVED THROUGHOUT THE BUILDING20 AMP PTAC UNITS (HVAC)FUSEDE AT 30 AMPS. I OB... | $1,280 | $0 | Sep 4, 2019 |
| Feb 10, 2018 | 35284285H | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35286772Y ISSUED ON 07/28/17 & TO FILE A C OF C PURSUAN... | $2,000 | $0 | Apr 16, 2018 |
| Jan 24, 2018 | 38260748H | RESOLVE | CLASS - 2 | 2X10,59BB7,14M7. 2X10-IN CAR PHONE INOPERATIVE; 59BB7-BRAKE MAINTENANCE EXPIRED; 14M7-PROVIDE IN CAR MIRROR. | $530 | $0 | Mar 19, 2018 |
| Dec 23, 2017 | 35281883Y | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35286772Y ISSUED ON 07/28/17 & TO FILE A C OF C PURSUAN... | $6,000 | $0 | Feb 12, 2018 |
| Nov 16, 2017 | 35281001N | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35286772Y ISSUED ON 07/28/17 AND TO FI... | $12,000 | $0 | Jan 8, 2018 |
| Jul 28, 2017 | 35287071X | RESOLVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,MATERIALS APPARATUS,DEVICES APPLIANCE OR WIRING IN USE. OBSERVED IN... | $800 | $0 | Sep 22, 2017 |
| Jul 28, 2017 | 35286772Y | RESOLVE | CLASS - 1 | WORK W/OUT A PERMIT. OBSERVED ON THE 2ND FLR IN THE MECHANICAL ROOM A HOT WATER HEATER STORAGE TANK INSTALLED W/ FLUE... | $8,000 | $0 | Nov 6, 2017 |
| Jul 28, 2017 | 35287070Y | RESOLVE | CLASS - 1 | SEC. 250.04 FAILURE TO INSTALL GROUNDING ELECTRODE CNDUCTOR IN ACCORDANCE W/SECTION. OBSERVED GROUNDING CONDUCTOR INS... | $12,000 | $0 | Nov 13, 2017 |
| Jul 28, 2017 | 35287072H | RESOLVE | CLASS - 2 | FAILURE TO INSTALL(GFCI)GROUND CIRCUIT INTERRUPTER AS REQUIRED. OBSERVED IN LAUNDRY ROOM RECEPTACLE OUTLETS W/NO GFCI... | $2,400 | $0 | Sep 18, 2017 |
| Jul 28, 2017 | 35287069R | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O A PERMIT. OBSERVED EMERGENCY BACK UP GENERATOR ON ROOF W/WIRING FRON CELLAR ELECTRICAL ROOM,& EME... | $1,600 | $0 | Sep 22, 2017 |
| Jul 28, 2017 | 35286773X | RESOLVE | CLASS - 1 | FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED. OBSERVED FROM DOB RECORDS THAT A HOT WATER HEATER STORAGE TANK... | $2,500 | $0 | Nov 6, 2017 |
| Apr 21, 2017 | 35233355Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION#35228919Y ISSUED ON 02/22/17& TO FILE A CE... | $800 | $0 | Jun 26, 2017 |
| Feb 22, 2017 | 35228918M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER:FAILURE TO OBSERVE LAW OF DRAINAIGE SYSTEM-PC702.1-27-911.OBSERVED ... | $500 | $0 | Jun 26, 2017 |
| Feb 22, 2017 | 35228916Z | RESOLVE | CLASS - 1 | FGC411.1/MISC VIOLATION;OBSERVED RESID GAS FLEX ON COMMERCIAL DRYERS HARD PIPING REQUIRED FOR COMM EQUIPT.PHOTOS TAKE... | $800 | $0 | Jul 14, 2017 |
| Feb 22, 2017 | 35228917K | RESOLVE | CLASS - 2 | WORK WITHOUT A PERMIT.IN LAUNDRY ROOM-REMOVED LAUNDRY SINK NO DOB PERMITS ON FILE.PHOTOS TAKEN.REM:OBTAIN A PERMIT. | $400 | $0 | Jul 14, 2017 |
| Feb 22, 2017 | 35228919Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.OBSERVED AT TOP MOSTBULKHEAD STAIRS NO SPRINKLER INSPECTIONS TEST G... | $500 | $0 | Jun 26, 2017 |
| Sep 10, 2016 | 35207517Z | RESOLVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BUILDING DEPT RECRODS. NOTED: PER CO NO. 302370... | $0 | $0 | Jan 3, 2017 |
| Sep 7, 2016 | 35207157Y | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:AT CELLAR GAS METER ROOM THERE IS NO FRESH AIR VENT PROVIDED. R... | $0 | $0 | Mar 22, 2017 |
| Mar 7, 2008 | 34635984M | RESOLVE | Hazardous | FAILURE TO PROVIDE ADEQUATE PROTECTION FOR SIDEWALK DURING CONSTRUCTION OPERAT. UPON INSPEC. NOTED:THE SIDE OF THE SH... | $2,000 | $0 | Apr 28, 2008 |
| Jan 14, 2004 | 34399345Y | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BLDG WALL.PARAPET WALL LEANING TOWARDS ROOF CRACKED BULGING SEPERATING BRICK WORK ACROSS... | $2,000 | $0 | Aug 9, 2004 |
| Jun 10, 2003 | 34400426L | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL. NOTED: PARAPET WALL LEANING BACK TOWARDS ROOF. DISLACED, CRACKED, BULGING... | $800 | $0 | Sep 22, 2003 |
| Aug 1, 2002 | 34341829Z | RESOLVE | Hazardous | FAILURE TO MAINTIAN EXTERIOR BUILDING WALL NOTED: DISPLACED BUILGED AND SEPARATIUP BRICK (LEANINP) PARAPET WALL ACROS... | $800 | $0 | Jan 12, 2004 |
| Mar 21, 2002 | 34295462R | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL. NOTED: DISPLACED, BULGED+SEPARATING BRICK(LEANNING) PARAPET WALL ACROOS E... | $800 | $0 | Jul 14, 2004 |
| Aug 15, 2001 | 34291103R | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BLDG WALL HAZAROUS DEFECTS ARE:CRAKED,LOOSE & DEFECTIVE BRICHWORK IN VARIOUS AREA WEST E... | $2,500 | $0 | Sep 24, 2001 |