ECB violations
533-559 Prospect Place, Brooklyn • Block 01156 • Lot 0080
35 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jul 23, 2026 | 39197330H | ACTIVE | CLASS - 2 | 1) THERE IS A COUNTERWEIGHT ROLLER (TOP) THAT HAS A WORN BEARING (8.11.2.1.3). 2) THE DUST COVERS ARE HITTING THE CAR... | $625 | $625 | Oct 7, 2026 |
| Jul 23, 2026 | 39197331J | ACTIVE | CLASS - 2 | 1) THERE IS A WORN MOTOR BRUSH AND THE COMMUTATOR IS WORN AND SPARKING (8.11.2.1.2). 2) THERE IS A DOOR CLUTCH ROLLER... | $625 | $625 | Oct 7, 2026 |
| May 15, 2026 | 39188861M | RESOLVE | CLASS - 2 | CLASS 2: 1) FIREFIGHTER SERVICE PHASE 1 KEY TURNS 360 DEGREES ALTHOUGH ELEVATOR RECALL FUNCTIONS NORMALLY. VIOLATION ... | $0 | $0 | Jul 22, 2026 |
| May 15, 2026 | 39188862Y | RESOLVE | CLASS - 2 | CLASS 2: 1) FIREFIGHTER SERVICE PHASE 1 KEY TURNS 360 DEGREES ALTHOUGH ELEVATOR RECALL FUNCTIONS NORMALLY. VIOLATION ... | $0 | $0 | Jul 22, 2026 |
| Jan 20, 2026 | 39174526H | RESOLVE | CLASS - 2 | 1) THE STEADING PLATE ARE WORN. 2) THERE IS A NOISE IN THE HOISTWAY AS THE CAR MOVES UP AND DOWN (THE SAFETY MAY HAVE... | $0 | $0 | Apr 1, 2026 |
| Jan 20, 2026 | 39174525X | RESOLVE | CLASS - 2 | 1) THE DOOR CLUTCH RETRACTING VANE IS HITTING THE ROLLER ON THE 8TH FLOOR. 2) THE TOP OF CAR LIGHT IS NOT WORKING. | $0 | $0 | Apr 1, 2026 |
| Jul 21, 2025 | 39154290M | RESOLVE | CLASS - 2 | CLASS 2: MACHINE OIL LEAKAGE DRIPPING ON TOP OF THE CAR. THIS CONDITION MAKES IT IMPOSSIBLE TO TURN IN-CAR FAN ON. HO... | $0 | $0 | Oct 1, 2025 |
| May 7, 2024 | 39113690K | RESOLVE | CLASS - 2 | IN APT 9M, WATER DAMAGE HAS OCCURRED AT CEILING,IN LIVING ROOM AND KITCHEN AREA. FINISHED CEILING PEELING., REPAIR AN... | $310 | $0 | Jul 17, 2024 |
| Nov 13, 2023 | 39099152P | RESOLVE | CLASS - 1 | BRAKE IS NOT LIFTING. C/U. REPAIR BRAKE. BRING TEST WEIGHTS FOR REINSPECTION. 125%. | $1,250 | $0 | Jan 17, 2024 |
| Jul 9, 2023 | 39089915P | RESOLVE | CLASS - 2 | CLASS 2: PHONE INOPRATIVE REPAIR & PROGRAM TO 24 HR EMERGENCY OPERATOR. DROP CEILING TILES MISSING. PROVIDE NEW TILES... | $310 | $0 | Sep 13, 2023 |
| Jan 3, 2023 | 39076809Z | RESOLVE | CLASS - 2 | REPAIR IN-CAR EMERGENCY PHONE ( OPRERATOR CAN NOT HEAR ME )., CLEAN CAR TOP (OIL LEAK)., CLEAN HOIST MACHINE (OIL LEA... | $0 | $0 | Mar 15, 2023 |
| Dec 9, 2022 | 37024554Z | ACTIVE | CLASS - 2 | FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 9A REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... | $1,250 | $0 | Jun 12, 2023 |
| Oct 17, 2021 | 39049692K | RESOLVE | CLASS - 2 | CLASS 2 VIOLATION ISSUED, PIT MISSING LADDER, PROVIDE ,/ IN CAR PHONE NOT WORKING,REPAIR,/MOTOR ROOM DOOR DAMAGE, REP... | $625 | $0 | Mar 30, 2022 |
| Jun 29, 2020 | 37019230X | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35264608P ISSUED ON 10/17/2017,AND TO FILE... | $625 | $0 | Nov 18, 2020 |
| Apr 18, 2019 | 38269378K | RESOLVE | CLASS - 2 | 02X10,01B10,52M07,53M07,39Y02,52Y02,44Y09,39X10,57BB07; 02.X.10 REPAIRINSIDE CAR PHONE(REPAIR AUDIBLE STOP SWITCH 01.... | $310 | $0 | Jul 29, 2019 |
| Feb 4, 2019 | 35383055X | RESOLVE | CLASS - 2 | PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATIONS. AT TIME OF INSPECTION I OBSERVED SIDEWALK SHED IN PLACE. FAI... | $2,400 | $0 | Sep 16, 2019 |
| Sep 26, 2018 | 35344969K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN EXTERIOR BLDG FACADE AND APPURTENANCES.NOTE: AT THE TIME OF INSPECTION BUILDING FACADE OBSEVE VAR... | $2,500 | $0 | Jun 19, 2019 |
| May 18, 2018 | 37010722L | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT ACCEPTABLE 8TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS & APPUR... | $1,250 | $0 | Feb 20, 2019 |
| Oct 17, 2017 | 35264608P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN EXTERIOR BLDG WALLS & APPURTENANCES.@TIME OF INSP OBSERVED OF EXP#1 SOUTH ELEVATION CRACKS @10FL ... | $1,000 | $0 | Dec 4, 2017 |
| Apr 11, 2017 | 35253733K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALLS AND APPURTENANCES NOTED AT TIME OF INSPECTION (I) AT EXP1 A-SPALLED BRICKWORK AT P... | $500 | $0 | Jun 6, 2017 |
| Apr 20, 2016 | 38242160H | RESOLVE | CLASS - 2 | 21J01,41B07,56O02,59O02,68B07,17B07. 21J01-THE ELEVATOR IS CLIPPING THE DOOR LOCKS DURING TRAVEL; 41B07-THE LOCK ON D... | $0 | $0 | Jun 13, 2016 |
| Apr 20, 2016 | 38242159K | RESOLVE | CLASS - 2 | 17B07,56O02,59O02,68B07,100M07. 17B07-FIRE GIBS ARE TOO SHORT; 56O02- IL ON HOIST MACHINE; 59O02-OIL FILM IN BRAKE AR... | $0 | $0 | Jun 13, 2016 |
| Jan 7, 2010 | 36011040M | RESOLVE | CLASS - 2 | FAILURE TO FILE AN ACCEPTABLE SIXTH ROUND TECHNICAL REPORT IN COMPLIANCE W/CODE PROVISIONS:PERIODIC INSPECTION OF EXT... | $800 | $0 | Mar 29, 2010 |
| Sep 29, 2009 | 34809664K | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPT OF BUILDINGS NOTED:... | $800 | $0 | Mar 1, 2010 |
| Sep 29, 2009 | 34809663Z | RESOLVE | CLASS - 1 | ALTERED/CHANGED BUILDING OCCUPIED W/O A VALID C OF O AS PER 28-118.3.1 28-118.3.2. NOTED: BUILDING ALTERED UNDER ALT ... | $1,000 | $0 | Mar 1, 2010 |
| Jul 7, 2009 | 36006535H | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT AN ACCEPTABLE SIXTH ROUND TECHNICAL REPORT IN COMPLAINCE WITH CODE PROVISIONS: PERIODIC INSPECTION ... | $800 | $0 | May 3, 2010 |
| Apr 3, 2009 | 34767356X | RESOLVE | CLASS - 1 | ALTERED BLDG OCCUPIED W/O A VALID C OF O 80% OCCUPANCY OBSERVED NO C OF O AVAILABLE AT THE RENTAL MGMT OFFICE AT THE ... | $1,000 | $0 | Jun 1, 2009 |
| Jan 13, 2009 | 34739996X | RESOLVE | CLASS - 2 | ALTERED/CHANGED BLDG OCCUPIED W/O A VALID C OF O AS PER 28-118.31 - 28-118.3.2. 90% & OCCUPANCY OBSERVED AT THE TIME ... | $500 | $0 | Mar 9, 2009 |
| Feb 12, 2008 | 34611841Z | RESOLVE | Hazardous | FAILURE TO COMPLY W/THE COMM'S ORDER TO CORRECT THE VIOLATING CONDITION & FILE A C OF O W/THE NYC DOB FOR NOTICE OF V... | $500 | $0 | Apr 7, 2008 |
| Jul 19, 2007 | 34573109N | RESOLVE | Non-Hazardous | ALTERED BLDG OCCUPIED W/O A VALID C OF O. ALT TYPE 1 #301755312. REMEDY: OBTAIN A VALID C OF O. | $180 | $0 | Sep 17, 2007 |
| Jun 3, 2005 | 34475658R | RESOLVE | Non-Hazardous | ALTERED BUILDING OCCUPIED WITHOUT A VALID CERTIFICAE OF OCCUPANCY TIME OF INSPECTION NUMBER OF DWELLING IS 83 UNOCCUP... | $350 | $0 | Dec 14, 2005 |
| Sep 24, 2001 | 38118567L | RESOLVE | Non-Hazardous | 35Z2/ 35Z14/ 44K11/ 2B11/ 57Z2/ 30O2/ 35- WATER ABOUT 2" INCH MOTOR ROOM- 44 GENERTOR RUSTED FROM WATER | $350 | $0 | Nov 19, 2001 |
| Jul 26, 1999 | 38089228R | RESOLVE | Non-Hazardous | 01L 44D 35B 36D 01 REPLACE CAR STOP SWITCH 36 PROIVDE LOCK AT MR 44 PROPERLY WIREING AT GENERATOR SECURE 35 PROVIDE L... | $350 | $0 | Oct 18, 1999 |
| Jul 27, 1993 | 34095917H | RESOLVE | Hazardous | FAILURE TO SUBMIT A 3RD ROUND TECHNICAL REPORT. PERIODIC INSPECTION OFEXTERIOR WALL AND APPURTENANCES. AS REQUIRED BY... | $500 | $0 | Nov 29, 1993 |
| Mar 2, 1993 | 38030283N | RESOLVE | Non-Hazardous | 08V 09H 16H 35O 37G | $200 | $0 | Jun 28, 1993 |