ECB violations
1418-1424 Atlantic Avenue, Brooklyn • Block 01202 • Lot 0032
46 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Feb 4, 2026 | 39175906Y | RESOLVE | CLASS - 1 | RTS CLASS 1: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-9... | $1,250 | $1,250 | Apr 15, 2026 |
| Dec 19, 2025 | 39171031M | RESOLVE | CLASS - 1 | CLASS 1 RTS: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-9... | $1,250 | $1,250 | Feb 25, 2026 |
| Jul 21, 2025 | 39154319R | RESOLVE | CLASS - 2 | CLASS 2: CAR OPERATING PANEL FRONT DOOR UNLOCKED, SECURE. INSUFFICIENT IN-CAR LIGHTING, REPAIR. | $0 | $0 | Oct 1, 2025 |
| Jan 14, 2025 | 39135523K | RESOLVE | CLASS - 1 | UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. OBSERVED UNSAFE STORAGE UNDERNEATH STAIRCASE AT BASEMENT LEVEL.... | $2,500 | $2,500 | May 9, 2025 |
| Jan 14, 2025 | 39135527H | RESOLVE | CLASS - 2 | I OBSERVED IN THE ELEVATOR MOTOR DISCONNECT THE IMPROPER FUSING OF THE CONDUCTORS, ALL FUSES SHALL BE COORDINATED OF ... | $1,200 | $1,200 | May 9, 2025 |
| Jul 26, 2024 | 39119918P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. CLASS 2 ITEMS: OIL LEAK IN THE MOTOR ROOM, SEAL THE LEAK AND C... | $625 | $315 | Oct 2, 2024 |
| Nov 9, 2023 | 39099097L | RESOLVE | CLASS - 2 | FIRE PROOF SELF-CLOSING DOOR DOES NOT SELF-CLOSE, ROOF LEVEL, STAIRCASE A., REPAIR/REPLACE DOOR | $0 | $0 | May 1, 2024 |
| Mar 8, 2022 | 35644420H | RESOLVE | CLASS - 1 | OCCUPANCY CONTRARY TO THAT ALLOWED BY CERTIFICATE OF OCCUPANCY OR BUILDING DEPT RECORDS. OBSERVED CERTIFICATE OF OCCU... | $1,250 | $250 | Aug 8, 2024 |
| Mar 8, 2022 | 35644419K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NO FIRE STOPPING PER BC 712.3;27-345.OBSERVED AT 5TH 4TH 3RD 2N... | $0 | $0 | Jul 27, 2022 |
| Mar 8, 2022 | 39057601X | RESOLVE | CLASS - 2 | I OBSERVED ON ALL FLOORS NO REMOTE SHUT-OFF SWITCHES AT THE ENTRANCE OF THE MECHANICAL ROOMS FOR THE GAS FIRED WATER ... | $1,250 | $1,250 | Apr 1, 2024 |
| Oct 5, 2021 | 39048700R | RESOLVE | CLASS - 2 | OPEN BALL VALVES IN ROOM WHERE HOT WATER HEATERS ARE NEED TO BE PIPED DOWN 8" OFF FLOOR, MAINTAIN BOILER; CORRECT VIO... | $310 | $0 | Mar 2, 2022 |
| Feb 11, 2020 | 39017344H | RESOLVE | CLASS - 2 | FIRE STOP NOT DONE IN THE MAIN ELECTRICAL ROOM AND GAS METER ROOM, FIRE BLOCK USED WHICH DOES NOT MEET THE FIRE RATIN... | $1,250 | $0 | Mar 10, 2021 |
| Aug 2, 2019 | 39007055M | RESOLVE | CLASS - 2 | OBSERVED ON ROOFTOP THE REMOVAL AND RELOCATION OF A EQUIPMENT DISCONNECT FOR A HVAC SYSTEM; THE INSTALLATION OF CONDU... | $2,000 | $0 | Jan 23, 2020 |
| Aug 2, 2019 | 39007056Y | RESOLVE | CLASS - 2 | OBSERVED THE CORRECTION OF ECB #35386388H WRITTEN ON 02/11/2019 THAT STATED NO ACCESS/WORKSPACE TO EQUIPMENT DISCONNE... | $3,125 | $0 | Jan 23, 2020 |
| Feb 11, 2019 | 35386388H | RESOLVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE. OBSERVED O... | $830 | $0 | Nov 4, 2019 |
| Feb 20, 2018 | 35317553N | RESOLVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY C OF O OR BLDG DEPT RECORDS. NOTED: OBSERVED ON THE 3RD FL,ROOMS 301,307,308,AR... | $600 | $0 | Jun 11, 2018 |
| Jul 19, 2017 | 35272444H | RESOLVE | CLASS - 1 | FGC.403.8/MISCELLANEOUS VIOLATION:UNPAINTED GAS PIPING NOT PROTECTED FROM THE ELEMENTS.OBSERVED GAS PIPING ON ROOF UN... | $400 | $0 | Sep 11, 2017 |
| Jul 19, 2017 | 35272446L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED EXCESSIVE STORAGE IN MECHANICAL ROOMS ON 2ND AND 5TH F... | $250 | $0 | Nov 9, 2017 |
| Jul 19, 2017 | 35286726N | RESOLVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,MATERIALS APPARATUS,DEVICES,APPLIANCE OR WIRING IN USE. OBSERVED RE... | $400 | $0 | Nov 9, 2017 |
| Jul 19, 2017 | 35272445J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED 1ST FLRSPRINKLER HEAD INSTALLED TO HIGH INSIDE OF CEIL... | $250 | $0 | Nov 9, 2017 |
| Jul 19, 2017 | 35286727P | RESOLVE | CLASS - 1 | OBSERVED GROUNDING CONDUCTOR ENTER ELECTRICAL ROOM THROUGH SHEETROCK WALL FROM WATER METER ROOM YET OBSERVED NO WATER... | $1,200 | $0 | Oct 3, 2017 |
| Jul 19, 2017 | 35286725L | RESOLVE | CLASS - 2 | ELECTRICAL WORK W/O A PERMIT. OBSERVED SWITCH PUTLETS CONNECTED TO ELECTRIC HEATERS IN STAIRWAY & BASEMENT AREA. NO P... | $400 | $0 | Nov 8, 2017 |
| Feb 8, 2017 | 35229187M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 2/08/17SPRINKLER HEAD IS IN CEILING. PHOTOS TAKEN. REM... | $250 | $0 | Mar 27, 2017 |
| Feb 8, 2017 | 35229188Y | RESOLVE | CLASS - 1 | FGC411.1. RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT. OBSERVED ON 2/08/17 RESIDENTIAL GAS FLEX USED ON DRYERS ... | $0 | -$250 | Apr 3, 2017 |
| Apr 6, 2016 | 38241865N | RESOLVE | CLASS - 2 | 61G11,01B01,68B07,60Q03,42M07,48Y13,17H11. 61G-UNREADABLE FUSES;61B- CAR DOOR DOES NOT FULLY OPEN WHEN ENGAGED; 68B-W... | $530 | $0 | May 23, 2016 |
| Jul 26, 2012 | 34941095H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN ADEQUATE HOUSEKEEPING PER SECTION REQUIREMENTS: NOTED AT FRONT & REAR YARD OF PREMISES,IT HAVE DE... | $0 | $0 | Sep 10, 2012 |
| Jun 18, 2012 | 34958455N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN ADEQUATE HOUSEKEEPING PER SECTION REQUIREMENTS: NOTED: 5 STORY NB HAVE CONSTRUCTION DEBRIS THROUG... | $400 | $0 | Aug 6, 2012 |
| Apr 24, 2012 | 34941818M | RESOLVE | CLASS - 1 | INADEQUATE SAFETY MEASURES:OPERATION OF HOISTING EQUIPMENT IN UNSAFE MANNER.NOTED:@ 5 FLR LEVEL OF NEW BLDG A HYDRADI... | $4,800 | $0 | Aug 22, 2012 |
| Apr 24, 2012 | 34941814P | RESOLVE | CLASS - 1 | LIFELINES & SUSPENSION ROPES.NOTED:BLDG @ 5 STORIES HIGH BLOCK & BRICK WORK BEING PERFORMED BY NUMEROUS WORKERS @ EXP... | $8,000 | $0 | Sep 10, 2012 |
| Apr 24, 2012 | 34941816Z | RESOLVE | CLASS - 2 | 3303.14)DRAINAGE:NO CONDITION SHALL BE CREATED AS A RESULT OF CONSTRUCTION OPERATION THAT WILL INTERFERE W/ NATURAL S... | $0 | $0 | Jul 23, 2012 |
| Apr 24, 2012 | 34941815R | RESOLVE | CLASS - 1 | FAILURE TO INSTITUTE/MAINTAIN SAFETY EQUIPMENT MEASURES OR TEMP CONSTRUCTION.NO TOE BOARDS.NOTED:@ ELEVATOR SHAFT OPE... | $1,000 | $0 | Jun 25, 2012 |
| Apr 24, 2012 | 34941817K | RESOLVE | CLASS - 2 | FAILURE TO MIANTAIN ADEQUATE HOUSEKEEPING PER SECTION REQUIREMENTS:NOTED:@ INTERIOR & EXTERIOR OF 5 STORY NEW BLDG HA... | $800 | $0 | Jul 26, 2012 |
| Aug 19, 2010 | 34769565L | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE GUARD RAILS - AT TIME OF INSPECTION,DEMOLITION IN PROGRESS,AT 2ND FL LEVEL NO GUARD RAILS SYSTEM I... | $1,200 | $0 | Oct 18, 2010 |
| Aug 19, 2010 | 34769566N | RESOLVE | CLASS - 1 | FAILURE TO CONTRARY OUT DEMOLITION OPERATING AS REQUIRED DEMO IN PROGRESS LIGHT FIXTURES ATTACHED TO CEILING WITH FLO... | $1,200 | $0 | Oct 18, 2010 |
| Aug 19, 2010 | 34769567P | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE ADEQUATE HOUSEKEEPING. AT TIME OF INSPECTION DEMOLITION IN PROGRESS OBSERVED EXISTING PER STAIRS W... | $0 | $0 | Feb 23, 2011 |
| Aug 19, 2010 | 34769568R | RESOLVE | CLASS - 1 | FAILURE TO SAFEGUARD ALL PERSONS & PROPERTY AFFECTED BY DEMOLITION OPERATIONS. AT TIME OF INSPECTION OBSERVED PIPE SC... | $2,400 | $0 | Oct 18, 2010 |
| Aug 19, 2010 | 34769563H | RESOLVE | CLASS - 1 | SEC. 3301.7 DESIGN REQUIRED AT TIME OF INSPECTION,OBSERVED PIPE SCAFFOLD ERECTED ON SIDEWALK SHED NO DESIGN DRAWING P... | $1,600 | $0 | Feb 23, 2011 |
| Aug 19, 2010 | 34769564J | RESOLVE | CLASS - 1 | SEC. 3307.6.4 SIDEWALK SHED NOT IN CODE. AT TIME OF INSPECTION,OBSERVED SIDEWALK SHED(ERECTED) ON ATLANTIC AVE AT ABO... | $1,600 | $0 | Feb 23, 2011 |
| Aug 19, 2010 | 34769569Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN(TRIPPING)HAZARD AT 2 OF INSPECTION OBSERVED SIDEWALK ALL BROKEN & CAUSING A TRIPPING HAZARD IN PE... | $1,600 | $0 | Feb 23, 2011 |
| Aug 13, 2010 | 34860402Y | RESOLVE | CLASS - 1 | FAILURE TO SAFEGUARD ALL PERSONS & PROPERTY AFFECTED BY CONST OPERATION NOTE @ THE TIME OF INSPECTION OF COMPLAIN 335... | $2,400 | $0 | Oct 18, 2010 |
| Aug 3, 2010 | 34844643P | RESOLVE | CLASS - 2 | 3303.4.1)ALL AREA USED BY THE PUBLIC SHALL BE MAINTAINED FREE FROM ICE,SNOW,GREASE,DEBRIS,EQUIPMENT,MATERIAL PROFECTU... | $800 | $0 | Sep 27, 2010 |
| Jun 30, 2010 | 34844631H | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE APPROVED/ACCEPTED PLANS AT JOB SITE AT TIME OF INSPNOTE AT THE TIME OF INSP ON DEMOLITION SITE SID... | $0 | $0 | Aug 23, 2010 |
| Jun 30, 2010 | 34844630X | RESOLVE | CLASS - 2 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND APPROVED AMENDMENTS AT THE OF MY INSP ON DEMOLITION SITE... | $0 | $0 | Aug 23, 2010 |
| Oct 12, 2004 | 34426570L | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED. OBSERVED THAT THERE IS NO TYPE OF SPRINKLER SYSTE... | $400 | $0 | Apr 4, 2005 |
| Sep 10, 2004 | 34450481J | RESOLVE | Non-Hazardous | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY #175409 NOTED: C OF INDICATES FACTORY WITH OFFICE ... | $0 | $0 | Oct 25, 2004 |
| Oct 1, 2003 | 34413297R | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BLDG DEFECT IS PLASTER AND JOINT PEELING OFF CEILING AND WALLS IN OFFICE AT 1ST FL DUE TO WATER L... | $0 | $0 | Nov 17, 2003 |