ECB violations
1270 Pacific Street, Brooklyn • Block 01207 • Lot 0009
27 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Oct 3, 2024 | 39126531X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $2,500 | Jun 9, 2025 |
| Apr 22, 2024 | 39112221N | RESOLVE | CLASS - 2 | WEIL MCLAIN BOILER, MODEL# LGB5. FOUND HOLES IN CEILING AND FRESH AIR SCREENS CLOGGED. CORRECT VIOLATING CONDITIONS A... | $0 | $0 | Jun 26, 2024 |
| Apr 22, 2024 | 39112304Z | RESOLVE | CLASS - 1 | HEAVY OIL LEAK FROM THE VALVE BODY AS THE ELEVATOR RUN. MUST HAVE THE CAPACITY FOR THE RETEST(CU). CLEAN OIL OFF THE ... | $1,250 | $0 | Dec 2, 2024 |
| Mar 31, 2023 | 39082760H | RESOLVE | CLASS - 1 | CEASE USE ITEM. DOOR ZONE RESTRICTOR HAS BEEN TAMPERED WITH/ DISABLED AND RENDERED INOPERATIVE. THIS IS A SAFETY DEVI... | $1,250 | $0 | Aug 2, 2023 |
| Dec 12, 2022 | 39075485R | RESOLVE | CLASS - 1 | RESTORE SERVICE TO DEVICE. ONLY ELEVATOR IN A DHS LOCATION OUT OF SERVICE. | $1,280 | $0 | Feb 15, 2023 |
| May 17, 2022 | 39062313H | RESOLVE | CLASS - 2 | AT 4TH, 3RD, 2ND & FIRST FLOORS, CORRIDORS THERE ARE NO EMERGENCY LIGHTS. ALSO, THERE IS NO BACKUP POWER GENERATOR IN... | $1,250 | $0 | Jan 23, 2023 |
| Mar 4, 2020 | 38272738M | RESOLVE | CLASS - 1 | 42M7:(42,M,7)NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 N... | $1,250 | $0 | Jul 8, 2020 |
| Feb 11, 2020 | 39017298X | RESOLVE | CLASS - 2 | FIRE STOP NOT DONE IN THE MAIN METER ROOM AND GAS METER ROOM, FIRE BLOCK USED WHICH DOES NOT MEET THE FIRE RATING NEE... | $1,250 | $0 | Jun 17, 2020 |
| Sep 11, 2019 | 39009324K | RESOLVE | CLASS - 2 | I OBSERVED IN THE ELECTRICAL EQUIPMENT THE INSTALLATION OF EMT CONDUITS, PROPERLY SECURE/SUPPORT EMT | $500 | $0 | Jan 15, 2020 |
| Aug 2, 2019 | 39006960H | RESOLVE | CLASS - 2 | NO SIGNAGE AT EXPOSURE ONE OF BUILDING TO INDICATE THAT AN AUTOMATIC FIRE SPRINKLER SYSTEM IS INSTALLED THROUGH OUT T... | $310 | $0 | Sep 16, 2019 |
| Feb 21, 2019 | 38268357R | RESOLVE | CLASS - 1 | CU1B10;CU2L10;CU5B1;CU5A10; 61M7. 1B10-EMERGENCY STOP SWITCH WORK BUT NO BUZZER; 2L10-ALARM NOT WORKING NO BUZZER; 5B... | $1,250 | $0 | Jun 3, 2019 |
| Jul 16, 2018 | 32097356N | RESOLVE | CLASS - 2 | B254,32A,50. BURNHAM MODEL #P81ONEI-L2 HOT WATER BOILER; 50-REMOVE BANDIRON FROM FLUE PIPING AND REPLACE WITH PROPER ... | $312 | $0 | Nov 26, 2018 |
| Feb 20, 2018 | 35311870J | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS. OBSERVED THE FOLLOWING VIOLATINGCONDITION IN THE ELECTRICAL ROOM LOCATED IN THE... | $4,800 | $0 | Jun 6, 2018 |
| Feb 20, 2018 | 35311361L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3;27-345. NOTE: GAS METER ROOM MISSING... | $0 | $0 | Apr 16, 2018 |
| Dec 28, 2017 | 35312057L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 12-28-17 AT ABOVE ADDRESS EXCESSIVE STORAGE IN GAS MET... | $0 | $0 | Apr 23, 2018 |
| Dec 28, 2017 | 35298007P | RESOLVE | CLASS - 2 | WORK W/O A PERMIT. OBSERVED ON 12/28/17 AT ABOVE ADDRESS WATER LINES AND WASTE LINES REMOVED FROM LAUNDRY ROOM IN BAS... | $0 | $0 | Mar 13, 2018 |
| Dec 28, 2017 | 35298009Z | RESOLVE | CLASS - 2 | WORK W/O PERMIT. OBSERVED ON 12/28/17 AT ABOVE ADDRESS WATER AND WASTELINES REMOVED FROM THE LAUNDRY ROOM W/O AN PERM... | $0 | $0 | Mar 13, 2018 |
| Jul 19, 2017 | 35286729Z | RESOLVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,MATERIALS APPARATUS,DEVICES,APPLIANCE OR WIRING IN USE. OBSERVED LA... | $800 | $0 | Mar 12, 2018 |
| Jul 19, 2017 | 35286730X | RESOLVE | CLASS - 2 | FAILURE TO INSTALL GROUND FAULT CIRCUIT INTERRUPTER(GFCI)AS REQUIRED. OBSERVED SINGLE RECEPTACLE UTLETS IN LAUNDRY RO... | $2,400 | $0 | Mar 12, 2018 |
| Feb 7, 2017 | 35226474L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 2/07/17IN CELLAR GAS METER ROOM HAS NO FRESH AIR INLET... | $530 | $0 | Mar 27, 2017 |
| Oct 20, 2016 | 35216400J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALL(S)OR APPURTENANCES NOTED:1EXTERIOR WALL @EXP#3 (REAR)HAS APPROX 1 1/2" WIDE STEP CRACKS... | $500 | $0 | Jun 7, 2017 |
| Oct 20, 2016 | 35216401L | RESOLVE | CLASS - 2 | 27-766 MISSING FRESH AIR INLET.@CELLAR GAS METER ROOM, NO FRESH AIR INLET.REM:PROVIDE FRESH AIR INLET IN GAS METER ROOM. | $800 | $0 | Jun 7, 2017 |
| Apr 28, 2016 | 35177919R | RESOLVE | CLASS - 2 | SEC. 27-766 FAILURE TO PROVIDE FRESH AIR (INLET) (FAI)PER 27-766. NOTED: AT CELLAR GAS METER ROOM,THERE IS NO FRESH A... | $830 | $0 | Jun 13, 2016 |
| Apr 28, 2016 | 35177917N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC712.3;27-345. NOTED: AT CELLAR GAS METER ROOM,... | $530 | $0 | Jun 13, 2016 |
| Apr 28, 2016 | 35177918P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG CODE COMPLIANT: LACK OF EMERGENCY LIGHTING PER BC1006.1;27-542. NOTED: AT 2ND,3RD,& 4TH FLOO... | $530 | $0 | Jun 13, 2016 |
| Jan 12, 2016 | 35164196J | RESOLVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY JOB#300715705 IN THAT CELLAR OCCUPIED AS OFFICE TO OPERATE SHELTER & 1ST FL NOW... | $600 | $0 | Feb 29, 2016 |
| Jun 17, 2015 | 38236786Z | RESOLVE | CLASS - 2 | 40Y02,48Y13 SEAL EXCESSIVE OIL LEAK FROM TANK. | $0 | $0 | Aug 3, 2015 |