| Jun 24, 2025 | 39151866M | RESOLVE | CLASS - 2 | FEDERAL STEAM BOILER HAS CORRODED FLUE PIPE+CONDENSATE TANK GLASS GAUGE DEFECTIVE+BODY DRAIN PIPES MISSING@SAFETY VAL... | $3,125 | $3,125 | Dec 4, 2026 |
| Jun 24, 2025 | 39151865K | RESOLVE | CLASS - 2 | BEST HW HEATING BOILER IS OPERATING@MAWP+CHIMNEY BASE NOT ACCESSIBLE NO CLEANOUT+OIL GAUGE DEFECTIVE;CORRECT VIOLATIO... | $3,125 | $3,125 | Dec 4, 2026 |
| Feb 25, 2022 | 35636895L | ACTIVE | CLASS - 1 | BC3314.1 UNSAFE SUPPORTED SCF.ATOI ON INACTIVE DEMO SITE,I OBSERVED SUPPORTED SCF@EXP4 W/FOLLOWING VIOLATING CONDITIO... | $6,250 | $6,250 | Jan 11, 2023 |
| Jun 30, 2021 | 35575848M | ACTIVE | CLASS - 1 | SEC. BC3314.1 UNSAFE SUPPORTED PIPE SCAFFOLD. NOTE: AT THE TIME OF INSPECTION I OBSERVED SUPPORTED PIPE SCAFFOLD IN P... | $12,500 | $12,500 | Nov 10, 2021 |
| Jun 30, 2021 | 35575325N | ACTIVE | CLASS - 1 | SEC. BC3307.7.2 GATES. NOTE: AT THE TIME OF INSPECTION OF A 3 STY DEMOSITE I OBSERVED THE CONSTRUCTION GATE WAS SWING... | $12,500 | $12,500 | Nov 10, 2021 |
| Jun 30, 2021 | 35575846Z | ACTIVE | CLASS - 1 | PERMIT HOLDER FAILED TO MAINTAIN RECORD OF PRE-SHIFT SAFETY MEETING FOR EACH WORKER. NOTE: AT THE TIME OF INSPECTION,... | $25,000 | $25,000 | Nov 10, 2021 |
| Jun 30, 2021 | 35575847K | ACTIVE | CLASS - 1 | FAILURE TO ENSURE EACH WORKER IS IN COMPLIANCE W/BC3321.1. NOTE: AT THE TIME OF INSPECTION,I OBSERVED 2 WORKERS ON SI... | $25,000 | $25,000 | Nov 10, 2021 |
| Jun 30, 2021 | 35575849Y | RESOLVE | CLASS - 2 | CONSTRUCTION SUPERINTENDENT FAIL TO PERFORM DUTIES PER RULE. THE FOLLOWING HAZARDS CONDITION & STOP WORK ORDER WAS OB... | $5,000 | $5,000 | Nov 10, 2021 |
| Jun 30, 2021 | 35575845R | ACTIVE | CLASS - 1 | PERMIT HOLDER FAILED TO ENSURE WORKERS RECEIVE SITE SAFETY ORIENTATION. NOTE: AT THE TIME OF MY INSPECTION,I OBSERVED... | $25,000 | $25,000 | Nov 10, 2021 |
| Jun 17, 2021 | 35557014R | RESOLVE | CLASS - 2 | TEMP CONST EQUIPMENT ONSITE NOTED:ATOI OF NONACTIVE JOBSITE.UPON REVIEWING BIS/DOBNOW OBSERVED JOBSITE CONST PERMIT#B... | $0 | $0 | Oct 27, 2021 |
| May 20, 2021 | 39041550Z | RESOLVE | CLASS - 2 | NO MANUAL RESET LOW WATER CUT OFF. NO BLOW DOWN PIPE ON RELIEF VALVE NO LOW PRESSURE GAS SWITCH. NO SPILL SWITCH. | $0 | $0 | Sep 22, 2021 |
| Mar 8, 2021 | 35548540M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER ILLUMINATION FOR EXITS,EXIT DISCHARGES&PUBLIC CORRIDORS PER BC1006.... | $0 | $0 | May 16, 2022 |
| Mar 8, 2021 | 35548541Y | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELFCLOSING PROPERLY,@CELLAR LEVEL RMC2 1EXIT DOOR NOT SELFCLOSING PROPERLY,&@4FL EXIT DOORWAY TO 3FL E... | $0 | $0 | May 16, 2022 |
| Sep 25, 2020 | 35510053L | RESOLVE | CLASS - 1 | FAILURE TO PRODUCE CONSTRUCTION DOCUMENTS. NOTE: AT TIME OF MY INSPECTION OF A 3 STY BLDG. AT DEMOLITION STAGE. DEMOL... | $2,500 | $2,500 | Oct 15, 2021 |
| Sep 25, 2020 | 35510058K | RESOLVE | CLASS - 1 | SEC. 3303.4.7 STORAGE NEAR SIDEWALK,WALKWAYS & PATHWAYS. NOTE: AT TIE OF MY INSPECTION OF A 3 STY BLDG UNDERGOING INT... | $625 | $625 | Mar 21, 2022 |
| Sep 25, 2020 | 35510056R | RESOLVE | CLASS - 1 | HOUSEKEEPING. NOTE: AT TIME OF MY INSPECTION OF A 3 STY BLDG UNDERGOING INTERIOR & DEMOLITION. I OBSERVED LARGE QUANL... | $625 | $625 | Mar 21, 2022 |
| Sep 25, 2020 | 35510054N | RESOLVE | CLASS - 1 | FAILURE TO PRODUCE CONSTRUCTION DOCUMENTS. NOTE: AT TIME OF MY INSPECTION OF A 3 STY BLDG. AT DEMOLITION STAGE DEMOLI... | $1,250 | $1,250 | Oct 15, 2021 |
| Sep 24, 2020 | 35510055P | RESOLVE | CLASS - 1 | SUPERINTENDENT FAILED TO PERFORM DUTIES PER CODE: NOTE: AT TIME OF MY INSPECTION OF A 3 STY BLDG DEMOLITION OF THE IN... | $0 | $0 | Mar 21, 2022 |
| Jun 13, 2018 | 38263710X | RESOLVE | CLASS - 1 | CU1B10,CU5A10,VCU5B10; 29M7,3L10,39X2,57BB7,56M7,59BB5,67X10,70O2,71L10. 1B10-EMERGENCY STOP SWITCH DEFECTIVE UNABLE ... | $1,250 | $0 | Jan 10, 2020 |
| May 5, 2017 | 35260623P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NOTED: AT THE GAS METER ROOM. STORAGE OF DEFECTIVE ELECTRICAL FITT... | $250 | $0 | Aug 25, 2017 |
| May 5, 2017 | 35260624R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDOR PER BC 10... | $250 | $0 | Aug 25, 2017 |
| May 5, 2017 | 35260620J | RESOLVE | CLASS - 2 | REISSUE ECB#35136522H FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3;27-345. NOTED ... | $250 | $0 | Aug 14, 2017 |
| May 5, 2017 | 35260621L | RESOLVE | CLASS - 2 | SEC. 28-301.1 UNLAWFUL PLACEMENT OF FURNISHINGS,DECORATIONS OR OTHER OBJECTS AT EXITS THAT OBSTRUCT ACCESS TO EGRESS ... | $400 | $0 | Aug 25, 2017 |
| May 5, 2017 | 35260622N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NOTED AT THE BASEMENT BOILER ROOM WATER LEAKAGES ON THE FLOOR. REM... | $250 | $0 | Aug 25, 2017 |
| Oct 7, 2016 | 35136575L | RESOLVE | CLASS - 2 | SEC. 27-527;1028.1.2 PLACE OF ASSEMBLY POSTED CAPACITY SIGN. CAPACITY SIGNS POSTED AT PREMISES NOT(CONFORMING)W/CODE ... | $800 | $0 | Dec 5, 2016 |
| Oct 7, 2016 | 35136523J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER:NOTED:OBSERVED AT TIME OF INSPECTION THE SPRINKLER HEADS COVERS TO ... | $1,000 | $0 | Feb 6, 2017 |
| Oct 7, 2016 | 35136522H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER PC 712.3; 27-345 NOTED: OBSERVED AT THE BOILE... | $1,000 | $0 | Feb 6, 2017 |
| Oct 7, 2016 | 35136576N | RESOLVE | CLASS - 2 | UNAPPROVE USE OF MATERIALS. NOTED: OBSERVED AT TIME OF INSPECTION AT THE COMMERCIAL KITCHEN INSPECTION OF A () CABLE,... | $500 | $0 | Dec 5, 2016 |
| Oct 7, 2016 | 35136521X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.NOTED AT CELLAR LEVEL AT THE DORMITORY ROOM OBSERVED THE EXIT DOOR ... | $500 | $0 | Dec 5, 2016 |
| Sep 29, 2016 | 38245897X | RESOLVE | CLASS - 2 | 34S13,45L10,53H11,76M07/34513:HOISTWAY HAS A HOLE THAT NEEDS TO BE SEALED;44L10:GOVERNOR NOT WORKING PROPERLY;53H11:G... | $250 | $0 | Jul 19, 2017 |
| Aug 26, 2015 | 35046005K | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN NOV #35146797X ISSUED ON 7/10/15 & TO FILE A C OF C PURSUANT TO 28-... | $2,400 | $0 | Jan 11, 2016 |
| Jul 10, 2015 | 35146796Y | RESOLVE | CLASS - 2 | APPROVED PLACE OF ASSEMBLY PLANS NOT AVAILABLE FOR INSPECTION.NOTE @ TIME OF INSPECTION A LEARNING/STUDY HALL APPROX ... | $500 | $0 | Nov 30, 2015 |
| Jul 10, 2015 | 35146795M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8, 27-371... | $1,000 | $0 | Nov 25, 2015 |
| Jul 10, 2015 | 35146797X | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. NOTE: AT THE TIME OF INSPECTION LOCATED ON THE 4TH AND 3RD FLR WESTERN PART OF THE BLDG ROLL DOWN ... | $1,000 | $0 | Dec 3, 2015 |
| Sep 28, 2012 | 34995394L | RESOLVE | CLASS - 2 | WORK W/O A PERMIT. NOTED AT CELLAR LEVEL AT REAR OF BUILDING A ROOM HAS BEEN CREATED W/NEW PLUMBING FIXTURE (5 URINAL... | $800 | $0 | Dec 17, 2012 |