ECB violations
2338-2342 Atlantic Avenue, Brooklyn • Block 01436 • Lot 0011
37 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jun 15, 2026 | 39192489R | RESOLVE | CLASS - 1 | THE ONLY ELEVATOR IN SECTION OF BUILDING OR BUILDING IS OUT-OF-SERVICE. UPON INSPECTION THE DEVICE IS FOUND TO BE OUT... | $1,250 | $1,250 | Aug 26, 2026 |
| Jun 5, 2026 | 39191516Z | ACTIVE | CLASS - 2 | AT FRONT OF BUILDING, AT RIGHT SIDE,ABOVE 4TH FLOOR WINDOW, STEP CRACK APPEARS WITH MISSING MORTAR., MAINTAIN EXTERIO... | $2,500 | $2,500 | Aug 19, 2026 |
| Apr 22, 2026 | 39185615N | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN ELEVATOR IN CODE COMPLIANT MANNER, IN VIOLATION OF NYC BUILDING CODE 28-301.1. CLASS 1 ITEM: 1) F... | $3,125 | $3,125 | Aug 3, 2026 |
| Apr 2, 2026 | 39183084Y | ACTIVE | CLASS - 2 | FAILURE TO CONDUCT A FINAL INSPECTION OF PERMITTED WORK WITH D.O.B AT TIME OF INSPECTION OBSERVED PERMIT B00510174-I1... | $1,250 | $1,250 | Mar 1, 2027 |
| Apr 2, 2026 | 39183083M | ACTIVE | CLASS - 2 | AT TIME OF INSPECTION OBSERVED ACTIVE VALID PERMITS# B01249276-I1-PL EXPIRES ON 8/21/26 ALSO PERMIT#B01295217-I1-BE E... | $300 | $300 | Mar 1, 2027 |
| Apr 1, 2026 | 39182778Y | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. CLASS 1 ITEM: 1) FIRE SERVICE MALFUNCTIONING (SAFETY EDGE NOT ... | $1,250 | $1,250 | Aug 3, 2026 |
| Mar 12, 2026 | 39180243Z | ACTIVE | CLASS - 1 | 1) IN-CAR TRAVEL LANTERN FIXTURE DAMAGED. 2) IN-CAR COMMUNICATION INOPERATIVE. 3) CLEAN THE MR HAS DAMAGES IN NUMEROU... | $1,250 | $1,250 | May 20, 2026 |
| Feb 19, 2026 | 39177920J | RESOLVE | CLASS - 2 | AT TIME OF INSPECTION OBSERVED ACTIVE VALID PERMITS# B01249276-I1-PL EXPIRES ON 8/21/26 ALSO PERMIT # B01249276-S1-BE... | $300 | $300 | Dec 10, 2026 |
| Feb 11, 2026 | 39176960J | ACTIVE | CLASS - 1 | 1) THE ELEVATOR IS SHUT DOWN DUE TO A WATER CONDITION IN THE BUILDING (HAVE THE DEVICE SERVICED AND NOTIFY DOB ELEVAT... | $3,125 | $3,125 | May 20, 2026 |
| Feb 10, 2026 | 39176657R | ACTIVE | CLASS - 2 | AT TIME OF INSPECTION I OBSERVED WATER ON LOBBY FLOOR WHICH IS A RESULT OF LEAKING VALVES IN THE WATER METER ROOM THA... | $1,280 | $1,280 | Nov 23, 2026 |
| Jan 28, 2026 | 39175213L | ACTIVE | CLASS - 3 | NAVIEN BOILER IN BOILER ROOM IN APT 3A>OCCUPANT HAS TO RESET BOILER CONTROL EVERY TIME HEAT+HOT WATER IS NEEDED ÝQUAL... | $500 | $500 | Nov 6, 2026 |
| Jan 28, 2026 | 39175212J | ACTIVE | CLASS - 3 | NAVIEN BOILER IN BOILER ROOM IN APT 2B HAS WIRES EXPOSED@WIRE BOX+A HOLE IN THE BOILER ROOM WALL, MAINTAIN BOILER; CO... | $500 | $500 | Nov 6, 2026 |
| Sep 24, 2025 | 39161479L | ACTIVE | CLASS - 1 | THE ONLY ELEVATOR IN SECTION OF BUILDING OR BUILDING IS OUT-OF-SERVICE. UPON INSPECTION THE DEVICE IS FOUND TO BE OUT... | $6,250 | $6,250 | Nov 17, 2026 |
| Mar 25, 2025 | 39142689X | ACTIVE | CLASS - 2 | DOME STARTING TO COLLAPSE. WORN CAB MIRROR. INOPERATIVE PHONE. REPLACE WORN GIBS WHERE NEEDED. SECURE GIBS WHERE NEED... | $3,125 | $3,125 | Dec 28, 2026 |
| Mar 14, 2025 | 39141524N | ACTIVE | CLASS - 2 | NAVIEN HW HEATING BOILER IN APT 4E>GAS LOCKED BY UTILITY BOILER HAS IMPROPER VENT CAUSING HIGH CO LEVELS, MAINTAIN BO... | $1,250 | $1,250 | Jul 6, 2026 |
| Mar 14, 2025 | 39141523L | ACTIVE | CLASS - 2 | REPORTED BY UTILITY BOILER IN APT 3A>IMPROPER VENT CAUSING HIGH CO LEVELS>GAS LOCKED BY UTILITY, MAINTAIN BOILER; COR... | $1,250 | $1,250 | Jul 6, 2026 |
| Mar 18, 2024 | 39108992J | ACTIVE | CLASS - 2 | PROVIDE CAT1 AND CAT5 AND CURRENT BRAKE MAINT. TAGS. REPAIR PHONE AND ADJUST LOBBY FLOOR LEVEL. REMOVE ALL NON ELEVAT... | $3,125 | $3,125 | Aug 25, 2025 |
| Dec 14, 2023 | 39101367M | ACTIVE | CLASS - 2 | VIOLATION 39089749Z 7-6-23 FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER TO FILE A CERTIFICATE OF CORRECTION WITH TH... | $1,250 | $1,250 | Dec 3, 2024 |
| Jul 19, 2023 | 39090588P | RESOLVE | CLASS - 2 | 2:X:10; PHONE IN CAR NOT WORKING, NEED TO REPAIR. 8:V:1; CAR SILL TO HALL SADDLE NOT LEVEL IN THE LOBBY, NEED TO ADJU... | $0 | -$625 | Sep 27, 2023 |
| Jul 6, 2023 | 39089749Z | ACTIVE | CLASS - 2 | FOUND NAVIEN-NCB 180 BOILER S/N 6608A1790711301 INSTALLED INSIDE APT 2-B. BOILER IS INOPERATIVE IN TEMP STATUS WITH D... | $625 | $0 | Sep 13, 2023 |
| Nov 16, 2021 | 39051233Y | ACTIVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $12,500 | $12,500 | May 25, 2022 |
| Mar 20, 2020 | 39020121H | ACTIVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $1,250 | $0 | Aug 19, 2020 |
| Dec 23, 2019 | 39014696H | ACTIVE | CLASS - 2 | NAVIEN BLR IN APT 5E-IS NOT REGISTERED-BLR FLUE MATERIAL IS PVC-FLUE VENTING WITHIN 4' OF A WINDOW-VENTING ONTO ADJAC... | $625 | $625 | Feb 28, 2022 |
| Jan 24, 2018 | 32091669R | ACTIVE | CLASS - 2 | B254,36. FOUND NAVIEN BOILER ON APT 2E MOEL #CH-180 150,000 BTU'S NOT REGISTER. REGISTER BOILER AND CORRECT ALL VIOLA... | $500 | $0 | Jul 16, 2018 |
| Sep 20, 2017 | 38258013Y | RESOLVE | CLASS - 1 | 5A10,67X10,57BB7,59B7,99BB15,68B7,68M7,100M7,40O2,17M7,33M7,32J1,52B1,100M7,61B10,61H11,52##1.BIG APPLE ELEV SVC & CO... | $0 | $0 | Apr 9, 2018 |
| Sep 20, 2017 | 38258007H | RESOLVE | CLASS - 1 | 5A10CU; 67X10,57BB7,59B7,99BB15,68B7,68M7,100M7,40O2,17M7,33M7,32J1,52B1,100M7,61B10,61H11,52##1. 5A10-CEASE USE ITEM... | $1,000 | $0 | Nov 6, 2017 |
| Sep 20, 2017 | 38258012M | RESOLVE | CLASS - 1 | 5A10,67X10,57BB7,59B7,99BB15,68M7,100M7,40O2,17M7,33M7,32J1,52B1,100M7,61B10,61H11,52##1.METRO ELEVATOR INSPECTION LI... | $0 | $0 | Apr 9, 2018 |
| May 18, 2015 | 38236237X | RESOLVE | CLASS - 2 | 14H11,100M07,67X10,17H11,17D06,10J01,05X10,70O02,40#07,39X10. 14H-REPLACE; 100M-PROVIDE IN CASE OF FIRE SIGNAGE AT 1S... | $0 | $0 | Jul 6, 2015 |
| Sep 14, 2012 | 32070383Z | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER. TO OBTAIN WORK PERMIT. FOR BOILER INSTALLATION IN EACH APT (25 APTS) | $1,600 | $0 | Nov 28, 2012 |
| Dec 7, 2011 | 38219449N | RESOLVE | CLASS - 2 | 67L10,05X10,39M07,40P10.(67L)REPAIR.(05X)ZONE-LOCK RESTRICTOR.(39M)LIGHT.(40P)NO AVAILABLE ACCESS-PROVIDE EXPLICITLY ... | $0 | $0 | Jan 23, 2012 |
| Jul 25, 2011 | 32070899J | ACTIVE | CLASS - 1 | B154 36 50A. 50A-BOILERS INSTALLED INTO TWO COMMON CHIMNEYS, BREAKING THE DRAFT ON EVERY BOILER EXCEPT THE TO HIGHEST... | $1,000 | $0 | Sep 12, 2011 |
| Jul 25, 2011 | 32070898H | RESOLVE | CLASS - 1 | B101. INSTALLATION OF 9 BOILERS IN APTS W/O PLANS OR PERMITS ON FILE W/THE NYC DEPT OF BUILDINGS ALSO NO SIGNOFF FROM... | $1,600 | $0 | Sep 12, 2011 |
| Mar 4, 2005 | 34469228X | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT.EXPIRED PERMIT:NOTED:PERMIT #301506948 EXPIRED ON 04/29/04.NO RENEWAL ON D.O.B. FILE.WORK BEING... | $500 | $0 | Jun 27, 2005 |
| Feb 18, 2005 | 34469347Z | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE HANDRAILS ON STAIRWELL:NOTED:STAIRWELL AT FRONT YARD OF PREMISES IS APPROX.5FT. DEEP FROM TOP OF S... | $500 | $0 | Jun 6, 2005 |
| Feb 18, 2005 | 34469346R | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE HANDRAILS ON STAIRWELL. NOTED: STAIRWELL APPROXIMATE 5 FEET DEEP FROM TOP OF SIDEWALK AND APPROXIM... | $500 | $0 | Apr 4, 2005 |
| Jul 10, 1998 | 34182492R | RESOLVE | Non-Hazardous | WORK W/O A PERMIT. WORK NOTED: RENOVATING ENTIRE STRUCTURE, ENTIRE ROOF REMOVED NEW MASONRY WALL CONSTRUCTED AT S SEC... | $2,500 | $0 | Aug 24, 1998 |
| Jul 2, 1998 | 34182480J | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT. WORK NOTED. RENOVATING ENTIRE STRUCTURE. ENTIRE ROOF REMOVED. NEW MASONRY WALL CONSTRUCTED WES... | $2,500 | $0 | Nov 30, 1998 |