ECB violations
2402-2414 Atlantic Avenue, Brooklyn • Block 01437 • Lot 0008
26 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 21, 2026 | 39189535L | ACTIVE | CLASS - 1 | OBSERVED THROUGHOUT BUILDING SPRINKLER HEADS PAINT TO CEILING,TRAP WRAPS MISSING ON SINK DRAINS, LAUNDRY ROOM DOES NO... | $2,500 | $2,500 | Aug 5, 2026 |
| May 21, 2026 | 39189484K | ACTIVE | CLASS - 2 | CLASS 2: 1) EMERGENCY PHONE INOPERATIVE AS PER ASME A17.1/CSA B44 2.27.1.1.3. REMEDY: REPAIR AND VERIFY TWO-WAY COMMU... | $310 | $310 | Aug 5, 2026 |
| May 21, 2026 | 39189474R | RESOLVE | CLASS - 2 | FOUND #1 BOILER TELEDYNELAARS MOD# POW500 WITH NO MANUAL RESET LOW WATER CUT OFF. CHIMNEY NOT TO CODE. | $1,250 | $1,250 | Aug 5, 2026 |
| May 22, 2025 | 39148694H | RESOLVE | CLASS - 2 | LARRS HYDRONIC BOILER MODEL# PWO500. LOW WATER CUTOFF IS LEAKING. CORRECT VIOLATING CONDITION AND SUBMIT A CERTIFICAT... | $0 | $0 | Aug 6, 2025 |
| May 22, 2025 | 39148857N | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. OBSERVED GAS POWERED EQUIPMENT OBSTRUCTING EMERGENCY EGRESS AT REAR ... | $1,250 | $0 | Aug 6, 2025 |
| May 22, 2025 | 39148858P | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $1,280 | $0 | Feb 8, 2027 |
| May 22, 2025 | 39148859R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: SERVICE EQUIPMENT - BOILER. DISCOVER GAS LEAK ON BOILER. NATIO... | $2,500 | $0 | Aug 6, 2025 |
| May 22, 2025 | 39148860Y | RESOLVE | CLASS - 1 | UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. OBSERVED EXCESSIVE STORAGE IN ELECTRICAL ROOMS THROUGHOUT THE B... | $0 | $0 | Aug 6, 2025 |
| Aug 11, 2023 | 39092394X | RESOLVE | CLASS - 2 | NON-COMPLIANT & INADEQUATE TPP. DUST WAS FOUND ON FLOORS, NO PLASTIC BARRIARS WERE NO IN PLACE AT WORK AREAS, AND DUS... | $0 | $0 | Oct 18, 2023 |
| Mar 30, 2023 | 39082707Z | RESOLVE | CLASS - 2 | I OBSERVED ON THE 4TH, 3RD AND 2ND FLOORS EXCESSIVE STORAGE IN THE ELECTRICAL CLOSET. I NOTED SHELVING, CLOTHING AND ... | $500 | $0 | Nov 27, 2023 |
| Mar 30, 2023 | 39082706R | RESOLVE | CLASS - 2 | I OBSERVED ON THE 4TH, 3RD AND 2ND FLOORS THE FAILURE TO MAINTAIN ILLUMINATION ALONG THE PATH OF EGRESS AND AT THE PO... | $1,250 | $0 | Nov 27, 2023 |
| Mar 30, 2023 | 39082705P | RESOLVE | CLASS - 2 | I OBSERVED IN THE REAR YARD AT EXPOSURE #3THE INSTALLATION OF SUBFEEDER WIRING, DISCONNSECT SWITCHES AND BRANCH CIRCU... | $0 | $0 | Jun 7, 2023 |
| Mar 29, 2023 | 39082583X | ACTIVE | CLASS - 2 | SAFETY EDGE ON CAR DOOR NOT SECURED AND MALFUNCTIONING, REPAIR AND SECURE. | $625 | $0 | Nov 27, 2023 |
| Jan 11, 2022 | 39054102H | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER SUMMONS 35634502M AND 39016174J STILL EXISTS, COMPLY WITH COMMISSIONE... | $2,500 | $0 | Sep 19, 2022 |
| Nov 28, 2021 | 35634502M | RESOLVE | CLASS - 1 | UNLAWFUL ACTS.FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS.RECORDS INDICATE NO APP WAS MADE TO CERTIFY OR CORRECT ECB... | $2,500 | $0 | Apr 6, 2022 |
| Jun 12, 2021 | 35548029P | RESOLVE | CLASS - 1 | UNLAWFUL ACTS OF FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS.RECORDS INDICATE NO APPLICATION WAS MADE TO CORRECT OR ... | $6,250 | $0 | Oct 20, 2021 |
| Jul 16, 2020 | 39025508P | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $1,250 | -$1,250 | Nov 18, 2020 |
| Mar 23, 2020 | 39020192P | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER SUMMONS 39016174J STILL REMAINS, COMPLY WITH COMMISSIONER'S ORDER; COM... | $6,250 | -$6,250 | Jul 29, 2020 |
| Mar 11, 2020 | 39019491R | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $3,125 | $0 | Sep 25, 2020 |
| Jan 23, 2020 | 39016174J | ACTIVE | CLASS - 1 | I OBSERVED IN THE KITCHEN AREA ON THE SIDE OF TWO DUTCH WARMING OVENS AN ELECTRICAL JUNCTION BOX WITH A DISCONNECTED ... | $1,600 | $0 | Sep 19, 2022 |
| Jan 23, 2020 | 39016173H | RESOLVE | CLASS - 2 | I OBSERVED ON THE ROOFTOP THE INSTALLATION OF LIQUID FLEXIBLE METALLIC CONDUIT (LFMC) WITHOUT THE REQUIRED EQUIPMENT ... | $5,000 | $0 | Jan 11, 2021 |
| Mar 25, 2019 | 38268961N | RESOLVE | CLASS - 2 | 39O02,56Y13,56O02,70O02,99M07,97U05. 39O02-CLEAN CAR TOP (OIL) 56Y13 SEAL MACHINE; 56O02-CLEAN MACHINE. 70O02-CLEAN P... | $310 | $0 | Jul 8, 2019 |
| Jan 15, 2019 | 38267337P | RESOLVE | CLASS - 2 | 11D6,32H10,56Y2,56Y10,59BB7,67X10,78B10,80B14. 11D6-CAR STATION NOT SECURED; 32H10- EXCESSIVE PLAY IN BOTTOM GUIDE SH... | $0 | $0 | Apr 22, 2019 |
| Oct 23, 2017 | 38258833J | RESOLVE | CLASS - 2 | 2X10;61U7;61T7;44Y13;60X7:ALARM BELL FOR STOP SWITCH IS INOPERATIVE;MAIN LINED DISCONNECT HAS NO DEVICE TAG-PROVIDE;M... | $0 | $0 | Dec 11, 2017 |
| Jun 12, 2015 | 38236472X | RESOLVE | CLASS - 2 | 16K-1.42G-1.42M09,56Y13,59Y02,61R11,39Y02,37Y02,05X10,17H11,17D02,70Z02. 16J-ADJUST BRAILLE TAGS TO ADA CODE HEIGHT; ... | $500 | $0 | Oct 26, 2015 |
| Jan 23, 2015 | 35150318L | RESOLVE | CLASS - 2 | 3314.4.1.5 NOTIFICATION OF SUSPENDED SCAFFOLD.NOTED AT TIME OF INSPEC TION NO SUSPENDED SCAFFOLDS ON SITE.FAILURE TO ... | $800 | $0 | Aug 26, 2015 |