ECB violations
1387-1389 Eastern Parkway, Brooklyn • Block 01475 • Lot 0004
37 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 30, 2026 | 39186702X | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIOONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPT. OF BUILDINGS FOR ... | $1,280 | $1,280 | Jul 8, 2026 |
| Nov 7, 2025 | 39166304M | ACTIVE | CLASS - 1 | CLASS 1 CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. RE... | $1,280 | $1,280 | Dec 10, 2026 |
| Jan 9, 2025 | 39135001N | RESOLVE | CLASS - 2 | I OBSERVED IN THE 5TH FLOOR BOILER ROOM AT THE POINT OF EGRESS LEADING TO THE FIFTH FLOOR ROOF NO REMOTE SHUT-DOWN FO... | $1,280 | $1,280 | Oct 29, 2026 |
| Jan 9, 2025 | 39134996X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,530 | $2,530 | Oct 29, 2026 |
| Jan 9, 2025 | 39134997H | RESOLVE | CLASS - 2 | CODE) EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING EXIT DOORS THROUGHOUT BUILDING. GAS METER ROOM AND ELECTR... | $625 | $625 | Apr 20, 2026 |
| Nov 28, 2023 | 39100235X | ACTIVE | CLASS - 2 | OBSERVED IN THE BOILER ROOM LOCATED ON 5TH FLOOR EXCESSIVE LEAK ON PUMP. AS PC 102.3 MAINTENANCE. INSTALLATIONS, BOTH... | $625 | $0 | Jul 29, 2024 |
| Nov 28, 2023 | 39100384J | RESOLVE | CLASS - 2 | I OBSERVED IN DOB RECORDS NO COMPLIANCE FOR ECB# 39086661K ISSUED ON 05/18/2023. AS PER COMMISSIONER'S ORDERS A CERTI... | $0 | $0 | Aug 5, 2024 |
| Nov 28, 2023 | 39100383H | RESOLVE | CLASS - 2 | I OBSERVED IN THE BASEMENT THE EGRESS FROM THE MAIN ELECTRICAL ROOM PASSING THROUGH THE GAS METER ROOM, THIS DOES NOT... | $0 | -$2,030 | Dec 20, 2024 |
| Nov 28, 2023 | 39100233M | RESOLVE | CLASS - 2 | BLIND SPOT MIRROR MISSING INSIDE THE CAR, PROVIDE. ALARM ON THE CAR STATION INOPERATIVE, REPAIR. CAT 1 TAG THAT IS CU... | $0 | $0 | Feb 7, 2024 |
| Jun 27, 2023 | 39089215Y | ACTIVE | CLASS - 2 | POOR FLAME FROM BURNERS/IGNITION CONTROL UNIT DEFECTIVE/FRONT BOILER JACKET NOT IN PLACE;CORRECT VIOLATION AND SUBMIT... | $625 | $0 | Feb 2, 2024 |
| Jun 27, 2023 | 39089214M | ACTIVE | CLASS - 3 | FRONT BOILER JACKET NOT IN PLACE/DOMESTIC WATER RELIEF VALVES NOT PIPED DOWN;CORRECT VIOLATION AND SUBMIT THE CERTIFI... | $500 | $0 | Feb 2, 2024 |
| May 18, 2023 | 39086660Z | RESOLVE | CLASS - 3 | I OBSERVED ON ALL FLOORS THE ELECTRICAL PANELS WITH NO/OR INCOMPLETE DIRECTORIES. PHOTOS TAKEN, PROVIDE CIRCUIT DIREC... | $200 | $0 | Jan 23, 2024 |
| May 18, 2023 | 39086622H | RESOLVE | CLASS - 2 | IN CAR COMMUNICATION MALFUNCTIONING (DOES NOT ALWAYS CONNECT), REPAIR. IN CAR ALARM INOPERATIVE, REPAIR. PIT DIRTY, C... | $0 | $0 | Jul 26, 2023 |
| May 18, 2023 | 39086659L | RESOLVE | CLASS - 1 | I OBSERVED ON THE ROOF NO EQUIPMENT GROUND CONDUCTOR INSTALLED AS PER EC 250.110(2). PHOTOS TAKEN.; EC 250.110(2), CO... | $1,600 | $0 | Jan 23, 2024 |
| May 18, 2023 | 39086661K | RESOLVE | CLASS - 2 | I OBSERVED IN THE BASEMENT AREA THE EGRESS FROM THE ELECTRICAL EQUIPMENT ROOM PASSING THROUGH THE GAS METER ROOM. THI... | $0 | -$800 | Jan 23, 2024 |
| May 18, 2023 | 39086779X | RESOLVE | CLASS - 1 | EMERGENCY EXIT FIRE ESCAPE DEFECTIVE AND CLOSED OFF DUE TO BROKE TRED LOCATED AT THE BOTTOM OF 2ND LEVEL FLOOR, (STAI... | $1,250 | $0 | Feb 5, 2024 |
| Mar 3, 2020 | 39018816L | RESOLVE | CLASS - 1 | DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH (CU). INSPECTION FRAME IN CAR MISSING PROVIDE. DLM TAG MISSING ON THE ... | $0 | $0 | Mar 3, 2022 |
| Dec 2, 2019 | 39013726P | RESOLVE | CLASS - 1 | DOOR ZONE RESTRICTOR IS NOT WORKING. REPAIR DOOR ZONE RESTRICTOR. MACHINE IS VIBRATING. REPAIR MACHINE. | $1,250 | $0 | Aug 20, 2020 |
| Jul 15, 2019 | 35442254X | RESOLVE | CLASS - 2 | UNSAFE, UNSUITABLE ELECTRICAL WIRING/EQIPMENT IN USE. I OBSERVED @THE MAIN ENTRANCE ARMORED CABLE INSTALLED FOR THE E... | $400 | $0 | Feb 28, 2020 |
| Jul 18, 2017 | 35272099X | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE PROPER SUPPORT FOR TEMPORARY WIRING.OBSERVED A THE TOP OF STAIRWELL A:THE USE OF 12 AWG WIRES TO P... | $1,600 | $0 | Oct 30, 2017 |
| Jul 18, 2017 | 35272098Y | RESOLVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT.OBSERVED AT THE TOP OF STAIRWELL A:THE INSTALLATION OF AN ELECTRICAL PANEL,POWER CAB... | $800 | $0 | Oct 30, 2017 |
| Jul 18, 2017 | 35272038M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 7/18/17AT ABOVE ADDRESS NO CURRENT BOILER INSPECTION O... | $0 | $0 | Dec 4, 2017 |
| Feb 2, 2017 | 35226482L | RESOLVE | CLASS - 1 | SEC. 408.2 MISC VIOLATION: FUTURE CONNECTION EXIST ON GAS PIPING. AT THE TIME OF MY INSPECTION I OBSERVED IN THE LAUD... | $0 | $0 | Apr 26, 2017 |
| Nov 19, 2016 | 35189433P | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN NOV #35207582P ISSUED ON 09/05/16 & TO FILE A C OF C PURSUANT TO 28... | $800 | $0 | Jan 9, 2017 |
| Oct 28, 2016 | 38250586P | RESOLVE | CLASS - 1 | 05X10,01L10,02X10,03I11,61J01,56Y3,52Y03,68B07,42M07,46J01,17H11,17D06,18M11,17J01. *CLASS ONE ITEM; 05X-ZONE LOCK RE... | $1,000 | $0 | Dec 12, 2016 |
| Sep 6, 2016 | 35207582P | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. OBSTRUCTION NOTED: BYLOBBY AREA CREATING SEATING WAITING AREA BLOCKI... | $1,200 | $0 | Dec 7, 2016 |
| Mar 2, 2016 | 35171299H | RESOLVE | CLASS - 2 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND/OR AMEND MENTS. NOTED: NEW SPRINKLER SYSTEM INSTALLED UN... | $500 | $0 | May 2, 2016 |
| Mar 2, 2016 | 35171575P | RESOLVE | CLASS - 2 | 27-937 FAILURE TO PROVIDE/POST WARNING SIGN ON ELECTRIC METER ROOM PER 27-937(B). NOTED: AT CELLAR ELECTRIC ROOM MARK... | $400 | $0 | May 2, 2016 |
| Nov 16, 2015 | 38239681X | RESOLVE | CLASS - 1 | 56Y10,56Y13,41I10,56L10,58L10,61B07,67X10,37X02. 56Y-REPAIR AND SEAL LEAKING; 56L-REPAIR NOISE COMING FROM MACHINE; 6... | $1,000 | $0 | Jan 4, 2016 |
| Jun 19, 2015 | 38236627L | RESOLVE | CLASS - 2 | 67X10,56L10,56M07,42N11,99M07,70O02,71X10,24X10,100B07. 67X10-REPAIR EMERGENCY PHONE; 56L10-ELIMINATE MACHINE EXCESSI... | $250 | $0 | Aug 3, 2015 |
| Jun 20, 2006 | 34521064Y | RESOLVE | Hazardous | FAILURE TO NOTIFY THE DOB PRIOR TO COMMENCEMENT OF DEMO WORK NOTED:AS PER DOB RECORDS NO NOTIFICATION (CALL-IN) WAS G... | $0 | $0 | Dec 17, 2007 |
| Oct 31, 2003 | 34398476J | RESOLVE | Hazardous | FAILURE TO MAINTAIN. DEFECT NOTED: (1) BROKEN WINDOWS THROUGHOUT GLASS IN DANGER OF FALLING ONTO PEDESTRIANS. (2) STO... | $800 | $0 | Mar 1, 2004 |
| Jan 6, 2003 | 34371730X | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL 2 & 3 FLOOR BUILDING FACADE IS MISSING 3'X6' SLABS OF CONCRETE THAT WERE N... | $2,500 | $0 | Mar 10, 2003 |
| Jan 6, 2003 | 34371729Z | RESOLVE | Hazardous | FAILURE TO MAINTAIN BUILDING FOUR STORE STEEL & CONCRETE BUILDING HAS STOPPED CONSTRUCTION AND ABANON DED SITE THE SI... | $2,500 | $0 | Mar 10, 2003 |
| Jun 24, 1998 | 34182714N | RESOLVE | Non-Hazardous | ABANDONED AND DISCONTINUED OPERATION. FAILURE TO PROVIDE REQUIRED 8 FOOT HIGH SOLID CONSTRUCTION FENCE PROTECT PUBLIC... | $2,500 | $0 | Aug 10, 1998 |
| Oct 6, 1989 | 32003829Y | RESOLVE | Non-Hazardous | TUBES: DIRTY. TUBES: LEAKING TUBES: PITTED | $250 | $0 | Dec 18, 1989 |
| Nov 28, 1988 | 32000163N | RESOLVE | Non-Hazardous | — | $0 | $0 | Feb 6, 1989 |