ECB violations
1027 Putnam Avenue, Brooklyn • Block 01484 • Lot 0033
31 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Sep 28, 2021 | 39048275P | RESOLVE | CLASS - 2 | BOILER ROOM LIGHTS DEFECTIVE/CHIMNEY BASE 1/2 FULL/OIL TANK SIGN MISSING/GAS METER AREA HAS NO VENTILATION;CORRECT VI... | $625 | $0 | Mar 21, 2022 |
| Sep 17, 2019 | 35429167L | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #39007251J ISSUED ON 08-07-2019 AND TO ... | $625 | $0 | Jun 26, 2020 |
| Aug 7, 2019 | 39007248Z | RESOLVE | CLASS - 2 | I OBSERVED IN THE REAR BASEMENT AREA THE INSTALLATION OF CONVENIENCE RECEPTACLES WITHIN 6 FT OF A SINK W/O GFCI PROTE... | $2,400 | $0 | Dec 6, 2019 |
| Aug 7, 2019 | 39007246P | RESOLVE | CLASS - 1 | I OBSERVED IN THE BASEMENT ABOVE THE ELECTRICAL METERS THE INSTALLATION OF A CIRCUIT BREAKER ENCLOSURE IMPROPERLY WIR... | $12,000 | $0 | Dec 4, 2019 |
| Aug 7, 2019 | 39007243J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EGRESS FROM REAR YARD AFTER YOU COME OFF THE FIRE ESCAPE,LESS THEN 20 FEET ON ONE OF THE YARD AND... | $655 | $0 | Sep 23, 2019 |
| Aug 7, 2019 | 39007250H | RESOLVE | CLASS - 2 | I OBSERVED IN THE REAR YARD THE USE OF EMT CONDUIT FOR THE INSTALLATION ON A WALL MOUNTED LIGHT. EMT IS NOT PERMITTED... | $830 | $0 | Sep 23, 2019 |
| Aug 7, 2019 | 39007249K | RESOLVE | CLASS - 2 | FAILURE TO CORRECT ECB # 35311865P ISSUED ON 02/05/2018, FILE A CERTIFICATE OF CORRECTION; PROPER FUSE CONDUCTORS | $0 | $0 | Dec 6, 2019 |
| Aug 7, 2019 | 39007251J | RESOLVE | CLASS - 1 | I OBSERVED IN THE BASEMENT ELECTRICAL EQUIPMENT AREA THE FUSEHOLDERS WITH 30 AMP FUSES AND A CIRCUIT BREAKER ENCLOSUR... | $12,500 | $0 | Dec 18, 2019 |
| Jul 26, 2018 | 35342239J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER RE:INSTALLATION/MAINTENANCE OF PLUMBING MATERIALS/EQUIPMENT PER PC ... | $0 | $0 | Jan 23, 2019 |
| May 8, 2018 | 35337997M | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35324739RISSUED ON 03/22/2018 AND TO F... | $1,250 | $0 | Aug 27, 2018 |
| Apr 17, 2018 | 32096506P | RESOLVE | CLASS - 2 | B254,2A&B, 39,50A,50B. AS PER CLASS 2 (B254) 28-301.1 VIOLATING CONDITIONS AND 21A AND B, #39. 50A-NO SHUT OFF ON OIL... | $310 | $0 | Jun 18, 2018 |
| Mar 22, 2018 | 35324739R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG WALL(S)OR APPURTENANCES.NOTED;AT EXP#3 PARAPET WALL AT WEST IS LOOSE,CRACKED AND MISSING BRI... | $6,250 | $0 | Jul 2, 2018 |
| Mar 22, 2018 | 35324740Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/COMM'S ORDER CONTAINED IN SUMM/VIO#35311515P ISSD ON 02/05/18 AND TO FILE COFC PURSUANT TO 28-201... | $625 | $0 | Jul 2, 2018 |
| Feb 5, 2018 | 35311516R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: @ 4TH STORY CORRIDOR, WATER PENETRATING CEILING CAUSING PLA... | $250 | $0 | Apr 30, 2018 |
| Feb 5, 2018 | 35311513L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES. NOTED: @ EXP#3 PARAPET WALL @ WEST HAS LOOSE, CRACKED & MISSING BR... | $1,000 | $0 | Apr 30, 2018 |
| Feb 5, 2018 | 35311514N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: NOTED: @ BOILER ROOM, HOLES & OPENINGS IN VARIOUS LOCATION @ CEILI... | $250 | $0 | May 3, 2018 |
| Feb 5, 2018 | 35311515P | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTED: @ EXP#3 THERE IS LESS 30FT FROM BLDG TO BACK OF LOT & EGRESS ... | $1,000 | $0 | May 3, 2018 |
| Feb 5, 2018 | 35311865P | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE ADEQUATE CIRCUIT OVERCURRENT PROTECTION DEVICE PER TABLE. THE FOLLOWING VIOLATING CONDITION WAS OB... | $4,800 | $0 | May 10, 2018 |
| Aug 4, 2017 | 35287513Y | RESOLVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT.OBSERVED NEW PARTITION WALLS WITH SWITCHES,RECEPTACLES,BRANCH CKT WIRING AND CKT BRE... | $800 | $0 | Nov 15, 2017 |
| Aug 4, 2017 | 35287507H | RESOLVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,MATERIAL APPARATUS,DEVICE,APPLIANCE OR WIRING IN USE.OBSERVED(A)100... | $2,000 | $0 | Dec 20, 2017 |
| Aug 4, 2017 | 35287508J | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS.OBSERVED NO WATER SERVICE GROUND CLAMP OR GROUND CONDUCTOR INSTALLED ON MAIN WAT... | $4,800 | $0 | May 14, 2018 |
| Aug 4, 2017 | 35287269L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.RE:INSTALLATION /MAINTENANCE OF PLUMBING MATERIALS/EQUIPMENT PE... | $500 | $0 | Apr 25, 2018 |
| Aug 4, 2017 | 35287303X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NOTED: OBSERVED @ ROOF BULKHEAD (INTERIOR), CRACKS @ THE CORNER OF... | $250 | $0 | Dec 4, 2017 |
| Feb 23, 2017 | 35228924Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:FAILURE TO COMPLY WITH LAW OF DRAINAGE SYSTEM OBSERVED.(PER PC7... | $500 | $0 | May 1, 2017 |
| Feb 23, 2017 | 35225722R | RESOLVE | CLASS - 2 | WORK WITHOUT A PERMIT. NOTED: CELLAR LEVEL INSTALLED 3PCS FULL BATHROOM WITH WATER & WASTE LINES ENCLOSED IN FULL HEI... | $800 | $0 | Jun 7, 2017 |
| Oct 6, 2016 | 35194668X | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. AT CELLAR LEVELROOMS LABELED STORAGE ILLEGAL PARTITIONS ERECTE... | $200 | $0 | Nov 21, 2016 |
| Oct 6, 2016 | 35214285Y | RESOLVE | CLASS - 1 | 408.2 DRIPS-FUTURE CONNECTS EXIST DOWN STREAM F APPLIANCE.OBSERVED ON 10/6/16 @THE TIME OF 9AM FUTURE GAS CONNECTIONS... | $0 | $0 | Jun 14, 2017 |
| Oct 6, 2016 | 35214286X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED PER BC903.2... | $0 | $0 | May 24, 2017 |
| May 19, 2016 | 35194888H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:NO FIRE STOPPING PER BC7123;27-345.NOTED:AT CELLAR,BOILER ROOM,... | $500 | $0 | Jul 15, 2016 |
| Jun 16, 2015 | 32075394R | RESOLVE | CLASS - 2 | B254,15,32A,50A,50B,50C,50D,50E. 50A-CLEAN OUT DOOR IMPROPER CLOSING; 50B-CONTROL COVER MISSING; 50C-BOILER SECTION N... | $500 | $0 | Aug 3, 2015 |
| Oct 24, 2011 | 32071382L | RESOLVE | CLASS - 2 | B254,15,16,32A,5A,50A,B,C,D,E. 50A- CONTROL COVERS MISSING. 50B- BOILER SECTIONS NEED TO BE RESEALED.50C- FLUE PIPE N... | $500 | $0 | Dec 12, 2011 |