ECB violations
145 Ralph Avenue, Brooklyn • Block 01490 • Lot 0001
86 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 7, 2026 | 35731648J | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. LACK OF EMERGENCY LIGHTING FOR EXITS, EXIT DISCHARGES AND PUBL... | $1,250 | $0 | May 27, 2026 |
| May 7, 2026 | 35731647H | ACTIVE | CLASS - 2 | REISSUE ECB #35719700X. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. NOTED: AT (1ST FL)EXITS 7, 5, 9 (3RD FL... | $3,125 | $0 | May 27, 2026 |
| May 7, 2026 | 35731646X | ACTIVE | CLASS - 2 | REISSUE ECB #35719701H. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES... | $3,125 | $0 | May 27, 2026 |
| May 6, 2025 | 35719701H | ACTIVE | CLASS - 2 | REISSUE ECB#35677501K FAILURE TO MAINTAIN BUILDING IN CODE COMPIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND... | $1,250 | $0 | Jul 16, 2025 |
| May 6, 2025 | 35719700X | ACTIVE | CLASS - 2 | REISSUE ECB#35677502M EXIT DOOR NOT SELF CLOSING NOTED AT 4TH FL STAIR C/D & A/B 3RD FL STAIR A/B SMOKE DOOR HALLWAY ... | $625 | $0 | Jul 16, 2025 |
| Apr 26, 2024 | 35677502M | ACTIVE | CLASS - 2 | REISSUE#35671929Y EXIT DOOR NOT SELF-CLOSING AT TIME OF MY INSPECTION I OBSERVED AT THE 4TH FLOOR STAIR A AND BY 427 ... | $1,562 | $0 | May 13, 2024 |
| Apr 26, 2024 | 35677503Y | RESOLVE | CLASS - 2 | REISSUE#35671928M FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.AT TIME OF MY INSPECTION I OBSERVED THE DOOR ... | $1,562 | $0 | May 13, 2024 |
| Apr 26, 2024 | 35677501K | ACTIVE | CLASS - 2 | REISSUE#35671930L FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PU... | $1,562 | $0 | May 13, 2024 |
| Feb 8, 2023 | 35671929Y | ACTIVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING.NOTED:AT 4TH FL STAIR A & 4 BY 427, STAIR D BY 411, STAIR E BY 400, 3RD FL STAIR D BY 311,... | $625 | $0 | May 10, 2023 |
| Feb 8, 2023 | 35671930L | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:ILLUMINATION FOREXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER ... | $625 | $0 | May 10, 2023 |
| Feb 8, 2023 | 35671928M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:DOOR TO ROM 123 & CELLAR LEVEL ELECTRICAL METER ROOM ARE ... | $625 | $0 | May 10, 2023 |
| Apr 13, 2021 | 35553923X | RESOLVE | CLASS - 2 | REISSUE: 35490980L FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: ILLUMINATION FOR EXIT,EXIT DISCHARGES & PUBLIC ... | $1,562 | $0 | Sep 8, 2021 |
| Apr 16, 2020 | 35490988L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDOR PER BC 10... | $625 | $0 | Oct 7, 2020 |
| Mar 10, 2020 | 39019645K | RESOLVE | CLASS - 2 | COMBUSTION AIR OBSTRUCTED AND INTERLOCK INOPERABLE. LOW WATER CUT OFF NOT SUPPORTED. REAR DOOR GASKET MISSING. LINKAG... | $625 | $0 | Apr 21, 2020 |
| Mar 10, 2020 | 39019644Z | RESOLVE | CLASS - 1 | CEASE USE BOILER DUE TO MULTIPLE OIL LEAKS. COMBUSTION AIR OBSTRUCTED AND INTERLOCK NOT OPERABLE. LOW WATER CUT OFF N... | $1,250 | $0 | Apr 21, 2020 |
| Apr 3, 2019 | 35386283L | RESOLVE | CLASS - 2 | REISSUE 35324551H FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MAN NER NO FIRE STOPPING PER BC 712.3: 27-345 AT GAS... | $0 | $0 | Aug 12, 2019 |
| Mar 12, 2018 | 35322393J | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING. NOTED: THE DOORS HAVE DEFECTIVE IN THE TOP HINGE & NOT CLOSE COMPLETELY AT THE FOLLOWING ... | $0 | $0 | Jun 11, 2018 |
| Mar 12, 2018 | 35329551H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NO FIRE STOPPING PER BC 712.3; 27-345. NOTED: AT GAS METER ROOM... | $0 | $0 | Jul 9, 2018 |
| Mar 12, 2018 | 35322392H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER. NOTED: AT BULKHEAD STAIRCASE'A'WATER DAMAGED TO CEILING DUE TO WAT... | $0 | $0 | Jun 11, 2018 |
| Mar 12, 2018 | 35322391X | RESOLVE | CLASS - 2 | REISSUE#35253133R FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER. NO FIRE STOPPING PER BC 712.3;27-345. NOTED: AT ... | $0 | $0 | Jun 11, 2018 |
| Apr 21, 2017 | 35253133R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER,LACK OF EMERGENCY LIGHTING FOR EXITS,EXIT DISCHARGES AND PUBLIC... | $0 | $0 | Jun 12, 2017 |
| Apr 21, 2017 | 35253131N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER,LACK OF EMERGENCY LIGHTING FOR EXITS,EXIT DISCHARGES AND PUBLIC... | $0 | $0 | Jun 12, 2017 |
| Apr 21, 2017 | 35253132P | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING.NOTED:THE FOLLOWING DOOR NOT SELF CLOSING,DOOR MARKED AS EXIT.AT 2ND FL (STAIR A)REMEDY:CO... | $0 | $0 | Jun 12, 2017 |
| Feb 4, 2015 | 35108570Y | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NON FIRE RATE VIEW PANELS INSTALLED @ DOORS ON THE FOLLOWING ROOMS... | $0 | $0 | Mar 30, 2015 |
| May 21, 2014 | 35094881R | RESOLVE | CLASS - 2 | RE-ISSUE # 35013401L. 27-371(B). VISION PANELS. USE OF PROHIBITED VISION PANELS INSTALLED THROUGHOUT CLASSROOM DOORS ... | $0 | $0 | Jul 28, 2014 |
| May 21, 2014 | 35094882Z | RESOLVE | CLASS - 2 | COMBUSTIBLES. EXCESSIVE ARTWORK & PAPERS IN HALLWAYS ON 3RD & 4TH FLOOR. PAPERS HANGING FROM ELECTRICAL FIXTURES IN V... | $0 | $0 | Jul 28, 2014 |
| May 21, 2014 | 35094880P | RESOLVE | CLASS - 2 | RE-ISSUE # 35013402N. DOORS NOT SELF CLOSING. MAIN ENTRANCE TO CAFETERIA, EXTERIOR EXIT DOORS (4) AT REAR OF CAFETERI... | $0 | $0 | Jul 28, 2014 |
| Mar 4, 2013 | 35013402N | RESOLVE | CLASS - 2 | DEFECTIVE DOOR NOTED @ EXIT #7 DOOR STUCK SHUT. ALSO AUDITORIUM, GYM DOORS SPLIT FIRE RATING COMPRMISED. REM: REPAIR ... | $0 | $0 | Apr 15, 2013 |
| Mar 4, 2013 | 35003989M | RESOLVE | CLASS - 2 | 27-765. NO VENTILATION PROVIDED TO ROOM 422 4TH FLR STORAGE ROOM CONVERTED TO OFFICE. REM: PROVIDE VENTILATION. | $0 | $0 | Apr 15, 2013 |
| Mar 4, 2013 | 35003988K | RESOLVE | CLASS - 2 | ILLEGAL HARDWARE NOTED ROOF BULKHEAD DOORS KEYS CYLINDER IN PLACE ALSO DOOR STOPS ON MULTIPLE STAIR CASE DOORS EXIT 1... | $0 | $0 | Apr 15, 2013 |
| Mar 4, 2013 | 35013401L | RESOLVE | CLASS - 2 | REISSUE 34995729Y, 34896955Z. ILLEGAL VISION PANELS INSTALLED THROUGHOUT CLASSROOM DOORS (ALL FLOORS). REM: REPLACE V... | $0 | $0 | Apr 15, 2013 |
| Sep 17, 2012 | 34995729Y | RESOLVE | CLASS - 2 | REISSUE:34896955Z,FAILURE TO PROVIDE THE REQUIRED FIRE RATED CLASSROOMDOOR VISION PANEL AT ROOM 423,424,403,328,327,3... | $0 | $0 | Nov 5, 2012 |
| Jan 5, 2012 | 34933956K | RESOLVE | CLASS - 2 | THE GAS METER ROOM IS LACKING FRESH AIR VENTILATION ON THE CELLAR LEVEL. REMEDY: PROVIDE/MAINTIAN FRESH AIR VENTILATI... | $0 | $0 | Apr 16, 2012 |
| Jan 20, 2011 | 34882097Y | RESOLVE | CLASS - 3 | @ STAIRWELL C1 & D1 EXIT DOORS 3 & 4 (RIGHT HAND SIDE) DOOR DOES NOT PROPERLY OPEN OR CLOSE POSSIBLY DUE TO DOOR SADD... | $0 | $0 | Mar 14, 2011 |
| Jan 20, 2011 | 34896956K | RESOLVE | CLASS - 3 | FAIL TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER @ ROOF WEATHER PROOFING IS DEFECTIVE SEVERAL CONCRETE COPING STONES ... | $0 | $0 | Mar 14, 2011 |
| Jan 20, 2011 | 34896957M | RESOLVE | CLASS - 2 | @ BOILER ROOM FRESH AIR VENTS NOT WORKING. REM:PROVIDE OPERATING FRESH AIR VENTS FOR 3 PC OF COMBUSTION EQUIPMENT 2 B... | $0 | $0 | Mar 14, 2011 |
| Jan 20, 2011 | 34882094Z | RESOLVE | CLASS - 2 | PROVIDE F.A.I FOR GAS METER RM. @ CELLAR LEVEL COMPLY W/CODE. REM:PROVIDE FRESH AIR VENTILATION. | $0 | $0 | Mar 14, 2011 |
| Jan 20, 2011 | 34882096M | RESOLVE | CLASS - 3 | @ AUDITORIUM HALLWAY DUAL EXIT DOORS LEFT HAND DOOR PROVIDE AN OPERABLE CLOSER TO MAKE SELF CLOSING. REM: MAKE ALL NE... | $0 | $0 | Mar 14, 2011 |
| Jan 20, 2011 | 34882098X | RESOLVE | CLASS - 2 | @ AUDITORIUM SECTION, DIVIDING DOORS SEPERATING LUNCH RM, GYMNASIUM & AUDITORIUM ARE DEFECTIVE & PARTIALLY UNSECURED ... | $0 | $0 | Mar 14, 2011 |
| Jan 20, 2011 | 34882095K | RESOLVE | CLASS - 3 | @ CAFETERIA CONCRETE BLOCK EAST WALL HAS A VERTICAL CRACK APPX 8'FT LONG @ EXIT DOOR F1 SECTION INTERIOR BLOCK WALL L... | $0 | $0 | Mar 14, 2011 |
| Jan 20, 2011 | 34896955Z | RESOLVE | CLASS - 2 | FAIL TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER: FAIL TO PROVIDE THE REQUIRED FIRE RATED DOOR BETWEEN CLASSROOMS & C... | $0 | $0 | Mar 14, 2011 |
| Feb 23, 2010 | 34835284H | RESOLVE | CLASS - 2 | THE GAS METER ROOM IS LACKING FRESH AIR VENTILATION @ CELLAR LEVEL.REMEDY:PROVIDE/MAINTAIN FRESH AIR VENTILATION. | $0 | $0 | Apr 19, 2010 |
| Feb 23, 2010 | 34835283X | RESOLVE | CLASS - 2 | INTERIOR CONCRETE BLOCK WALL HAS A VERTICAL CRACK APPROX 8' FEET LONG LOCATE IN THE CAFETERIA 1ST FLOOR LEVEL.REMEDY:... | $0 | $0 | Apr 19, 2010 |
| Feb 12, 2009 | 34760761H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN THAT WINDOWS ARE NOT CLOSING OR LOCKING PROPERLY AT VARIOUS LOCATIONS W/I CLASSROOMS AND ... | $0 | $0 | May 11, 2009 |
| Jan 21, 2009 | 34760760X | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BLDG IN THAT ROOF IS LEAKING OVER RM 427 VISIBLE STAINING REMEDY:MAINTAIN BLDG REPAIR LEAK REPLAC... | $0 | $0 | May 11, 2009 |
| Jan 21, 2009 | 34760762J | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING AT GYM DUE TO FIBER CORE OF DOOOR ISN'T HOLDING HINGE SCREWS REMEDY:REPAIR/REPLACE DOOR | $0 | $0 | May 11, 2009 |
| Jan 21, 2009 | 34760763L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER IN THAT A.F.P.S.C DOOR IS MISSING AT EXIT 8 AUDITORIUM REMEDY:REPLA... | $0 | $0 | May 11, 2009 |
| Mar 3, 2008 | 34639625Z | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN INTERIOR. GAS METER ROOM 1) STANDARD UNPROTECTED LIGHTBULB IN ROOM IN LIEU OF THE BLDG CODE APPRO... | $0 | $0 | Apr 21, 2008 |
| Mar 21, 2007 | 34569884M | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN. NOTED: GATES FOR GARBAGE DUMPSTER ARE IN DIS- REPAIR BENT & NOT ABLE TO CLOSE. REMEDY: REPAIR OR... | $0 | $0 | Jun 25, 2007 |
| Mar 21, 2007 | 34569885Y | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN. NOTED: STORM DRAIN AT ROOF LEVEL LEAKING INTO CORRIDOR AT 4TH FLOOR BETWEEN ROOMS 425 & 427, WAT... | $0 | $0 | Jun 25, 2007 |