ECB violations
771 Mac Donough Street, Brooklyn • Block 01498 • Lot 0053
40 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Sep 3, 2020 | 35502851X | RESOLVE | CLASS - 1 | REISSUE ECB #35475677Z FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANENR NOTED AT CELLAR GAS METER RM OBSERVED NO... | $3,125 | $0 | Jan 20, 2021 |
| Jan 28, 2020 | 35475677Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT THE CELLAR LEVEL GAS METER ROOM; NO VENTILATION SYST... | $3,125 | $0 | Jun 10, 2020 |
| Jan 22, 2020 | 39016223R | RESOLVE | CLASS - 2 | I OBSERVED AT ABOVE ADDRESS NO VENTILATION IN THE GAS METER ROOM. AS PER FGC101.2.3, REPAIR AND/OR REPLACE | $1,562 | $0 | Feb 5, 2020 |
| Dec 9, 2019 | 35465142N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.OBSERVED @CELLAR LEVEL GAS METER ROOM;NO VENTILATION SYSTEM INSTALL... | $3,125 | $0 | Apr 22, 2020 |
| Sep 23, 2019 | 35452518J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT CELLAR GAS METER ROOM WITH HAVING NO VENTILATION SYSTE... | $3,125 | $0 | Dec 2, 2019 |
| Sep 23, 2019 | 35429073K | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION#35442207N ISSUED ON 7/17/19 AND TO FILE... | $1,250 | $0 | Dec 2, 2019 |
| Sep 23, 2019 | 35452519L | ACTIVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE COFO OR DOB RECORDS.NOTED:ATCELLAR GAS METER ROOM CONVERTED/OCCUPIED AS CON... | $1,250 | $0 | Dec 2, 2019 |
| Aug 17, 2019 | 35447852Z | RESOLVE | CLASS - 2 | 28-301.1 FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE),FGC APPENDIX E(E4)(2014 CODE). NOTED:... | $0 | $0 | Dec 23, 2019 |
| Jul 17, 2019 | 35442207N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT CELLAR GAS METER RM. HAS NO FRESH AIR VENTILATION SY... | $0 | $0 | Nov 25, 2019 |
| Jul 15, 2019 | 39005596X | RESOLVE | CLASS - 1 | NO VENTILATION IN GAS METER ROOM., REPAIR AND/REPLACE | $0 | $0 | Jul 19, 2019 |
| May 25, 2019 | 35423308Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT CELL AR LEVEL GAS METER ROOM WITH HAVING NO AIR VENT... | $0 | $0 | Sep 23, 2019 |
| May 18, 2019 | 35423357P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT CELLAR GAS METER ROOM HAS NO FRESH AIR VENTILATION. ... | $0 | $0 | Sep 16, 2019 |
| Apr 22, 2019 | 35406313Z | RESOLVE | CLASS - 1 | AN UNLAWFUL ACT. FAILURE TO COMPLY W/ AN ORDER OF THE COMMISSIONER. FAILURE TO CORRECT AND CERTIFY SUMMONS#35386553M,... | $0 | $0 | Aug 5, 2019 |
| Apr 6, 2019 | 35402525M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTE AT CELLAR LEVEL IN GAS METER ROOM NO FRESH AIR VENTILATIO... | $0 | $0 | Jul 29, 2019 |
| Feb 27, 2019 | 35386553M | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEM I OBSERVED AT THE WATER MAIN, THE GROUNDING ELECTRODE CONDUCTOR DISCONNECTED FROM... | $0 | $0 | Jun 17, 2019 |
| Feb 27, 2019 | 35386211M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 2/27/19 AT ABOVE ADDRESS NO VENTILATION IN THE GAS... | $0 | $0 | Jul 1, 2019 |
| Feb 7, 2019 | 35383636Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER.NOTED:@CELLAR LVL NO FRESH AIR VENTILATION IN GAS METER ROOM.RE... | $0 | $0 | Jun 3, 2019 |
| Jan 2, 2019 | 35379915P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER. NOTED: AT CELLAR LEVEL NO FRESH AIR VENTILATION IN GAS METER R... | $0 | $0 | Apr 15, 2019 |
| Dec 14, 2018 | 35358779R | RESOLVE | CLASS - 1 | UNLAWFUL ACT,FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. RECORDS INDICATE NO APPLICATION FILED TO CORRECT CE... | $0 | $0 | Apr 1, 2019 |
| Nov 7, 2018 | 35372291Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT CELLAR LEVEL, IN THE GAS METER ROOM, HOT FRESH AIR V... | $0 | $0 | Nov 27, 2018 |
| Oct 30, 2018 | 35359139N | RESOLVE | CLASS - 1 | UNLAWFUL ACT,FAILURE TO COMPLY TITH AN ORDER OF THE COMMISSIONER RECORDS INDICATE NO APPLICATION FILED TO CORRECT,CER... | $0 | $0 | Jan 28, 2019 |
| Sep 19, 2018 | 35346969J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT TIME OF INSPECTION OBSERVED AT CELLAR IN GAS METER R... | $0 | $0 | Dec 24, 2018 |
| Sep 17, 2018 | 35346143N | RESOLVE | CLASS - 1 | UNLAWFUL ACT, FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. RECORDS INDICATE NO APPLICATION FILED TO REMOVE CO... | $0 | $0 | Dec 10, 2018 |
| Aug 6, 2018 | 35346952N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT TIME OF INSPECTION OBSERVED AT CELLAR IN GAS METER ROO... | $0 | $0 | Oct 29, 2018 |
| Jul 26, 2018 | 35341624L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER, NO (FIRE STOOPING) PER BC 712.3;27-345 THROUGH OUT CELLAR LEVE... | $0 | $0 | Oct 29, 2018 |
| Jul 26, 2018 | 35344712P | RESOLVE | CLASS - 1 | FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH SECTION.OBSERVED AT WATER MAIN LOCATED IN THE CEL... | $0 | $0 | Oct 29, 2018 |
| Jul 26, 2018 | 35347075P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED ON 7/26/2018 AT ABOVE ADDRESS NO VENTILATION IN HAS ME... | $0 | $0 | Oct 29, 2018 |
| Jun 27, 2018 | 35341958L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: @ TIME OF INSP OBSERVED @ CELLAR IN GAS METER ROOM NOT FRES... | $0 | $0 | Sep 17, 2018 |
| Apr 24, 2018 | 35329068H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: @ CELLAR GAS METER ROOM, NOT FRESH AIR VENTILATION PROVIDED... | $0 | $0 | Jul 2, 2018 |
| Mar 9, 2018 | 35321659N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER. NOTED: NO FRESH AIR VENTILATION PROVIDED FOR CELLAR GAS METER RO... | $0 | $0 | May 21, 2018 |
| Jan 10, 2018 | 35297795K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: IN THE CELLAR, GAS METER ROOM, O FRESH AIR VENTILATION. RMD... | $0 | $0 | Apr 9, 2018 |
| Nov 24, 2017 | 35281142R | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35294108X ISSUED ON 10/10/17 AND TO FI... | $4,000 | $0 | Mar 19, 2018 |
| Oct 10, 2017 | 35294108X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.NOTED;NO FRESH AIR VENTILATION IN THE GAS METER RM IN CELLAR.REM:PR... | $0 | $0 | Dec 4, 2017 |
| Aug 4, 2017 | 35287577N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3; 27-345, NOTED: FIRE STOPPING MI... | $0 | $0 | Dec 18, 2017 |
| Aug 4, 2017 | 35286918H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON 8/4/17 AT ABOVE ADDRESS NO FRESH AIR VEN IN GAS MET... | $2,500 | $0 | Aug 16, 2017 |
| Jun 21, 2017 | 35271441H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.OBSERVED ON 6/21/17 @ ABOVE ADDRESS IN BASEMENT,PIPE GOING THROUGH ... | $0 | $0 | Sep 11, 2017 |
| Oct 4, 2016 | 35214277Y | RESOLVE | CLASS - 1 | SEC: FGC 408.2. DRIP-FUTURE CONNECTS EXIST DOWN STREAM OF APPLIANCE, OBSERVED ON 10/04/16 @ 1:30PM FUTURE GAS CONNECT... | $0 | $0 | Nov 14, 2016 |
| Oct 4, 2016 | 35214278X | RESOLVE | CLASS - 1 | SEC: FGC401.5. GAS PIPING NOT LABELED OBSERVED ON 10/4/16 @ THE TIME OF 1:30PM THE GAS PIPES THROUGHOUT THE BASEMENT ... | $1,600 | $0 | Nov 14, 2016 |
| Oct 4, 2016 | 35214279H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: FAILURE TO COMPLY W/ LAW FOR DRAINAGE SYSTEM PER PC702.1; 27-911 O... | $0 | $0 | Nov 14, 2016 |
| Sep 5, 2015 | 35141125K | ACTIVE | CLASS - 1 | SEC. 411.1 MISC VIOLATION. INSTALLED RESIDENTIAL FLEX CONNECTION ON COMM-GAS DRYERS W/O MOVABLE(CASTERS)HAND PIPE REQ... | $0 | $0 | Oct 26, 2015 |