Jun 12, 2025 39150877N ACTIVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. CLASS 2 ITEMS: 1) HALLWAY POSITION INDICATORS MALFUNCTIONING, ... $3,125 $3,125 Aug 20, 2025
Apr 25, 2025 35717441L ACTIVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: LACK OF EMERGENCY LIGHTING FOR EXITS, EXIT DISCHARGES AND PUBL... $6,250 $6,250 Jul 2, 2025
Oct 29, 2020 39031225X RESOLVE CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS PER 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. REMEDY : INSTAL... $3,125 $0 Mar 3, 2021
Mar 2, 2020 39018649N ACTIVE CLASS - 2 POTABLE/DOMESTIC HOT WATER TEMP GAUGE ON ROCKMILL MP50 BOILER IS NOT WORKING.CORRECT VIOLATING CONDITION & SUBMIT A C... $3,125 $0 Jan 11, 2021
Mar 7, 2019 32098700H ACTIVE CLASS - 2 B254,3A,11A,4A. B254. 4A-MANUAL RESET LOW WATER CUT OFF NEEDED; 3A-FLUE CORRODING. CORRECT ALL LISTED VIOLATIONS AND ... $625 $0 Sep 4, 2019
Jan 15, 2019 37014190H RESOLVE CLASS - 2 FAILURE TO COMPLY WITH COMMISSIONERS ORDER CONTAINED IN SUMMONS/ VIOLATION #35325030Y ISSUED ON 3/19/18 AND TO FILE A... $1,250 $0 Jul 15, 2019
Mar 19, 2018 35325030Y RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING WALL(S) OF APPURTENANCES (INTERIOR) NOTED AT BASEMENT IN THE BOILER ROOM; 4" OF SANDING ... $1,250 $0 May 14, 2018
Mar 14, 2018 32093328H ACTIVE CLASS - 2 B254, 6, 11, 32A,50. VIOLATING CONDITIONS #11 BLOWDOWN VALVES NOT PROPERLY PIPED #6 RELIEF VALVE ON DOMESTIC HOT WATE... $625 $0 May 7, 2018
Mar 12, 2018 32093327X ACTIVE CLASS - 1 CEASE USE B154, 51, 286 AS PER CLASS 1(B154) 29-301.1 #28 AND 51 EVIDENCE OF STEAM COMMING OUT OF TUBE ACCESS DOOR. D... $1,250 $0 May 7, 2018
Apr 20, 2017 35235861X RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.DEFECTS NOTED:@GYM, WOODEN FLR FINISH ROTTEN AND MISSING PIECES @VA... $500 $0 Jun 12, 2017
Sep 26, 2016 35207969J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG WALLS IN CODE-COMPLIANT MANNER(INTERIOR)NOTED:CMN BLOCK IS BROKEN AROUND PIPES GOING FROM BO... $530 $0 Nov 14, 2016
Sep 20, 2007 34547147P RESOLVE Non-Hazardous WORK W/O A PERMIT.WORK NOTED:STEEL PLATFORM ERECTED IN ALLEYWAY & ATTACHED TO 2 BLDG W/SUPPORT POSTS & STEEL LADDER A... $0 $0 Sep 29, 2009
Sep 20, 2007 34547148R RESOLVE Non-Hazardous FAILURE TO PROVIDE THE MINIMUM SPACE REQUIRED BETWEEN EXTERIOR MECHANICAL EQUIPMENT & THE WINDOWS OF A DWELLING UNIT.... $0 $0 Oct 2, 2009
Nov 13, 2002 38134327M RESOLVE Non-Hazardous 55X11,54B7,73##,41H8,21M7,11I12,8V1,17H12,29H11,49E1,49#11,80D6,36M7,54-B-PROVIDE PROPER COTTER PINS IN BRAKE PINS,73... $350 $0 Dec 31, 2002
Aug 13, 1999 34223161K RESOLVE Non-Hazardous FAILURE TO OBTAIN A CERTIFICATE OF ELECTRICAL INSPECTION FROM THE BUREAU OF ELECTRICAL CONTROL FOR THE INSPECTION OF ... $800 $0 Sep 27, 1999
Nov 16, 1993 38038130Z RESOLVE Non-Hazardous 28H,74D,75#. 74 PROPERLY SECURE MOTOR ROOM FLOOR GRATING. 75 PERFORM 5YR. TEST. PROPERLY TAG DEVICE AND FILE ELEV. 3 ... $200 $0 May 2, 1994
Jul 26, 1993 34087655R RESOLVE Non-Hazardous FAILURE TO FILE A REPORT OF COMPLIANCE WITH LOCAL LAW 16/84 OF REQUIREFILE PROTECTION SYSTEMS. REMEDY:FILE REPORT. $400 $0 Sep 20, 1993
Jul 26, 1993 34087654P RESOLVE Non-Hazardous FAILURE TO PROVIDE ADEQUATE EMERGENCY POWER EXIT LIGHT PURSUANT TO BECSTANDARDS. FAILURE TO PROVIDE ADEQUATE EMERGENC... $800 $0 Sep 20, 1993
May 10, 1991 34054405N RESOLVE Non-Hazardous FAILURE TO PROVIDE EMERGENCY POWER EXIT/DIRECTIONAL SIGNS THROUGHOUT 1ST 2ND FLOOR AND STAIRCASE (BOTH-2)AND TO BASEM... $500 $0 Jun 24, 1991