ECB violations
520 Gates Avenue, Brooklyn • Block 01814 • Lot 0123
32 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Oct 31, 2025 | 39165551P | ACTIVE | CLASS - 2 | OBSERVED BATHROOM DOOR ON SECOND FLOOR IS OBSTRUCTED BY URINAL. TOILET SEATS IS NOT OPEN ENDED AND PVC PIPING ON WAST... | $1,250 | $1,250 | Jan 14, 2026 |
| Oct 31, 2025 | 39165525L | ACTIVE | CLASS - 2 | HB SMITH STEAM BOILER, MODEL# 28A-07.BOILER IS UNREGISTERED. FILE PERMIT AND HAVE DOB DO FINAL INSPECTION. | $1,250 | $1,250 | Feb 18, 2026 |
| Dec 31, 2024 | 39134172N | ACTIVE | CLASS - 2 | I NOTED THE PREVIOUSLY INSTALLED WATER METER JUMPER CONDUCTOR MISSING. AS REQUIRED THE GROUNDING SYSTEM SHALL BE MAIN... | $1,200 | $0 | May 5, 2025 |
| Dec 31, 2024 | 39134174R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $1,250 | $1,250 | Apr 21, 2026 |
| Dec 31, 2024 | 39134176K | RESOLVE | CLASS - 2 | NON SELF CLOSING. OBSERVED NON SELF CLOSING EXIT DOORS THROUGHOUT BUILDING. POTENTIAL FIRE HAZARD., REPAIR/REPLACE DOOR | $625 | $625 | Apr 21, 2026 |
| Dec 31, 2024 | 39134175Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1 (2014 COD... | $1,250 | $1,250 | Apr 21, 2026 |
| Nov 6, 2023 | 39098892X | RESOLVE | CLASS - 2 | NO EMERGENCY LIGHTING THROUGHOUT STAIRCASE CORRIDOR., REPAIR AND/OR REPLACE LIGHTING | $1,250 | $0 | Jan 10, 2024 |
| Mar 22, 2022 | 35651043R | RESOLVE | CLASS - 2 | WORK WITHOUT A PERMIT.OBSERVED AT CELLAR LEVEL GAS METER ROOM,A ROOM WITH DOOR AND LOCK WAS BUILT.ALSO THE ROOM WALLS... | $500 | $0 | Aug 24, 2022 |
| Mar 22, 2022 | 35651035R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:NO FIRESTOPPING PER BC712.3;27-345.SEVERAL HOLES ON BLOCK WALLS DUE ... | $625 | $0 | Aug 10, 2022 |
| Oct 13, 2021 | 39049228R | RESOLVE | CLASS - 1 | I OBSERVED NEWLY INSTALLED GAS PIPING IN THE GAS METER ROOM LOCATED THE THE BASEMENT., OBTAIN PERMIT | $2,500 | $0 | Feb 16, 2022 |
| Oct 13, 2021 | 39049229Z | RESOLVE | CLASS - 2 | I OBSERVED ACTIVE WATER LEAK IN THE GAS METER ROOM LOCATED IN THE BASEMENT., REPAIR AND/OR REPLACE | $625 | $0 | Feb 16, 2022 |
| Sep 27, 2021 | 39048212H | ACTIVE | CLASS - 2 | CONDENSATE PUMP IS DEFECT/CONDENSATE TANK VENT IS REDUCED/CHIMNEY BASE DOOR DEFECT/#2 HWH IS DEFECT/DEBRIS AT OIL TAN... | $625 | $0 | Feb 2, 2022 |
| Jan 6, 2021 | 39034401J | ACTIVE | CLASS - 2 | A NEW BOILER IS BEING INSTALLED ON SITE WITHOUT A DOB PERMIT; CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECT... | $1,250 | $0 | May 12, 2021 |
| Sep 6, 2018 | 35388393L | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35341999H ISSUED ON 07-20-18 & TO FILE A C OF C PURSUAN... | $625 | $0 | Mar 20, 2019 |
| Jul 20, 2018 | 35341999H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED IN GAS METER ROOM NO PERMANENT VENTILATION INSTALLED I... | $1,250 | $0 | Oct 30, 2018 |
| Jul 20, 2018 | 35341981J | RESOLVE | CLASS - 2 | FAILURE TO PAINT DEDICATED SPRINKLER PIPING/VALUES IN ACCORDANCE WITH SECTION.OBSERVED THROUGHOUT BUILDING THE AUTOMA... | $1,250 | $0 | Oct 29, 2018 |
| Jul 20, 2018 | 35342225Z | RESOLVE | CLASS - 2 | FAIL TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER RE:INSTALLATION/MAINTENANCE OF PLUMBING MATERIAL/EQUIPMENT PER PC ... | $1,250 | $0 | Oct 30, 2018 |
| Mar 31, 2018 | 35326325X | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35311902P ISSUED ON 1-31-18 & TO FILE A C OF C PURSUANT... | $1,250 | $0 | Jul 30, 2018 |
| Jan 31, 2018 | 35311901N | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE GROUND FAULT CIRCUIT INTERRUPTOR (GFCI) AS REQUIREDOBSERVED DEFECTIVE GFCI OUTLETS THROUGHOUT BATH... | $6,000 | $0 | May 31, 2018 |
| Jan 31, 2018 | 35311902P | RESOLVE | CLASS - 1 | FILED A CERT OF CORRECTION OR OTHER RELATED MATERIALS CONTAINING MATERIAL FALSE STATEMENT(S).APPL B 434557 OBTAINED T... | $4,800 | $0 | May 16, 2018 |
| Jan 31, 2018 | 35275730M | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO #35286734N ISSUED ON 07/20/2017 & TO FILE A CERT OF COR... | $800 | $0 | May 31, 2018 |
| Jan 31, 2018 | 35311903R | RESOLVE | CLASS - 1 | FAILURE TO INSTALL GROUNDING ELEC TRUDE CONDUCTOR IN AXXURDANCE W/SECTION.I OBSERVED THE GROUNDING CONDUCTOR INSTALLE... | $4,800 | $0 | May 31, 2018 |
| Oct 26, 2017 | 35285091Y | RESOLVE | CLASS - 1 | UNLAWFUL ACT FAILURE TO COMPLY W/AN ORDER TO THE COMMISSIONER. RECORDSINDICATE NO APPLICATION WAS MADE TO CORRECT & C... | $2,400 | $0 | Feb 21, 2018 |
| Jul 20, 2017 | 35286735P | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SERVICES.OBSERVED GROUND CONNECTOR AND CONDUCTOR HANGING FREE AND NOT CONNECTED TO WATER... | $4,800 | $0 | Nov 13, 2017 |
| Jul 20, 2017 | 35286734N | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE GROUND FAULT CIRCUIT INTERRUPTER(GFCI)AS REQUIRED. OBSERVED DEFECTIVE GFCI RECEPTACLE OUTLETS THRO... | $2,400 | $0 | Nov 13, 2017 |
| Jul 20, 2017 | 35286736R | RESOLVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,MATERIALS APPARATUS,DEVICE,APPLIANCE,OR WIRING IN USE.OBSERVED MC C... | $1,600 | $0 | Nov 13, 2017 |
| Feb 28, 2017 | 35228757K | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES. NOTE: PARAPET (INNER) WALL @ EXP#1 HAS APPROX 1" WIDE STEP CRACK. ... | $0 | $0 | Apr 17, 2017 |
| Feb 28, 2017 | 35228824L | RESOLVE | CLASS - 2 | MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED ON 2/28/17 ON THECELLAR LEVEL GAS METER ROOM IS NOT PROPERLY VEN... | $530 | $0 | Apr 17, 2017 |
| Oct 18, 2016 | 35214515K | RESOLVE | CLASS - 1 | 408.2MISCELLANEOUS VIOLATIONS DRIPS-FUTURE CONNECTS EXIST DOWN STREAM OF APPLIANCE OBSERVED ON 10/18/16 A FUTURE GAS ... | $1,600 | $0 | Jan 4, 2017 |
| Oct 18, 2016 | 35214513R | RESOLVE | CLASS - 1 | 411.1 MISCELLANEOUS VIOLATION RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT.OBSERVED ON10/18/16 COMMERCIAL GAS FL... | $1,600 | $0 | Dec 5, 2016 |
| Oct 18, 2016 | 35214516M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED ON 10/18/16 EXCESSIVE STORAGE IN GAS METER ROOM.REMEDY... | $1,000 | $0 | Jan 4, 2017 |
| Oct 18, 2016 | 35214514Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER TO COMPLY W.LAW FOR DRAINAGE SYSTEM PER PD702.1;27-911.OBSERVED ON ... | $500 | $0 | Mar 6, 2017 |