ECB violations
263 Classon Avenue • Block 01924 • Lot 7501
117 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 10, 2005 | 32048032X | ACTIVE | Hazardous | BQ9/36 4A/19B 4A HAZARDOUS. BQ9-UTICA BOILER HAS NO BL WORK TYPE. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048033H | ACTIVE | Hazardous | BQ9/36 4A/19B 24B/50 38/50A BQ9- UTICA BOILER HAS NO BL WORK TYPE 4A- HAZARDOUS. 24B- OUTSIDE THE BOILER ROOM. 50- FA... | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048034J | ACTIVE | Hazardous | BQ9/36 4A/19B 4A-HAZARDOUS BQ9- UTICA BOILER HAS NO BL WORK TYPE. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048036N | ACTIVE | Hazardous | BQ9/36 4A/19B 24B/50 38/50A BQ9- UTICA BOILER HAS NO BL WORK TYPE 4A HAZARDOUS. 50- FAN INDUCER IS NOT WIRED PROPERLY... | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048037P | ACTIVE | Hazardous | BQ9/36 4A/19B 4A- HAZARDOUS BQ9- UTICA BOILER HAS NO BL WORK TYPE. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048038R | ACTIVE | Hazardous | BQ9/36 4A/19B 4A- HAZARDOUS. BQ9- UTICA BOILER HAS NO BL WORK TYPE. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048039Z | ACTIVE | Hazardous | BQ9/36 4A/19B BQ9 UTICA HOT WATER BOILER HAS NO BL WORK TYPE 4A HAZARDOUS. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048040X | ACTIVE | Hazardous | BQ9/36 4A/19B 50 BQ9- UTICA HOT WATER BOILER HAS NO BL WORK TYPE. 4A- HAZARDOUS 50- VALVE IS NOT INSTALLED UPRIGHT WI... | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048041H | ACTIVE | Hazardous | BQ9- UTICA HOT WATER BOILER HAS NO BL WORK TYPE 4A HAZARDOUS. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048042J | ACTIVE | Hazardous | BQ9/36 4A/19B BQ9 UTICA BOILER HAS NO BL WORK TYPE 4A HAZARDOUS. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048043L | ACTIVE | Hazardous | BQ9/36 4A/19B BQ9- UTICA BOILER HAS NO BL WORK TYPE 4A HAZARDOUS. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048044N | ACTIVE | Hazardous | BQ9/36/4A/19B/38/50/50A/50B/50C BQ9-SLANT FIN BOILER HAS NO BL WORK TYPE 4A HAZARDOUS 50)FAN INDUCER IS WEIRD IMPROPE... | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048045P | ACTIVE | Hazardous | BQ9/36/4A/19B/50 BQ9-SLANT FIN BOILER HAS NO BL WORK TYPE 4A HAZARDOUS50-RELIEF VALVE IS NOT INSTALLED UPRIGHT WITH T... | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048046R | ACTIVE | Hazardous | BQ9/36/19B/36/50 BQ9-SLANT FIN BOILER HAS NO BL WORK TYPE 4A HAZARDOUS50-RELIEF VALVE IS NOT INSTALLED IN THE UPRIGHT... | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048047Z | ACTIVE | Hazardous | BQ9/36/4A/19B/50 BQ0-SLANT FIN BOILER HAS NO BL WORK TYPE.4A HAZARDOUS50-RELIEF VALVE IS NOT INSTALLED WITH THE LEVER... | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048049M | ACTIVE | Hazardous | BQ9/36/4A/19B/50 BQ9-SLANT VALVE IS NOT INSTALLED IN THE UPRIGHT POSITION WITH THE TEST LEVER ON TOP | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048050J | ACTIVE | Non-Hazardous | BQ9/50/36/50A. ENERJET MODEL #BG-3 HAS NO BL WORK TYPE. 50-DISCHARGE PIPE HAS A THREADED ELBOW AT THE END. 50A-RELIEF... | $350 | $0 | Oct 31, 2005 |
| May 10, 2005 | 32048051L | ACTIVE | Non-Hazardous | BQ9/44C/36/50. BQ9-ENERJET MODEL #BG-3 HAS NO BL WORK TYPE. 50-LOW WATER CUT OFF IS NOT PROTECTING THE BOILER WHERE I... | $350 | $0 | Oct 31, 2005 |
| May 10, 2005 | 32048052N | ACTIVE | Non-Hazardous | BQ9/50/36. BQ9-ENERJET MODEL #BG-3 HAS NO BL WORK TYPE. 50-LOW WATER CUT OFF DOES NOT PROTECT THE BOILER WHERE IT IS ... | $350 | $0 | Oct 31, 2005 |
| May 10, 2005 | 32048053P | ACTIVE | Non-Hazardous | BQ9/50/36/50A. BQ9-ENERJET HOT WATER BOILER MODEL #BG-3 HAS NO BL WORKTYPE. 50-HAZARDOUS-DEBRIS IS PILED UP ONTO THE ... | $800 | $0 | Oct 31, 2005 |
| May 10, 2005 | 32048054R | ACTIVE | Non-Hazardous | BQ9/44C/36/50. BQ9-ENERJET MODEL #BG-3 HAS NO BL WORK TYPE. 50-LOW WATER CUT OFF DOES NOT PROTECT THE BOILER WHERE IT... | $350 | $0 | Oct 31, 2005 |
| May 10, 2005 | 32048055Z | ACTIVE | Non-Hazardous | BQ9/4A/50/36/19B/50A. BQ9-ENERJET HOT WATER BOILER HAS NO BL WORK TYPE4A-HAZARDOUS. 50-MISSING COVER PLATE ON RELAY B... | $800 | $0 | Oct 31, 2005 |
| May 10, 2005 | 32048056K | ACTIVE | Hazardous | BQ9/4A 19B/36 34A/50 BQ9-UTICA BOILER HAS NO BL WORK TYPE 4A HAZARDOUS50-MISSING CLEAN-OUT ACCESS ON THE CHIMNEY. | $850 | $0 | Dec 21, 2005 |
| May 10, 2005 | 32048057M | ACTIVE | Hazardous | 4A/19B 36/32A BQ9-UTICA BOILER HAS NO BL WORK TYPE 32A- RELAY COVER MISSING EXPOSING THE WIRES 4A- HAZARDOUS. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048062R | ACTIVE | Hazardous | BQ9/36 19B/4A 4A HAZARDOUS BQ9- UTICA HOT WATER BOILER HAS NO BL WORK TYPE. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048035L | ACTIVE | Hazardous | BQ9/36 4A/19B 4A-HAZARDOUS. BQ9- UTICA BOILER HAS NO BL WORK TYPE. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048048K | ACTIVE | Hazardous | BQ9-SLANT FIN BOILER HAS NO BL WORK TYPE 4A HAZARDOUS 50-RELIEF VALVE IS NOT INSTALLED IN THE UPRIGHT POSITION WITH T... | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048074Y | ACTIVE | Hazardous | BQ9/36 4A/19B 24B/50 38/50A BQ9- UTICA MODEL #MGB 50 HAS NO BL WORK TYPE 4A HAZARDOUS. 50 FAN INDUCERS ARE NOT WIRED ... | $850 | $0 | Dec 21, 2005 |
| May 10, 2005 | 32048058Y | ACTIVE | Hazardous | BQ9/36 19B/4A 4A-HAZARDOUS BQ9- UTICA HOT WATER BOILER HAS NO BL WORK TYPE. | $850 | $0 | Dec 21, 2005 |
| May 10, 2005 | 32048059X | ACTIVE | Hazardous | 4A/19B 36/BQ9 32A 4A-HAZARDOUS BQ9- UTICA HOT WATER BOILER HAS NO BL WORK TYPE. 32A-MISSING COVER ON RELAY EXPOSING T... | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048060N | ACTIVE | Hazardous | BQ9/36 4A/19B 4A-HAZARDOUS BQ9- UTICA HOT WATER HAS NO BL WORK TYPE. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048061P | ACTIVE | Hazardous | BQ9/4A 19B/36 4A HAZARDOUS BQ9-UTICA HOT WATER BOILER HAS NO BL WORK TYPE. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048063Z | ACTIVE | Hazardous | BQ9/36 19B/4A 4A-HAZARDOUS BQ9- UTICA HOT WATER BOILER HAS NO BL WORK TYPE. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048064K | ACTIVE | Hazardous | BQ9/36 4A/19B 4A HAZARDOUS BQ9-UTICA BOILER HAS NOT BL WORK TYPE. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048065M | ACTIVE | Hazardous | 4A/BQ9 19B/36 4A- HAZARDOUS BQ9- UTICA HOT WATER BOILER HAS NO BL WORKTYPE. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048066Y | ACTIVE | Hazardous | 4A/BQ9 36/19B 4A-HAZARDOUS BQ9-UTICA HOT WATER BOILER HAS NO BL WORK TYPE. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048067X | ACTIVE | Hazardous | 4A/BQ9 19B/36 4A- HAZARDOUS BQ9-UTICA HOT WATER BOILER HAS NO BL WORK TYPE. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048068H | ACTIVE | Hazardous | 4A/19B BQ9/36 4A- HAZARDOUS. BQ9- UTICA HOT WATER HAS NO BL WORK TYPE. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048069J | ACTIVE | Hazardous | 4A/19B BQ9/36 4A-HAZARDOUS. BQ9- UTICA HOT WATER BOILER HAS NO BL WORKTYPE. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048070R | ACTIVE | Hazardous | BQ9/36 4A/19B 4A-HAZARDOUS BQ9- UTICA HOT WATER BOILER HAS NO BL WORK TYPE. | $850 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32047734X | ACTIVE | Non-Hazardous | 4A/24B/50A/BQ9/19B/50/36. 4A-HAZARDOUS. 24B-OUTSIDE THE BOILER ROOM. 50-INCORRECT SIZED BACKFLOW PREVENTER FOR TOTAL ... | $800 | $0 | Oct 31, 2005 |
| May 10, 2005 | 32048072K | ACTIVE | Hazardous | 4B/36/19A. 4B-HAZARDOUS-NOT WIRED. 19A-NOT WIRED. | $350 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048073M | ACTIVE | Hazardous | 4B/36/19A. 4B-HAZARDOUS-NOT WIRED. 19A-NOT WIRED. | $350 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32048071Z | ACTIVE | Hazardous | 4B/36/19A. 4B-HAZARDOUS/NOT WIRED INTO THE SYSTEM. 19A-NOT WIRED. | $350 | $0 | Dec 5, 2005 |
| May 10, 2005 | 32047735H | ACTIVE | Non-Hazardous | BQ9/50/36/32A. 50-LOW WATER CUT OFF DOES NOT PROTECT THE BOILER WHERE IT IS INSTALLED. 32A-AQUASTAT COVER PLATE IS MI... | $350 | $0 | Oct 31, 2005 |
| May 10, 2005 | 32047736J | ACTIVE | Non-Hazardous | 50/JUA/36/44C/BQ9. 50-HAZARDOUS-DISCHARGE PIPE FROM THE RELIEF VALVE IS TOUCHING THE FLOOR. 44C-LEAKING. 50A-LOW WATE... | $800 | $0 | Oct 31, 2005 |
| May 10, 2005 | 32047737L | ACTIVE | Non-Hazardous | BQ9/32A/36. BQ9-ENERJET HOT WATER BOILER BG-3 HAS NO BL WORK TYPE. 32A-CIRCULATOR PUMP/MOTOR WIRING. | $350 | $0 | Oct 31, 2005 |
| May 10, 2005 | 32047738N | ACTIVE | Non-Hazardous | BQ9/50/36. 50-LOW WATER CUT OFF DOES NOT PROTECT THE BOILER WHERE IT IS INSTALLED AT THE BOTTOM. BQ9-ENERJET BG-3 HOT... | $350 | $0 | Oct 31, 2005 |
| May 10, 2005 | 32047739P | ACTIVE | Non-Hazardous | BQ9/50/36. BQ9-ENERJET MODEL BG3 HAS NOT BL WORK TYPE. 50-LOW WATER CUT OFF DOES NOT PROTECT THE BOILER WHERE IT IS I... | $350 | $0 | Oct 31, 2005 |
| May 10, 2005 | 32047740M | ACTIVE | Non-Hazardous | BQ9/50/36. BQ9-ENERJET MODEL #BG3 HAS NO BL WORK TYPE. 50-LOW WATER CUT OFF DOES NOT PROTECT THE BOILER WHERE IT IS I... | $350 | $0 | Oct 31, 2005 |