ECB violations
77 Lexington Avenue, Brooklyn • Block 01967 • Lot 0068
42 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Feb 9, 2026 | 39176642Y | ACTIVE | CLASS - 1 | OBSERVED ON THE ROOF VENT TERMINAL NOT BEING SUPPORTED PROPERLY. ON FIRST AND SECOND FLOORS IN THE BATHROOMS NOT HAVI... | $2,500 | $0 | Apr 7, 2026 |
| Feb 9, 2026 | 39176643X | ACTIVE | CLASS - 1 | OBSERVED SLOP SINK ROOM, THERE IS NO FIRE STOP FOR THE PIPE PENETRATION THROUGH WALLS. THERE IS NO AIR GAP AT MOP SIN... | $2,500 | $0 | Apr 7, 2026 |
| Feb 9, 2026 | 39176607Z | ACTIVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. OBSERVED ON THE GROUND FLOOR MAIN ENTRANCE METAL DETECTOR/ ITEM SCAN... | $2,500 | $0 | Apr 7, 2026 |
| Feb 9, 2026 | 39176641M | ACTIVE | CLASS - 1 | OBSERVED ON THE FIRST FLOOR STORAGE ROOM AND LAUNDRY ROOM, SPRINKLER HEADS ARE OBSTRUCTED. THROUGHOUT THE BUILDING, S... | $2,500 | $0 | Apr 7, 2026 |
| Apr 10, 2025 | 39144705X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | May 8, 2025 |
| Apr 10, 2025 | 39144704Y | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING DOOR AT 1ST FLOOR E DORM ROOM. POTENTIAL FIRE HAZARD., REPAIR/R... | $625 | $0 | May 8, 2025 |
| Apr 10, 2025 | 39144706H | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED A FLEXGAS CORD ON A COMMERCIAL FIXED OVEN. POTENTIAL ... | $1,250 | $0 | May 8, 2025 |
| Sep 27, 2024 | 39125989N | RESOLVE | CLASS - 1 | ON 1ST FLOOR AT END OF HALLWAY EXIT DOOR IS LOCKED OBSTRUCTING EGRESS., REMOVE OBSTRUCTION | $1,250 | $0 | Oct 18, 2024 |
| Dec 7, 2023 | 39100940L | RESOLVE | CLASS - 2 | I OBSERVED IN DOB RECORDS NO PERMIT FOR THE INSTALLATION OF BRANCH CIRCUIT WIRING FOR THREE SPLIT UNIT A.C. UNITS ALO... | $800 | $0 | Jan 2, 2024 |
| Dec 7, 2023 | 39100939Y | RESOLVE | CLASS - 2 | I OBSERVED IN THE ROOFTOP DISCONNECT FOR THE EXHAUST FAN THE FAILURE TO INSTALL THE EQUIPMENT GROUND CONDUCTOR., PROV... | $2,400 | $0 | Jan 2, 2024 |
| Jun 1, 2023 | 39087534M | RESOLVE | CLASS - 2 | I OBSERVED IN THE SIDE YARD( EXP #2) THE INSTALLATION OF CONDUITS, WIRING AND FITTINGS TO SUPPLY POWER FOR THREE AC U... | $800 | $0 | Jun 30, 2023 |
| Jun 1, 2023 | 39087536X | RESOLVE | CLASS - 2 | I OBSERVED IN THE PARKING AREA ALONG EXP #2 THE INSTALLATION OF A.C. UNITS WITHOUT EQUIPMENT DISCONNECT SWITCHES PRIO... | $800 | $0 | Jun 30, 2023 |
| Jun 1, 2023 | 39087535Y | RESOLVE | CLASS - 2 | I OBSERVED IN THE DISCONNECT SWITCH FOR THE ROOFTOP EXHAUST FAN FAILURE TO INSTALL AN EQUIPMENT GROUNDING CONDUCTOR R... | $2,400 | $0 | Jun 30, 2023 |
| Jun 1, 2023 | 39087550M | RESOLVE | CLASS - 2 | OBSERVED IN THE KITCHEN COMMERCIAL GAS FLEX ON OVEN THAT IN NOT ON CASTERS. AS PER 411.1.1 COMMERCIAL COOKING APPLIAN... | $625 | $0 | Jun 30, 2023 |
| Mar 17, 2022 | 35644256P | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELFCLOSING.OBSERVED:FIREPROOF SELFCLOSING DOOR@1FL,CORRIDOR SMOKE DOOR NEAR MAIN ENTRANCE,SMOKE DOOR N... | $625 | $0 | Sep 7, 2022 |
| Jan 7, 2021 | 39034505Y | RESOLVE | CLASS - 2 | ROTTED WATER LINES AT BOILER. REPAIR PIPES | $625 | $0 | Jan 22, 2021 |
| Aug 2, 2019 | 39007035P | RESOLVE | CLASS - 2 | MAIN ELECTRICAL ROOM AND BOILER ROOM FIRE STOP NOT DONE, ALSO SECTIONS OF THE WALLS ARE MISSING FOR FIRE RATED CONSTR... | $0 | $0 | Aug 12, 2019 |
| Aug 2, 2019 | 39007192Z | RESOLVE | CLASS - 2 | GAS PIPING TO COMMERCIAL COOKING EQUIPMENT INCORRECTLY INSTALLED. , REPAIR AND/OR REPLACE | $0 | $0 | Aug 12, 2019 |
| Feb 11, 2019 | 35379822X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3; 27-345. NOTED: OBSERVED AT CELL... | $0 | $0 | May 20, 2019 |
| Feb 6, 2019 | 38268180K | RESOLVE | CLASS - 2 | 70O2,2B7,81Y10,68B7. 70O2-DIRTY PIT CLEAN; 2B7-OUTSIDE COMM NOT CONNECTED TO CURRENT MAINTENANCE COMPANY, PROVIDE. 81... | $0 | $0 | Jun 3, 2019 |
| Feb 6, 2019 | 32093180K | ACTIVE | CLASS - 2 | B254, 15, 32(A), 50. FOUND(WEILELAIN) MODEL #BL-788 BTUS 2,049,000 HOTWATER HEATING SYSTEM, AS PER CLASS 2 (B254) 28.... | $0 | $0 | Jul 29, 2019 |
| Sep 5, 2018 | 38265116M | RESOLVE | CLASS - 2 | 11D6,15M7,46L10. 11D6-CAR STATION NOT SECURED; 15M7-MISSING CERTIFICATE OR LOCATION IN CAR; 46L10-AMBIENT TEMPERATURE... | $0 | $0 | Dec 24, 2018 |
| Jul 20, 2018 | 35345996K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NO FIRE STOPPING PER BC 712.3,27-345 NOTED:OBSERVED THROUGHOUT ... | $0 | $0 | Jan 7, 2019 |
| Jul 20, 2018 | 35345997M | RESOLVE | CLASS - 2 | ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY AS PER 28-118.3.1-28-118.3.2-NOTED:OBSERVE... | $0 | $0 | Jan 7, 2019 |
| May 25, 2018 | 35313379Z | RESOLVE | CLASS - 1 | UNLAWFUL ACT. FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER. RECORDS INDICATE NO APPLICATION FILED TO REMOVE,CERTI... | $0 | $0 | Jul 23, 2018 |
| Mar 19, 2018 | 35313005Y | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS 35274494P AND 35289684H ISSUED ON 12/29/17 AND T... | $0 | $0 | Dec 3, 2018 |
| Jan 30, 2018 | 35298036Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3; 27-345. NOTED: OBSERVED AT CELL... | $0 | $0 | Apr 9, 2018 |
| Jan 10, 2018 | 35282834M | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #35290737K ISSUED ON 11/26/17 AND TO FILE ... | $0 | $0 | Apr 9, 2018 |
| Dec 29, 2017 | 35274494P | RESOLVE | CLASS - 1 | UNLAWFUL ACT, FAILURE TO COMPLY W/ AN ORDER OF THE COMMISSIONER. RECORDS INDICATE NO APPLICATION FILED TO CERTIFY, CO... | $0 | $0 | Jun 20, 2018 |
| Nov 26, 2017 | 35290737K | RESOLVE | CLASS - 1 | FAILURE TO MAINTIAN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 11/26/17 AT ABOVE COMMERICIAL COOLING EQUIPMENT NOT HA... | $0 | $0 | Jan 29, 2018 |
| Oct 26, 2017 | 38258836P | RESOLVE | CLASS - 2 | 11J1'39O2;42B6;40O2:CAR STATION HAS A GAP BETWEEN THE APANEL AND THE STRIKE SIDE-CLOSE GAP;CAR TOP DIRTY-CLEAN;EXPOSE... | $0 | $0 | Jan 18, 2018 |
| Aug 10, 2017 | 35289684H | RESOLVE | CLASS - 1 | UNAPPROVED, UNSAFE, UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, DEVICES, MATERIALS, APPLIANCES OR WIRING IN USE. OBSE... | $0 | $0 | Jan 3, 2018 |
| Aug 10, 2017 | 35289622M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 8/10/17@ ABOVE ADDRESS NO SPRINKLER GAUGE ON UPPER MOS... | $0 | $0 | Dec 11, 2017 |
| Aug 10, 2017 | 35272122P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING AS PER BC712.3;27-345. NOTED: AT CELLAR, IN G... | $0 | $0 | Oct 16, 2017 |
| Aug 10, 2017 | 35289621K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 8/10/17@ ABOVE ADDRESS COMMERCIAL COOLING EQUIPMENT NO... | $0 | $0 | Dec 11, 2017 |
| May 31, 2017 | 38255675J | RESOLVE | CLASS - 1 | 97X17-THE ONLY ELEVATOR IN SECTION OF BUILDING OUT OF SERVICE. UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVI... | $0 | $0 | Aug 14, 2017 |
| Mar 1, 2017 | 35234785Z | RESOLVE | CLASS - 1 | SEC: FGC 411.1. RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT. OBSERVED ON 3/1/17 @ ABOVE ADDRESS RESIDENTIAL GAS... | $0 | $0 | Mar 27, 2017 |
| Mar 1, 2017 | 35234786K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 3/1/17 @ ABOVE ADDRESS INSPECTORS TEST GAUGE NOT INSTA... | $0 | $0 | Mar 27, 2017 |
| Jul 22, 2016 | 35200997P | RESOLVE | CLASS - 2 | ALTERED/CHANGED BUILDING OCCUPIED W/O A VALID CERTIFICATE OF OCCUPANCYPER 28-118.3.2; 28-118.3.1. NOTED: BUILDING ALT... | $0 | $0 | Sep 12, 2016 |
| Sep 5, 2015 | 35141121N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER. STRAINER INSTALLED ON SPRINKLER SYSTEM IN METER ROOM-WATER SERVICE... | $0 | $0 | Oct 26, 2015 |
| Jun 17, 2015 | 38236787K | RESOLVE | CLASS - 2 | /16B11/48BB05/99M05/10H11/17H11/70Y13/39X10/34Q03/ (16B) PROVIDE DESIGNATED LOBBY BRAILLE TAGS. (48BB,99M) CAT ONE. (... | $0 | $0 | Aug 17, 2015 |
| Jul 15, 2011 | 34917430X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLAINT MANNER DEFECT IS AT REAR OF BUILDING. METAL CHAIN LINK FENCE IS IN DIS... | $0 | $0 | Aug 29, 2011 |