ECB violations
Fdny Ems Station 31, Brooklyn • Block 02039 • Lot 0101
68 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jan 28, 2026 | 39175172Y | ACTIVE | CLASS - 1 | CLASS 1 CEASE USE ORDER: IN-CAR EMERGENCY STOP SWITCH INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER S... | $1,250 | $0 | Feb 6, 2026 |
| Oct 1, 2024 | 39126356H | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED EXCESSIVE CRACKS ON ROOF IN MECHANICAL ROOM AND BASEM... | $1,250 | $0 | Jan 2, 2025 |
| Oct 1, 2024 | 39126355X | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Oct 18, 2024 |
| Oct 1, 2024 | 39126371X | ACTIVE | CLASS - 2 | OBSERVED SPRINKLER MAIN NOT PAINTED RED IN THE BOILER ROOM. AS PER 903.6.2 OF THE BUILDING CODE ALTERATIONS. CROSS CO... | $625 | $0 | Oct 18, 2024 |
| Dec 29, 2022 | 39076601J | ACTIVE | CLASS - 1 | DEVICE WAS FOUND OUT OF SERVICE RESTORE TO SERVICE IMMEDIATELY. YOU CAN CONTACT NYCDOB AT EIR@BUILDINGS.NYC.GOV FOR A... | $1,250 | $0 | Jan 10, 2023 |
| Dec 2, 2022 | 37023903N | ACTIVE | CLASS - 2 | FAILURE TO SUBMIT ACCEPTABLE REQUIRED CYCLE8A,9A REPORT OF CRITICAL EXAM DOCUMENTING CONDITION OF EXTERIOR WALL&APPUR... | $1,250 | $0 | Feb 8, 2023 |
| Dec 1, 2022 | 39076602L | ACTIVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $3,125 | $0 | Jan 10, 2023 |
| Feb 2, 2022 | 35640340J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE/WALLS AND APPURTENANCES.NOTE:AT TIME OF INSPECTION OBSERVED SAME CONDITI... | $6,250 | $0 | Jun 15, 2022 |
| Dec 8, 2021 | 35635149P | ACTIVE | CLASS - 3 | FAILURE TO POST EXTERIOR BUILDING WALL CONDITION CERTIFICATE AS REQUIRED UNDER 1RCNY103-04(F)AS NOTED:AT TIME OF INSP... | $500 | $0 | May 4, 2022 |
| Dec 8, 2021 | 35635148N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN EXTERIOR BUILDING WALLS AND APPURTENANCES.AS NOTED:AT TIME OF INSPECTION OBSERVED AT EXP #1 SOUTH... | $2,500 | $0 | May 4, 2022 |
| Nov 17, 2021 | 39051307H | ACTIVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $1,250 | $0 | Dec 14, 2021 |
| Nov 17, 2021 | 39051309L | ACTIVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $1,250 | $0 | Dec 14, 2021 |
| Aug 17, 2021 | 39046125K | RESOLVE | CLASS - 2 | NOTED: BUILDING FULLY OCCUPIED AS A HOMELESS SHELTER UNDER AN EXPIRED TEMPORARY CERTIFICATE OF OCCUPANCY. RE: T.C.O. ... | $3,125 | $0 | Sep 14, 2021 |
| Sep 4, 2019 | 38271306Y | RESOLVE | CLASS - 2 | (16R9/400M7)16R9-ILLEGAL VESTIBULE ON THE 8TH FLOOR.40M7-NO ACCESS TO MACHINE ROOM CONTROL SPACE KEYS MISSINGS. | $625 | $0 | Jan 22, 2020 |
| Mar 4, 2019 | 35383805X | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NOTED:OBSERVED AT SOUTHWEST CORNER OF CELLAR WATER PENETRATING... | $0 | $0 | Jul 1, 2019 |
| Mar 4, 2019 | 35383806H | RESOLVE | CLASS - 2 | ALTERED/CHANGED BUILDING OCCUPIED W/O A VALID CERTIFICATE OF OCCUPANCYAS PER 28-118.3.1, 28-118.3.2 NOTED: BUILDING O... | $0 | $0 | Jul 1, 2019 |
| Dec 27, 2018 | 38267089P | RESOLVE | CLASS - 1 | 68M7,97X10. 68M7-MAINTENANCE LOG MISSING; 97X10-UPON INSPECTION DEVICE WAS FOUND OUT OF SERVICE. RESTORE TO SERVICE I... | $0 | $0 | Jun 3, 2019 |
| Dec 21, 2018 | 38266866X | RESOLVE | CLASS - 1 | (CEASE USE):97-R-##;WORK WITHOUT PERMIT.DEVICE #3P6211 BEING USED TO PROVIDE TRANSPORATION FOR CONSTRUCTING PERSONNEL... | $0 | $0 | May 6, 2019 |
| Sep 5, 2018 | 38265118X | RESOLVE | CLASS - 2 | 97B7 UNSAFE IMPROPER USE OF ELEVATOR IS BEING USED FOR CONSTRUCTION W/O A CONSTRUCTION TEMP. | $0 | $0 | Dec 24, 2018 |
| Sep 5, 2018 | 38265117Y | RESOLVE | CLASS - 2 | 32H10,32H10. 32H10-BAD ROLLER ON TOP OF CAR SHAKING AS ELEVATOR RUN UP AND DOWN. 32H10- BAD ROLLER ON COUNTERWEIGHT. | $0 | $0 | Dec 24, 2018 |
| May 18, 2018 | 37010188K | ACTIVE | CLASS - 2 | FAILURE TO SUBMIT ACCEPTABLE 8TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS & APPUR... | $0 | $0 | Sep 10, 2018 |
| Feb 15, 2018 | 35298046H | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: INTERIOR. NOTED: OBSERVED @ CELLAR SOUTH WEST CORNER & SOUTH OF ST... | $0 | $0 | Apr 23, 2018 |
| Feb 15, 2018 | 35298047J | RESOLVE | CLASS - 2 | ALTERED/CHANGED BLDG OCCUPIED W/OUT A VALID C OF O AS PER 28-118.3.1, 28-118.3.2. NOTED: BLDG OCCUPIED AS SHELTER UND... | $0 | $0 | Apr 23, 2018 |
| Oct 10, 2017 | 38258416Z | RESOLVE | CLASS - 1 | 5X10 DOOR RESTRICTOR INOPERATIVE,REPAIR. | $0 | $0 | Dec 11, 2017 |
| Oct 10, 2017 | 38258414P | RESOLVE | CLASS - 2 | 44Y13,56Y2,52O2 TRACTION SHOWER LEAKING OIL SEAL. 56Y2 HOIST MACHINELEAKING OIL,SEAL 52O2 HOIST ROPES OILY CLEAN | $0 | $0 | Dec 11, 2017 |
| Oct 10, 2017 | 38258415R | RESOLVE | CLASS - 1 | 5X10 | $0 | $0 | Dec 11, 2017 |
| Oct 10, 2017 | 38258418M | RESOLVE | CLASS - 2 | 97R## WORK WITHOUT A PERMIT DEVICE # 3P6211 BEING USED TO PROVIDE TRANSPORTATION FOR CONSTRUCTION PERSONNEL TOOLS AND... | $0 | $0 | Dec 11, 2017 |
| Oct 10, 2017 | 38258417K | RESOLVE | CLASS - 2 | 44Y13, 52,O2, 39O2, 59M7 44,Y,13 TRACTION SHOWER LEAKING OIL ,SEAL 52O2 HOIST ROPES ONLY,CLEAN 39O2 CAR TOP OILY CLEA... | $0 | $0 | Dec 11, 2017 |
| Jul 27, 2017 | 38256243K | RESOLVE | CLASS - 2 | 10M11,1B11,19B11,17M11,18M7,41D7,56Y2,59X11,59X10 (17M11)ALL FLOORS;( 18M7)5 FLOOR, ECCENTRIC;(59X11 ON 10)BRAKE SWITCH | $0 | $0 | Oct 23, 2017 |
| Apr 6, 2017 | 38254009N | RESOLVE | CLASS - 2 | 70O2, 71X10, 80M7, 39O2, 39Q3, 56Y13, 59M7, 56O2, 67P7. 39.Q.3-PROVIDE GUARD FOR TOP OF CAR LIGHT. 59.M.7-PROVIDE BRA... | $0 | $0 | May 15, 2017 |
| Mar 9, 2017 | 35235127L | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 3/09/17IN THE CAFETERIA ROOM ON THE FIRST FL SPRINKLER... | $0 | $0 | May 8, 2017 |
| Mar 9, 2017 | 35235128N | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 3/9.17 JIM CAPS BEING USED THROUGHOUT BSMT MUST BE HAN... | $0 | $0 | May 8, 2017 |
| Dec 6, 2016 | 38251752X | RESOLVE | CLASS - 1 | 97X10 | $0 | $0 | Jan 23, 2017 |
| Oct 27, 2016 | 38250584L | RESOLVE | CLASS - 1 | 97X10. ONE OF TWO DEVICES IN A DHS FACILITY OUT OF SERVICE.THIS IS A HAZARDOUS CONDITION, INCLUDING THOSE WITH SPECIA... | $0 | $0 | Jan 23, 2017 |
| Oct 27, 2016 | 38250585N | RESOLVE | CLASS - 1 | 97X10 ONE OF TWO DEVICES IN A DHS FACILITY OUT OF SERVICE. THIS CONDITION AFFECTS NUMEROUS CLIENTS, INCLUDING THOSE W... | $0 | $0 | Jan 23, 2017 |
| Oct 18, 2016 | 38250553Z | RESOLVE | CLASS - 1 | CU 30X10,05X10,59M07,52Y02,03M07,56B07,10M11,05H10 30-X-10 BOTTOM NORAL AND FINAL INOPERATIVE REPAIR.05-X-10ZONE REST... | $0 | $0 | Dec 5, 2016 |
| Oct 14, 2016 | 38250184M | RESOLVE | CLASS - 1 | 05X10,05B01,39O02,52O02,52H11,53O02,56Y10,56Y13,59M07,59U15,100L10,100L10. 05X-REPAIR DOOR ZONE LOCK; 05B-ADJUST CAB ... | $0 | $0 | Jan 23, 2017 |
| Aug 19, 2016 | 38244873R | RESOLVE | CLASS - 1 | 05A10,59U15. 05-ZONE RESTRICTOR ALTERED/INOPERATIVE; 59-NO BRAKE SERV ICE PERFORMED. | $2,500 | $0 | Mar 1, 2017 |
| Aug 19, 2016 | 38244862L | RESOLVE | CLASS - 1 | 05A10,56Y13,59U15,52O02,39O02,97X10. 05-ELEVATOR COMPANY ALTERED CAB DOOR ZONE RESTRICTOR; INOPERATIVE; 56-OIL LEAK M... | $2,500 | $0 | Oct 3, 2016 |
| Aug 4, 2016 | 35200754K | RESOLVE | CLASS - 2 | ALTERED/CHANGED BUILDING OCCUPIED W/OUT A VALID CERTIFICATE OF OCCUPANCY PER 28-118.3.1 AND 28-118.3.2 NOTED: EXPIRED... | $0 | $0 | Sep 12, 2016 |
| Jul 13, 2015 | 38237644H | RESOLVE | CLASS - 2 | /67X10/05X10/98BB05/59I10/70O02/06B01/ 67X10-REPAIR EMERGENCY PHONE. 05X10-REPAIR DOOR ZONE LOCK. 59I10-GREENFIELD GO... | $0 | $0 | Aug 17, 2015 |
| Jul 13, 2015 | 38238212Z | RESOLVE | CLASS - 2 | /56Y13/59Y02/40Y02/61G11/98BB05/17H10/17D06/39Y02/37Y02/70O02/10H11/ (56Y) SEAL LEAKS. (59Y) CLEAN DRUM. (61G) UNREAD... | $0 | $0 | Aug 17, 2015 |
| Apr 22, 2014 | 35091526Z | RESOLVE | CLASS - 2 | OPERATION OF A PLACE OF ASSEMBLY WITHOUT A PA PERMIT. NOTED: AT 2ND FLOOR CAFETERIA HAVING SET-UP/LAYOUT ACCOMMODATIN... | $0 | $0 | Jun 16, 2014 |
| Apr 22, 2014 | 35038846P | RESOLVE | CLASS - 2 | UNAPPROVED UNSAFE UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS MATERIALS DEVICES APPLIANCES OR WIRING IN USE.ON 04/22/14... | $0 | $0 | Jun 23, 2014 |
| Apr 22, 2014 | 35091525R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG. NOTED: AT 8TH FLOOR ELEVATOR ELETRICAL ROOM. OBSERVED SEVERE SPALLING OF MORTAR. & ALSO FOU... | $0 | $0 | Jun 16, 2014 |
| Apr 22, 2014 | 35091527K | RESOLVE | CLASS - 2 | WORK WITHOUT A PERMIT. NOTED: AT 8TH FLOOR ELEVATOR ELECTRICAL ROOM, FOUND NEW PLYWOOD/SHEETROCK PARTITION APPROX 10'... | $0 | $0 | Jun 16, 2014 |
| Jan 23, 2012 | 38220131L | RESOLVE | CLASS - 3 | 42I10,59H11,59M07. 42I- COVER CONTROLLER FROM FALLING CEILING. 59H- WORN BRAKE PADS. 59M- COVER BAKE SW. | $0 | $0 | Mar 12, 2012 |
| Jan 23, 2012 | 38220130J | RESOLVE | CLASS - 3 | 42B09,56Y13,24X10,03N10. 42B- WIRES COMING OUT OF CONTROLLER. 24X- FLRINDICATORS IN CAR INOPERABLE. 03N - CAR TAKES C... | $0 | $0 | Mar 12, 2012 |
| Jan 27, 2010 | 36012454R | ACTIVE | CLASS - 2 | FAILURE TO FILE AN ARCHITECT/ENGINEER REPORT CERTIFYING EXIT/DIRECTIONAL SIGNS ARE CONNECTED TO EMERGENCY POWER SOURC... | $0 | $0 | Aug 2, 2010 |
| Mar 12, 2007 | 38165005L | RESOLVE | Non-Hazardous | 17L10,10H11,03M11,15M11.(17)REPAIR HOISTWAY DOOR GIBS @ 7TH FL.(10)REPLACE CAR DOOR GIBS.(03)REPLACE HAND RAIL IN CAR... | $0 | $0 | May 7, 2007 |