ECB violations
194-200 Tillary Street, Brooklyn • Block 02050 • Lot 0104
111 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 13, 2020 | 38273128J | RESOLVE | CLASS - 1 | 97X17 UPON INSPECTION ENTIRE DEVICE WAS FOUND TO BE OUT OF SERVICE.RESTORE TO SERVICE IMMEDIATELY AND CONTACT DOB FOR... | $3,155 | $0 | Aug 19, 2020 |
| Mar 3, 2020 | 39018768X | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $1,250 | $0 | Jul 8, 2020 |
| Mar 3, 2020 | 39018769H | RESOLVE | CLASS - 1 | UPON INSPECTION DEVICE WAS FOUND TO BE OUT OF SERVICE. THIS IS THE ONLY ELEVATOR IN THE SECTION OF THE BUILDING. REST... | $1,280 | $0 | Jul 8, 2020 |
| Feb 4, 2020 | 39016817Y | RESOLVE | CLASS - 1 | UPON INSPECTION ONLY ELEVATOR IN THE SECTION OF BUILDING OUT OF SERVICE. RESSTORE TO SERVICE IMMEDIATELY AND CONTACT ... | $1,250 | $0 | Jun 10, 2020 |
| Jan 17, 2020 | 39015996Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER, I OBSERVED AT THE ABOVE ADDRESS IN BASEMENT 3 GAS METERS. NO V... | $781 | -$781 | Dec 31, 2020 |
| Dec 2, 2019 | 38272433L | RESOLVE | CLASS - 1 | 97X17: (97,X,17) UPON INSPECTION THE ONLY ELEVATOR IN THE SECTION OF THIS BUILDING WAS FOUND TO BE OUT OF SERVICE. RE... | $1,280 | $0 | Mar 22, 2021 |
| Sep 20, 2019 | 35447757K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER. OBSERVED IN CELLAR NO VENTILATION FOR GAS METERS INSTALLATION. R... | $625 | $0 | Feb 12, 2020 |
| Jul 12, 2019 | 39005433L | RESOLVE | CLASS - 1 | I OBSERVED IN BASEMENT NO VENTILATION FOR ROTARY METERS IN THE GAS METER ROOM, ALSO EXCESSIVE STORAGE BY THE SECOND R... | $1,280 | $0 | Nov 2, 2020 |
| May 30, 2019 | 38269487J | RESOLVE | CLASS - 1 | 97X10 UPON INSPECTION DEVICE WAS FOUND OUT OF SERVICE. THIS IS THE ONLY ELEVATOR IN THIS SECTION OF THE BUILDING. RES... | $1,250 | $0 | Sep 16, 2019 |
| May 7, 2019 | 38268048N | RESOLVE | CLASS - 1 | CU05X17,11I10,34B07. 05X17-DOOR ZONE RESTRICTOR IS TIED UP; 11I10- DOOR OPEN BUTTON IS DAMAGED; 34B07-PROVIDE AN EXTR... | $1,250 | $0 | Aug 21, 2019 |
| Feb 12, 2019 | 38268258L | RESOLVE | CLASS - 1 | 42D6,42M7. 42D6-WIRES ON THE CONTROLLER TERMINAL OT SECURED. UNSECURED WIRES CAME OUT AND SHUT THE ELEVATOR DOWN. REP... | $1,250 | $0 | Sep 25, 2019 |
| Feb 12, 2019 | 38268257J | RESOLVE | CLASS - 1 | 16B7, CU17M7; CU59B10; 68B7. 16B7-HOISTWAY DOOR MISSING SPRING ONT HESPRING CLOSER; 17M7-MISSING GIBS 5 FLOOR HOISTWA... | $1,250 | $0 | Sep 23, 2019 |
| Jan 22, 2019 | 35381109N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER. OBSERVED ON THE ROOF FOUR OUT OF FIVE BOILERS BEING USED FOR... | $1,250 | $0 | Aug 19, 2019 |
| Jan 22, 2019 | 35383600M | RESOLVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE. OBSERVED I... | $1,600 | $0 | Aug 21, 2019 |
| Jan 22, 2019 | 35383601Y | RESOLVE | CLASS - 2 | ELECTRICAL WORK W/O A PERMIT. OBSERVED IN LAUNDRY ROOM THE INSTALLATION OF A "SQUARE D" TYPE PANEL W/ BRANCH CIRCUIT ... | $800 | $0 | Aug 21, 2019 |
| Jan 22, 2019 | 35383603H | RESOLVE | CLASS - 3 | FAILURE TO PROVIDE REQUIRED CIRCUIT DIRECTORY/IDENTIFICATION. OBSERVEDTHROUGHOUT BUILDING CIRCUIT BREAKER PANELS W/ P... | $0 | $0 | Apr 29, 2019 |
| Jan 22, 2019 | 35383602X | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE GROUND FAULT CIRCUIT INTERRUPTOR(GFCI) PROTECTION AS REQUIRED. OBSERVED IN 5TH FL LOUNGE-RESTROOM,... | $6,000 | $0 | Aug 21, 2019 |
| Dec 17, 2018 | 37013917P | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35311869M ISSUED ON 02-15-18 & TO FILE A C OF C PURSUAN... | $1,250 | $0 | Oct 21, 2019 |
| Dec 17, 2018 | 37013914J | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35311359M ISSUED ON 02-15-18 & TO FILE A C OF C PURSUAN... | $625 | $0 | Oct 21, 2019 |
| Oct 18, 2018 | 38265988J | RESOLVE | CLASS - 1 | CU6B7 DOOR POSITION MONITORING DOES NOT WORK CODE DATA TAG 2000/03; 70Z9CU-PIT INSTALLED WITH WATER AND TRAVELING CAB... | $1,250 | $0 | Apr 8, 2019 |
| Oct 18, 2018 | 38265987H | RESOLVE | CLASS - 1 | 5A10,29M7. 5A10-DOOR ZONE RESTRICTOR NOT WORKING REAR DOOR NEEDS TO BE ADJUSTED. THIS IS A SAFETY DEVICE TO ENSURE PA... | $1,250 | $0 | Jan 7, 2019 |
| Sep 10, 2018 | 35305941R | RESOLVE | CLASS - 2 | RESPONDENT FAILED TO PROPERTY NOTIFY DEPARTMENT OF OR MOBILE CRANE AFTER 05/01/2018 AT TIME OF INSPECTION NO CRANE ON... | $2,500 | $0 | Dec 24, 2018 |
| Aug 28, 2018 | 38265104P | RESOLVE | CLASS - 1 | 6.B.10,70.Z.9-(6,B,10)DOOR POSITION MONITORING DID NOT WORK CODE DATA TAG 2000/03 (70,Z,9)REMOVE WATER FROM PIT | $1,250 | $0 | Feb 4, 2019 |
| Aug 8, 2018 | 35316327K | RESOLVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT APPARTUS,MATERIALS,DEVICES,APPLIANCES OR WIRING METHOD IN USE.I OBS... | $400 | $0 | Feb 20, 2019 |
| Aug 8, 2018 | 35316326Z | RESOLVE | CLASS - 2 | ELECTRICAL WORK WITHOUT A PERMIT.I OBSERVED ON THE 5TH FLOOR OUTSIDE THE REC ROOM,ON THE 6TH FLOOR OUTSIDE THE EXIT A... | $400 | $0 | Feb 20, 2019 |
| Mar 27, 2018 | 35326388N | RESOLVE | CLASS - 2 | WORK W/O A PERMIT. OBSERVED 1ST FL IN(DOMITARY BALL DROP)INSTALLED ON F.D. CONNECTION W/O A PERMIT. REMEDY: OBTAIN AL... | $500 | $0 | Jun 5, 2019 |
| Feb 15, 2018 | 35311868K | RESOLVE | CLASS - 2 | FAILURE TO INSTALL GROUND FAULT CIRCUIT INTERRUPTER (GFCI) PROTECTION AS REQUIRED. OBSERVED THE FOLLOWING VIOLATING C... | $1,200 | $0 | Jun 4, 2018 |
| Feb 15, 2018 | 35312068R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON THE DAY OF 02/15/2018 LEAK ON PIPING TO COOLING TOW... | $500 | $0 | Jul 23, 2018 |
| Feb 15, 2018 | 35311360J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3; 27-345. NOTED: HOLES IN WALL ST... | $500 | $0 | Jun 4, 2018 |
| Feb 15, 2018 | 35311359M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: UTILITY CLOSET IN ROOM 602 PART OF CEILING IS FALLING, ... | $500 | $0 | Apr 9, 2018 |
| Feb 15, 2018 | 35311869M | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE/MAINTAIN SUFFICIENT ACCESS/WORK SPACE ABOUT ELECTRICAL EQUIPMENT. OBSERVED THE FOLLOWING VIOLATING... | $500 | $0 | Apr 9, 2018 |
| Jan 18, 2018 | 35297846L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER. PREVIOUS SUMMONS#35296708Z WAS ISSUED ON 8-1-17 FOR THE FOLLOWIN... | $1,000 | $0 | Mar 19, 2018 |
| Oct 20, 2017 | 38258830Y | RESOLVE | CLASS - 1 | 5X10;42G7;68M7/(5X10)DOOR RESTRICTOR HAS BEEN ALTERED OR TAMPERED WITHINOPERATIVE THIS DEVICE IS TO ENSURE THE SAFETY... | $1,000 | $0 | Feb 22, 2018 |
| Aug 1, 2017 | 35287425Y | RESOLVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,MATERIALS APPARATUS,DEVICES,APPLIANCE OR WIRING IN USE. OBSERVED EM... | $800 | $0 | Dec 13, 2017 |
| Aug 1, 2017 | 35287426X | RESOLVE | CLASS - 2 | FAILURE TO INSTALL(GFCI)GROUND FAULT CIRCUIT INTERRUPTER PROTECTION ASREQUIRED. OBSERVED RECEPTACLE OUTLETS NOT OF TH... | $2,400 | $0 | Dec 4, 2017 |
| Aug 1, 2017 | 35287252P | RESOLVE | CLASS - 1 | FGC 408.2. MISC VIOLATION FUTURE CONNECTIONS EXSIST ON GAS PIPING.OBSERVE IN CELLAR WHERE GAS METERS (2) ARE LOCATED ... | $4,000 | $0 | Feb 26, 2018 |
| Aug 1, 2017 | 35287253R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED AT SEVERAL LOCATIONS IN CELLAR JIM CAPS INSTALLED ON T... | $1,250 | $0 | Mar 2, 2018 |
| Aug 1, 2017 | 35296708Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUIDING IN A CODE COMPLIANT MANNER.OBSERVED CHECK VALVE FOR STANDPIPE FD CONNECTION ON PRINCE ST.... | $1,000 | $0 | Mar 19, 2018 |
| Aug 1, 2017 | 35287518N | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE GROUND FAULT CIRCUIT INTERRUPTOR(GFCI)PROTECTION ASREQUIRED.OBSERVED RECEPTACLE OUTLETS IN LAUNDRY... | $2,400 | $0 | Nov 20, 2017 |
| Aug 1, 2017 | 35287428J | RESOLVE | CLASS - 1 | UNAPPROVED,UNSAFE,UNSUITABLE ELECTRICAL EQUIPMENT MATERIALS,APPARATUS,DEVICE,APPLIANCE OR WIRING IN USE. OBSERVED ELE... | $1,600 | $0 | Nov 8, 2017 |
| Aug 1, 2017 | 35287429L | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE(GFCI)GROUND FAULT CIRCUIT INTERRUPTER PROTECTION AS REQUIRED. OBSERVED RECEPTACVLE OUTLETS IN LAUN... | $0 | $0 | Sep 1, 2017 |
| Aug 1, 2017 | 35287427H | RESOLVE | CLASS - 1 | FAILURE TO PROTECT TEMPORARY WIRING FROM IMPROPER CONTACT. OBSERVED 3 PANEL ON ROOFTOP TEMP WIRE WAS INSTALLED FROM E... | $1,600 | $0 | Nov 6, 2017 |
| Apr 10, 2017 | 38250469X | RESOLVE | CLASS - 2 | 2X10,56L10,68B07,70C7. 2X-REPAIR ALARM BELL; 56L-PROVIDE MISSING CLIPON BRAKE PIN; 68B-PROVIDE INFO IN LOG, PROVIDE M... | $500 | $0 | Jun 5, 2017 |
| Mar 9, 2017 | 38253733J | RESOLVE | CLASS - 1 | 5A10-CEASE USE ITEM DOOR ZONE RESTRICTOR HAS BEEN TAMPERED WITH DISABLED RENDERED INOPERATIVE. THIS IS A SAFETY DEVIC... | $5,000 | $0 | Apr 24, 2017 |
| Mar 2, 2017 | 35234784R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED ON 3/2/2017 AT ABOVE ADDRESS FERNCO COUPLINGS AND ALS... | $500 | $0 | Oct 18, 2017 |
| Mar 2, 2017 | 35234783P | RESOLVE | CLASS - 1 | DRIPS FUTURE CONNECTIONS EXIST DOWN STREAM OF APPLIANCE. OBSERVED ON 03/02/17 AT ABOVE ADDRESS FUTURE GAS CONNECTIONS... | $1,600 | $0 | Oct 4, 2017 |
| Feb 28, 2017 | 38253438R | RESOLVE | CLASS - 2 | 5L10,39D10,41N11,68M7,100M7,70O2. 5L10-DOOR RESTORER DEFECTIVE-REPAIR39D10-TOP CAR ALARM BELL UNSECURED, REPAIR; 42N1... | $0 | $0 | Apr 17, 2017 |
| Jun 14, 2016 | 35181046Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED PER BC903.... | $1,000 | $0 | Dec 7, 2016 |
| Mar 25, 2016 | 35177271N | RESOLVE | CLASS - 2 | WORK W/O A PERMIT. WORK NOTED: AT 2ND FL LEVEL INSTALLED GAS LINES FOR COMMERCIAL STOVE & DEEP FRYER AT KITCHEN. REME... | $0 | $0 | Apr 15, 2016 |
| Jan 7, 2016 | 35168158R | RESOLVE | CLASS - 2 | SEC. 3307.6.5 FAILURE TO MAINTAIN SIDEWALK SHED AS REQUIRED BY CODE. NOTED: AT TIME OF INSPECTION,SIDEWALK SHED ERECT... | $0 | $0 | Feb 29, 2016 |