ECB violations
Albert J Parham Playground, Brooklyn • Block 02091 • Lot 0003
111 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Feb 6, 2026 | 35728802L | ACTIVE | CLASS - 2 | 28-301.1. RE-ISSUED 3569188Y. FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE), FGC APPENDIX E(... | $3,125 | $0 | Mar 5, 2026 |
| Feb 6, 2026 | 35728806Z | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27-371... | $1,250 | $0 | Mar 5, 2026 |
| Feb 6, 2026 | 35728804P | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS P... | $1,250 | $0 | Mar 5, 2026 |
| Feb 6, 2026 | 35728805R | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION, THE FOLLOWING ROOM DOORS WERE NOT S... | $1,250 | $0 | Mar 5, 2026 |
| Feb 6, 2026 | 35728803N | ACTIVE | CLASS - 2 | RE-ISSUED 35691881M. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION, ELECTRICAL MET... | $3,125 | $0 | Mar 5, 2026 |
| Mar 19, 2025 | 35691882Y | ACTIVE | CLASS - 2 | 28-301.1. REISSUE: 35672435Z-CELLAR LEVEL BOILER ROOM. THE LEVERS FOR AIR HAS BEEN BOARDED UP. AIR VENTS FOR GAS METE... | $3,125 | $0 | Apr 23, 2025 |
| Mar 19, 2025 | 35691881M | ACTIVE | CLASS - 2 | REISSUE #35672432N-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: CELLAR ELECTRICAL ROOM HAS SPALLING ON WALL... | $3,125 | $0 | Apr 23, 2025 |
| Feb 8, 2024 | 35672434R | RESOLVE | CLASS - 2 | REISSUE: 35671809J-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: RM #130 ON 1ST FLOOR DOOR NOT CLOSING PROPE... | $1,562 | $0 | Apr 22, 2024 |
| Feb 8, 2024 | 35672432N | ACTIVE | CLASS - 1 | REISSUE: 35671813M-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: (CELLAR LEVEL ELECTRICAL ROOM, CEILING WALL... | $3,125 | $0 | Apr 22, 2024 |
| Feb 8, 2024 | 35672433P | RESOLVE | CLASS - 2 | REISSUE: 35671810R-EXIT DOOR NOT SELF CLOSING: NOTED ON 3RD FLOOR STAIRS A, B 2ND FL. #A EXIT 7,2,3 EXIT DOOR, NOT CL... | $1,562 | $0 | Apr 22, 2024 |
| Feb 6, 2024 | 35672435Z | ACTIVE | CLASS - 2 | 28-301.1. REISSUE: 3565093Y-CELLAR LEVEL BOILER ROOM. THE LEVEL NEXT TO GAS METER HAVE BEEN REMOVED AND BOARDED UP. R... | $3,125 | $0 | Apr 22, 2024 |
| Feb 2, 2023 | 35671809J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED THE CHANGING ROOM(130)ON 1ST FLOOR LEVEL DOOR IS NOT WORK... | $625 | $0 | May 10, 2023 |
| Feb 2, 2023 | 35671813M | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED AT CELLAR LEVEL ELECTRICAL METER ROOM CEILING AND OIL BOI... | $625 | $0 | May 10, 2023 |
| Feb 2, 2023 | 35671811Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.ILLUMINATION FOREXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER ... | $625 | $0 | May 10, 2023 |
| Feb 2, 2023 | 35671812K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED AT THE OUTSIDE OF EXIT 2,THE MASONRY STEPS ARE MISSING MO... | $625 | $0 | May 10, 2023 |
| Feb 2, 2023 | 35671808H | ACTIVE | CLASS - 2 | REISSUE#35650693Y.NOTED AT CELLAR LEVEL BOILER ROOM,THE LEVERS NEXT TOI THE GAS METER HAVE BEEN REMOVED AND BOARDED U... | $3,125 | $0 | May 10, 2023 |
| Feb 2, 2023 | 35671810R | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING.NOTED ON 3RD FLOOR STAIR A AND B,2ND FLOOR STAIR A,SMOKE BY EXIT#2,3,7,AND 8,EXTERIOR DOOR... | $625 | $0 | May 10, 2023 |
| Mar 30, 2022 | 35650692M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTED OBSERVED AT EXIT #2 EXTERIOR STAIRS RIGHT SIDE MISSING HA... | $625 | $0 | Sep 14, 2022 |
| Mar 30, 2022 | 35650690Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTED OBSERVED FIRE PROOF SELF CLOSING DOORS (FPSC) 3RD FLOOR S... | $625 | $0 | Sep 14, 2022 |
| Mar 30, 2022 | 35650688J | RESOLVE | CLASS - 2 | REISSUED35557763Y FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES&PUBLIC CORR... | $1,562 | $0 | Sep 14, 2022 |
| Mar 30, 2022 | 35650693Y | ACTIVE | CLASS - 2 | 28-301.1 FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P.115.6 (1968 CODE) FG+C APPENDIX E(E4)(2014 CODE)NOTED... | $1,250 | $0 | Sep 14, 2022 |
| Mar 30, 2022 | 35650689L | RESOLVE | CLASS - 2 | REISSUED35557761K FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:NOTED:OBSERVED@STAIR"A" BULKHEAD,SPALLING PLASTER ... | $1,562 | $0 | Sep 14, 2022 |
| Mar 30, 2022 | 35650691K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTED OBSERVED EXTERIOR STAIRS AT EXIT #2 MISSING MORTAR BETWEE... | $625 | $0 | Sep 14, 2022 |
| Apr 22, 2021 | 35557760Z | RESOLVE | CLASS - 2 | REISSUE35495523Y FAILUE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.NOTED:OBSERVED 1OF THE MAIN ENTRANCE DOORS ISNT CLOS... | $1,562 | $0 | Sep 22, 2021 |
| Apr 22, 2021 | 35557762M | RESOLVE | CLASS - 2 | REISSUE35495521K FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES.NOTED:@CELLAR LEVEL ON ADELPHIST SIDE,IN ELECTRICA... | $3,125 | $0 | Sep 22, 2021 |
| Apr 22, 2021 | 35557759L | RESOLVE | CLASS - 2 | REISSUE35498540J EXIT DOOR NOT SELFCLOSING NOTED:OBSERVED THRUOUT BLDGMOST DOORS WERENT OPENING&CLOSING PROPERLY.REPA... | $1,562 | $0 | Sep 22, 2021 |
| Apr 22, 2021 | 35557763Y | RESOLVE | CLASS - 2 | REISSUE35495520Z FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES&PUBLIC CORRI... | $1,562 | $0 | Sep 22, 2021 |
| Apr 22, 2021 | 35557761K | RESOLVE | CLASS - 2 | REISSUE35495522M FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.NOTED:@BULKHEADA THERES A LEAK IN THE WALL.REPAIR &... | $1,562 | $0 | Sep 22, 2021 |
| Feb 6, 2021 | 35454554X | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT. AT TIME OF INSPECTION I OBSERVED AT REAR OF SCHOOL YARD A TEMPORARY W... | $500 | $0 | Jun 9, 2021 |
| Sep 1, 2020 | 35498540J | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING NOTE AT TIME OF INSPECTION OBSERVED TRHOUGHOUT THE ENTIR EBUILDING AND ALL FLOORS THERE AR... | $625 | $0 | Jan 13, 2021 |
| May 15, 2020 | 35495522M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: ROOF LEAK ATBULKHEAD'A',CLASSROOM 317,318,306,304,310,AT 3R... | $625 | $0 | Feb 24, 2021 |
| May 15, 2020 | 35495520Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER ILLIMINATION. NOTED:EMERGENCY EXIT LIGHTING OBSERVED INOPERATIVE WH... | $625 | $0 | Feb 24, 2021 |
| May 15, 2020 | 35495521K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: AT CELLAR,FOUNDATION WALL AT ADELPHI STREET SIDE HAVE BECOME ... | $1,250 | $0 | Feb 24, 2021 |
| May 15, 2020 | 35495523Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: AT MAIN ENTRANCE,ONE OF THREEE INTERIOR DOOR DON'T CLOSE PR... | $625 | $0 | Feb 24, 2021 |
| Apr 26, 2019 | 35415593R | RESOLVE | CLASS - 2 | REISSUED 35330840M FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER 115.6(1968 CODE) FGC APPENDIX E(E4)(2014 CODE... | $0 | $0 | Aug 19, 2019 |
| Apr 26, 2019 | 35415594Z | RESOLVE | CLASS - 2 | 28-301.1 UNLAWFUL DISPLAY OF ARTWORK IN CORRIDORS GREATER THAN 20% PERFDNY 2008 CODE FC 803.2. NOTE ARTWORK DISPLAYED... | $0 | $0 | Aug 19, 2019 |
| Apr 26, 2019 | 35415595K | RESOLVE | CLASS - 2 | 28-301.1 FAILURE TO PROVIDE NATURAL OR MECHANICAL VENTILATION TO OCCUPIED SPACES PER MC 401.2. NOTE AT BASEMENT LEVEL... | $0 | $0 | Aug 19, 2019 |
| Apr 26, 2019 | 35415597Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ILLUMINATION FOREXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER ... | $0 | $0 | Aug 19, 2019 |
| Apr 26, 2019 | 35415598X | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING. NOTE AT EXIT C 1ST FLOOR DOOR LEADING TO EXITS ON RIGHT HAND SIDE MISSING CLOSURE. REMEDY... | $0 | $0 | Aug 19, 2019 |
| Apr 26, 2019 | 35415596M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER USE OF PROHIBITED DOOR AND OR HARDWARE PER BC 1008.8;27-371(J).... | $0 | $0 | Aug 19, 2019 |
| May 1, 2018 | 35330846N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT 2ND & 3RD FLR PUBLIC HALLWAYS AND STAIRCASE/EXIT 7 OBS... | $0 | $0 | Jul 30, 2018 |
| May 1, 2018 | 35330845L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.LACK OF EMERGENCY LIGHTING FOR EXITS,EXIT DISCHARGES AND PUBLIC... | $0 | $0 | Jul 30, 2018 |
| May 1, 2018 | 35330840M | RESOLVE | CLASS - 2 | BC28-301.1/REISSUE ECB#35267335M ISSUED 05/23/17 FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER 115.6(1968 CODE... | $0 | $0 | Jul 30, 2018 |
| May 1, 2018 | 35330844J | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT GYM CEILING TILES MISSING NONE AT VARIOUS LOCATIONS.RE... | $0 | $0 | Jul 30, 2018 |
| May 1, 2018 | 35330843H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT STAIRCASE C ROOF LEVEL WATER PENETRATION STAINING WALL... | $0 | $0 | Jul 30, 2018 |
| May 1, 2018 | 35330842X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT STAIRCASES/EXITS B,3,4,5 AND AUDITORIUM DOORS ARE IN D... | $0 | $0 | Jul 30, 2018 |
| May 1, 2018 | 35330841Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.USE OF PROHIBITED DOOR AND OR HARDWARE PER BC1008.1.8;27-371(J)... | $0 | $0 | Jul 30, 2018 |
| May 23, 2017 | 35267335M | RESOLVE | CLASS - 2 | 28-301.1 FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6 1968 CODE), FGC APPENDIX E (E4) 2014 CODE. AT TI... | $0 | $0 | Aug 7, 2017 |
| May 23, 2017 | 35267339J | RESOLVE | CLASS - 2 | EXIT DOOR(S) NOT SELF CLOSING. AT TIME OF INSPECTION, IN CAFETERIA ON 1ST FLOOR EXIT #5 AND #6, AUDITORIUM NEXT TO ST... | $0 | $0 | Aug 7, 2017 |
| May 23, 2017 | 35267338H | RESOLVE | CLASS - 2 | 28-301.1 UNLAWFUL PLACEMENT OF FURNISHINGS, DECORATIONS OR OTHERS OBJECTS AS EXITS THAT OBSTRUCT ACCESS TO EGRESS FRO... | $0 | $0 | Aug 7, 2017 |