ECB violations
Compass Charter School, Brooklyn • Block 02103 • Lot 0004
94 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Feb 5, 2026 | 35728765L | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION, CLASSROOM DOORS 407, 408, 310, 300,... | $1,250 | $0 | Mar 5, 2026 |
| Feb 5, 2026 | 35728764J | ACTIVE | CLASS - 2 | RE-ISSUED 35691880K. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION, STUDIO ON 2ND ... | $3,125 | $0 | Mar 5, 2026 |
| Feb 5, 2026 | 35728766N | ACTIVE | CLASS - 2 | 28-301.1. UNLAWFUL PLACEMENT OF FURNISHINGS, DECORATIONS OR OTHER OBJECTS AT EXITS THAT OBSTRUCT ACCESS TO, EGRESS FR... | $1,250 | $0 | Mar 5, 2026 |
| Feb 5, 2026 | 35728767P | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27-371... | $1,250 | $0 | Mar 5, 2026 |
| Jun 17, 2025 | 39151311Z | ACTIVE | CLASS - 3 | DELTA DOMESTIC HOT WATER TANK IS LEAKING WATER AT THE BOTTOM+LAARS H STAMPED-MT2H0500 HOT WATER BOILER DATED 2022 IS ... | $500 | $0 | Jun 30, 2025 |
| Mar 19, 2025 | 35691880K | ACTIVE | CLASS - 2 | REISSUE: 35672445M-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: 2ND FLOOR DANCE STUDIO HAS BROKEN GLASS. RE... | $3,125 | $0 | Apr 23, 2025 |
| Aug 14, 2024 | 39122068P | ACTIVE | CLASS - 2 | FOUND NATIONAL BOILER WORKS BOILERS ACTIVE WITH DEFECTS AT TIME OF INSPECTION. REFECTORY INSIDE COMBUSTION CHAMBER DE... | $625 | $0 | Aug 29, 2024 |
| Feb 22, 2024 | 35672444K | RESOLVE | CLASS - 2 | REISSUE#35671816H-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.AT BASEMENT LEVEL EXIT SIGN AT RIGHTSIDE OF E... | $1,562 | $0 | May 2, 2024 |
| Feb 22, 2024 | 35672445M | ACTIVE | CLASS - 2 | REISSUE#35650678X-2ND FLOOR DANCE STUDIO GLASS IS CRACK AT SEVERAL AREAS.REM:COMPLY WITH CODE. | $1,562 | $0 | May 2, 2024 |
| Feb 2, 2023 | 35671818L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED THE DOOR TO ROOM 322 AND 229 IS NOT WORKING PROPERLY.REME... | $625 | $0 | May 10, 2023 |
| Feb 2, 2023 | 35671816H | RESOLVE | CLASS - 2 | REISSUE#35650677Y.NOTED AT BASEMENT LEVEL EXIT SIGN BY THE RIGHT OF THE ENTRANCE DOOR,KITCHEN EXIT SIGN BY EXIT 9,CAF... | $1,562 | $0 | May 10, 2023 |
| Feb 2, 2023 | 35671814Y | RESOLVE | CLASS - 1 | REISSUE#35650678X.NOTED ON 2ND FLOOR DANCE STUDIO ROOM(205)THERE ARE BROKEN SECTION OF GLASS ON THE LEFT SIDE OF THE ... | $3,125 | $0 | May 10, 2023 |
| Feb 2, 2023 | 35671815X | RESOLVE | CLASS - 2 | REISSUE#35650676M.NOTED AT THE CAFETERIA KITCHEN,THERE IS A COMMERCIALGAS STOVE THAT DOES NOT HAVE AN ANNUAL SYSTEM I... | $1,562 | $0 | May 10, 2023 |
| Feb 2, 2023 | 35671817J | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING.NOTED ON 4TH FLOOR STAIR A BY 424,SMOKE BY 116,SMOKE BY EXIT 9 CORRIDOR BY EXIT 15,EXTERIO... | $625 | $0 | May 10, 2023 |
| Mar 23, 2022 | 35650680P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:PROVIDE REQUIRED CORRIDOR WIDTH PER BC1016.2;27-369 NOTED:OBSERVED T... | $625 | $0 | Sep 14, 2022 |
| Mar 23, 2022 | 35650678X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:NOTED:OBSERVED ON 2FLIN RM205(DANCE STUDIO) GLASS MIRROR BROKEN,MISS... | $1,250 | $0 | Sep 14, 2022 |
| Mar 23, 2022 | 35650676M | RESOLVE | CLASS - 2 | REISSUED35560796H FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:NOTED:OBSERVED IN KITCHEN,A10 BURNER COMMERCIAL GA... | $1,562 | $0 | Sep 14, 2022 |
| Mar 23, 2022 | 35650677Y | RESOLVE | CLASS - 2 | REISSUED35560797J FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES&PUBLIC CORR... | $1,562 | $0 | Sep 14, 2022 |
| Mar 23, 2022 | 35650679H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:NOTED:OBSERVED@BSMT B/W RMB46&STAIRB,BULGING/SAGGING CONCRETE APRX1"... | $1,250 | $0 | Sep 14, 2022 |
| Feb 23, 2022 | 39056656Z | ACTIVE | CLASS - 1 | W/O PERMIT=LAARS MT2H0500 500,000 BTU'S GAS FIRE DOMESTIC HOT WATER BOILER, OBTAIN PERMIT | $2,500 | $0 | Mar 7, 2022 |
| Feb 23, 2022 | 39056654P | RESOLVE | CLASS - 2 | NRC 6300000 BTU'S EVIDENCE OF CORROSION ON BOTTOM REAR SHELL PLATE. | $625 | $0 | Mar 7, 2022 |
| Feb 23, 2022 | 39056655R | RESOLVE | CLASS - 2 | NRC 6300000 BTU'S BRICK SET CHAMBER EVIDENCE OF CORROSION ON HAND HOLE BOTTOM FRONT LEFT SIDE OF BOILER | $625 | $0 | Mar 7, 2022 |
| Nov 17, 2021 | 39051332J | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $1,250 | $0 | Dec 14, 2021 |
| May 21, 2021 | 35560796H | RESOLVE | CLASS - 2 | RE-ISSUE#354995518J FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:DURING INSPECTION OBSERVED AT CELLAR ... | $1,562 | $0 | Nov 3, 2021 |
| May 12, 2021 | 35560797J | RESOLVE | CLASS - 2 | RE-ISSUE#35495519L FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ILLUMINATE EXITS.EXIT DISCHARGES & PUBLIC CO... | $1,562 | $0 | Nov 3, 2021 |
| May 15, 2020 | 35495518J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: AT KITCHEN,10 BURNER COMMERCIAL GAS STOVE DO NOT HAVE ANSUL... | $625 | $0 | Feb 25, 2021 |
| May 15, 2020 | 35495519L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER-ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS PER BC 10... | $625 | $0 | Feb 24, 2021 |
| Apr 29, 2019 | 35422170K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER. NOTE: DOORS ATROOM 20, 21,24 AND EXIT 2,3 AT 1ST FLOOR DO NOT ... | $0 | $0 | Sep 9, 2019 |
| May 2, 2018 | 35329522Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTE:AT LOWER LEVEL ADJACENT TO STAIR #6 WATER DAMAGE AT CEILING CA... | $0 | $0 | Aug 6, 2018 |
| May 2, 2018 | 35329521R | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BLDG WALL(S)AND APPURTENANCES.NOTED:DAMAGED/MISSING MORTAR ABOVE WINDOWS LOCATED IN ROOMS 412,414... | $0 | $0 | Aug 6, 2018 |
| May 2, 2018 | 35329520P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTED:DAMAGED/RAISEDSECTIONS OF CONCRETE FLAGS,LIFTED 4 INCHES AT M... | $0 | $0 | Aug 6, 2018 |
| May 30, 2017 | 35267344Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS P... | $0 | $0 | Aug 7, 2017 |
| May 30, 2017 | 35267343M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. USE OF PROHIBITED DOOR(S) AND/OR HARDWARE PER 1008.1.8; 27-371... | $0 | $0 | Aug 7, 2017 |
| May 30, 2017 | 35267340R | RESOLVE | CLASS - 2 | UNLAWFUL DISPLAY OF ARTWORK IN CORRIDORS GREATER THAN 70% PER FDNY 2008 CODE; FC 803.3.2 AT TIME OF INSPECTION THER E... | $0 | $0 | Aug 7, 2017 |
| May 30, 2017 | 35267341Z | RESOLVE | CLASS - 2 | UNLAWFUL PLACEMENT OF FURNISHING, DECORATIONS OR OTHER OBJECTS AT EXITTHAT OBSTRUCT ACCESS TO EGRESS FORM OR, VISIBIL... | $0 | $0 | Aug 7, 2017 |
| May 30, 2017 | 35267342K | RESOLVE | CLASS - 2 | EXIT DOOR(S) NOT SELF CLOSING. AT TIME OF INSPECTION AT EXIT 3 ON 1ST FLR, 2 DOOR ARE NOT CLOSE PROPERLY, STAIR "D" 1... | $0 | $0 | Aug 7, 2017 |
| Apr 21, 2015 | 35128212M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. IN THE CAFETERIA WATER IS PENETRATING THE CEILING TILES AT VARIOUS... | $0 | $0 | Aug 3, 2015 |
| Apr 21, 2015 | 35128210Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. ON THE 4TH FLOOR CORRIDOR WOODEN COAT LOCKERS/CUBBIES ARE ON BOTH ... | $0 | $0 | Aug 3, 2015 |
| Apr 21, 2015 | 35128213Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. INSIDE THE KITCHEN ADJACENT TO THE REAR YARD EXIT WATER IS PENETRATI... | $0 | $0 | Aug 3, 2015 |
| Apr 21, 2015 | 35128209L | RESOLVE | CLASS - 2 | 17-371(B) REISSUE: 35093127K. PLEXIGLASS VISION PANELS INSTALLED ON DOORS AT VARIOUS LOCATIONS THROUGHOUT THE BUILDIN... | $0 | $0 | Aug 3, 2015 |
| Apr 21, 2015 | 35128211K | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE POWER FOR EMERGENCY EXIT LIGHTING.IN THE AUDITORIUMSIX EMERGENCY EXIT LIGHTS ARE NOT WORKING. IN T... | $0 | $0 | Aug 3, 2015 |
| Apr 16, 2014 | 35093127K | RESOLVE | CLASS - 2 | 27-371(B). RE-ISSUE # 34954322L. PLEXI VISION PANELS INSTALLED ON DOORS THROUGHOUT ENTIRE BUILDING. REMEDY: REPLACE W... | $0 | $0 | Jun 16, 2014 |
| Apr 16, 2014 | 35093126Z | RESOLVE | CLASS - 2 | RE-ISSUE # 35004083K. DEFECTIVE GYM FLOOR WARPED SECTION FRONT OF WATER FOUNTAIN. REMEDY: REPAIR FLOOR. | $0 | $0 | Jun 16, 2014 |
| Mar 26, 2013 | 35004083K | RESOLVE | CLASS - 2 | REISSUE: 34954324P GYMNASIUM WOODEN FLOOR IS WARPED AND DAMAGED BY WATER PENETRATION ADJACENT TO THE MAIN ENTRANCE ON... | $0 | $0 | May 13, 2013 |
| Apr 19, 2012 | 34954323N | RESOLVE | CLASS - 2 | DOORS NOT SELF CLOSING. AT STAIR A 3RD FLR STAIR C BASEMENT STAIR D,3RD FLR & CAFETERIA ACROSS FROM RM B32 DOORS RACK... | $0 | $0 | Oct 15, 2012 |
| Apr 19, 2012 | 34954322L | RESOLVE | CLASS - 2 | 27-371B:REISSUE 34919565M PLEXI VISSION PANELS INSTALLED ON DOORS AT VARIOUS LOCATIONS THROUGHOUT BLDG. REM:PROVIDE R... | $0 | $0 | Oct 15, 2012 |
| Apr 19, 2012 | 34954324P | RESOLVE | CLASS - 2 | REISSUE 34919566Y GYM FLR IS WARP & UNEVEN DUE TO WATER LEAK. REM:REPAIR OR REPLACE FLOORING. | $0 | $0 | Oct 15, 2012 |
| Jul 1, 2011 | 34919563Z | RESOLVE | CLASS - 2 | RACKED DOORS. THE FIRE PROOF SELF CLOSING DOORS ARE RACKED TO FRAME AND WILL NOT CLOSE PROPERLY AT 4TH FLR. STAIRWAY ... | $0 | $0 | Aug 1, 2011 |
| Jul 1, 2011 | 34919564K | RESOLVE | CLASS - 2 | MISSING DOOR. AT 3RD FLR STAIRWAY B, FIRE PROOF SELF CLOSING DOOR IS MISSING. REMEDY:PROVIDE/REPLACE DOOR. | $0 | $0 | Aug 1, 2011 |
| Jul 1, 2011 | 34919566Y | RESOLVE | CLASS - 2 | DEFECTIVE FLOORING. AT GYM, APPROX 50SQ.FT. OF FLOORING IS UNEVEN, WA RPED AND BLACKENED DUE TO PRIOR WATER LEAK.REME... | $0 | $0 | Aug 1, 2011 |