ECB violations
16-38 South 11 Street, Brooklyn • Block 02159 • Lot 0001
151 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Sep 6, 2024 | 39124123H | RESOLVE | CLASS - 1 | 1) AN ELEVATOR IN SECTION OF BUILDING OR BUILDING IS OUT-OF-SERVICE. UPON INSPECTION THE DEVICE IS FOUND TO BE OUT-OF... | $1,250 | $0 | Nov 13, 2024 |
| Jul 23, 2024 | 39119706N | RESOLVE | CLASS - 1 | CEASE USE ITEM: DOOR ZONE RESTRICTOR NOT WORKING PROPERLY. THIS SAFETY DEVICE PREVENTS THE CAB DOOR FROM OPENING IN B... | $3,125 | $0 | Oct 2, 2024 |
| Jan 16, 2024 | 37026398P | RESOLVE | CLASS - 2 | FAILURE TO FILE ACCEPTABLE AMENDED CYCLE 7A,8A & 9A REPORT INDICATING CORRECTION OF UNSAFE CONDITIONS DESCRIBED IN IN... | $0 | $0 | Apr 17, 2024 |
| Jan 25, 2022 | 35636837N | RESOLVE | CLASS - 2 | EXPIRED ELEVATOR PERMIT AND TEMPORARY CERTIFICATE.OBSERVED ACTIVE WORKSITE ON OCCUPIED 11 STORY EXISTING BUILDING.USI... | $0 | $0 | Jun 8, 2022 |
| Dec 15, 2020 | 35543359P | RESOLVE | CLASS - 1 | FAILURE TO FILE EVIDENCE OF COMPLIANCE WITH WORKERS COMPENSATION LAW.NOTE:AT THE TIME OF MY INSPECTION OF A 11 STORY ... | $5,000 | $0 | Dec 20, 2021 |
| Dec 15, 2020 | 35543358N | RESOLVE | CLASS - 1 | 3303.12.4 CONVERTING ELEVATORS.NOTE:AT THE TIME OF MY INSPECTION OF AN11 STORY BUILDING WITH CONSTRUCTION WORK IN PRO... | $0 | $0 | Dec 20, 2021 |
| Dec 15, 2020 | 35543356J | RESOLVE | CLASS - 1 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS.NOTE:AT THE TIME OF INSPECTION OF AN 11 STORY UNDERGOING ALT... | $0 | $0 | Dec 20, 2021 |
| Dec 14, 2020 | 35547201N | RESOLVE | CLASS - 2 | WORK DOESN'T CONFORM TO APPROVED CONSTRUCTION DOCS-SWS DRAWINGS(B00092556) @TIME OF INSPECTION ON 11STYALT SITE OBSER... | $0 | $0 | Feb 7, 2022 |
| Dec 14, 2020 | 35547202P | RESOLVE | CLASS - 2 | BC3307.6.5.8 PERIODIC INSPECTION @TIME OF INSPECTION ON 11STYALT SITE OBSERVED SIDEWALK SHED IN PLACE @EXP1&2.AFTER R... | $625 | $0 | Feb 7, 2022 |
| Dec 14, 2020 | 35508459Z | RESOLVE | CLASS - 2 | CONSTRUCTION FENCE NOT MAINTAINED. AT THE TIME OF INSPECTION OF 11 STORY BLDG UNDER ALTERATION AND ONGOING EXTERIOR W... | $500 | $0 | Aug 18, 2021 |
| Dec 14, 2020 | 35547203R | RESOLVE | CLASS - 1 | BC3307.6.5.10 DAILY INSPECTION @TIME OF INSPECTION ON 11STYALT SITE OBSERVED SIDEWALK SHED INSTALLED @EXP1&2.AFTER RE... | $625 | $0 | Feb 7, 2022 |
| Sep 29, 2020 | 39029455Z | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $0 | $0 | Feb 3, 2021 |
| Jan 31, 2020 | 39016677L | RESOLVE | CLASS - 2 | CONSTRUCTION DEBRIS ACCUMULATIONS ON THE ROOF. LOOSE AND UNPROTECTED DEBRIS., MAINTAIN ADEQUATE CONSTRUCTION HOUSEKEE... | $3,125 | $0 | Jul 12, 2021 |
| Sep 3, 2019 | 38271303Z | RESOLVE | CLASS - 1 | CEASE USE 5-B-1,45-H-10,59-BB-7,80-M-7 | $1,250 | $0 | Nov 9, 2020 |
| Aug 5, 2019 | 35438930K | RESOLVE | CLASS - 1 | FAILURE TO SAFEGUARD PUBLIC AND PROPERTY. IN RESPONSE TO INCIDENT,WHERE A WORKER FELL AND INJURED HIMSELF. IT WAS REP... | $0 | $0 | Dec 9, 2019 |
| Mar 12, 2019 | 38268438Z | RESOLVE | CLASS - 2 | 2X10,100P7,40P7. 2X10-OUTSIDE COMM INOPERATIVE REPAIR; 100P7-NO MEANSOF ACCESS TO HOISTWAY, PROVIDE; 40P7-NO ACCESS T... | $0 | $0 | Jun 24, 2019 |
| Feb 11, 2019 | 37014433N | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT A REQUIRED CYCLE 8A REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPUR... | $3,125 | -$3,125 | Jul 8, 2019 |
| Feb 1, 2019 | 35352524H | RESOLVE | CLASS - 1 | WORK WITHOUT A PERMIT.I OBSERVED IN THE CELLAR AREA GAS METER FOR THE THIRD FLOOR LOCKED BUT A ILLEGAL BYPASS INSTALL... | $0 | $0 | May 6, 2019 |
| Feb 1, 2019 | 35352752J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. I OBSERVED THROUGHOUT THE BLDG FROM THE 2ND FL THROUGH 10TH FL,GAS... | $0 | $0 | Mar 9, 2020 |
| Feb 1, 2019 | 35352751H | RESOLVE | CLASS - 1 | GAS BEING SUPPLIED TO BLDG W/O INSPECTION & CERTIFICATIKON BY DOB. I OBSERVED IN THE CELLAR AREA GAS BEING SUPPLIED T... | $5,000 | $0 | Aug 26, 2019 |
| Feb 1, 2019 | 35352750X | RESOLVE | CLASS - 1 | FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED/INSPECTED. I OBSERVED IN THE CELLAR AREA GAS METER FOR THE 3RD ... | $2,500 | $0 | Aug 27, 2019 |
| Feb 1, 2019 | 35352523X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANER.PROHIBITED MATERIAL.I OBSERVED ON THE THIRD FLOOR AREA IN THE CE... | $3,125 | -$3,125 | Sep 16, 2019 |
| Jan 25, 2019 | 39001186P | RESOLVE | CLASS - 1 | CEASE USE ITEMS: 1) MISSING ESCAPE HATCH EXPOSING HOISTWAY 2) HOLES IN DOME EXPOSING HOISTWAY CLASS 2 ITEMS: INOPERAT... | $1,250 | $0 | Mar 11, 2019 |
| Jan 25, 2019 | 39001187R | RESOLVE | CLASS - 2 | PROVIDE SIGHT GUARDS PER K3, PROVIDE IN CASE OF FIRE SIGNS ON ALL FLOORS, DEFECTIVE EMERGENCY LIGHTING, INOPERATIVE P... | $312 | $0 | Mar 13, 2019 |
| Oct 22, 2018 | 35344943M | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE SIDEWALK SHED. EXP 2 BROKEN GLASS AT 3RD STORY, BROKEN CONCRETE AT 9TH STORY, BROKEN CONCRETE AT 2... | $10,000 | $0 | Jan 14, 2019 |
| Oct 22, 2018 | 35344942K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING EXTERIOR WALLS/FACADE AND APPURTENANCES. EXP2: BROKEN GLASS AT 3RD STORY, CRACKS AT CORN... | $2,500 | $0 | Jan 14, 2019 |
| Aug 7, 2017 | 38257024P | RESOLVE | CLASS - 2 | 5E1,5J1,10H11,29J10,16E1,11L10,59BB7,69M7,56Y2,56Y13,17H11. 5E1-CAR DOOR RUBBING ADJUST; 5J1-CAR DOOR MISALIGNED ADJU... | $250 | $0 | Sep 25, 2017 |
| Jul 13, 2017 | 35259777J | RESOLVE | CLASS - 2 | VANDEL PROOF FIXTURES. PEDESTRIAN PROTECTION DOES NOT MEET CODE SPACIFICATIONS. FIXTURES MUST BE IN PLACE AT ALL TIME... | $2,430 | $0 | Aug 28, 2017 |
| Jul 13, 2017 | 35259776H | RESOLVE | CLASS - 2 | PARAPET PEDETRIAN PROTECTION DOES NOT MEET CODE SPECIFICATIONS, PARAPET SHALL BE INSTALLED AROUND PERIMETER OF PLATFO... | $2,430 | $0 | Aug 28, 2017 |
| Jun 29, 2017 | 38256312P | RESOLVE | CLASS - 2 | 5E1,10H11,16E1,17H11,29J10,59BB7,56Y2,56Y13,56O2. (5E)CAR DOOR RUBBING ADJUST. (10H)CAR DOOR GIBBS WORN REPLACE. (29J... | $250 | $0 | Aug 14, 2017 |
| Feb 24, 2017 | 35138386L | RESOLVE | CLASS - 2 | MAINTENANCE. PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATIONS. NOTE: AT TIME OF INSPECTION I OBSERVED SIDEWALK... | $2,400 | $0 | Apr 10, 2017 |
| Oct 31, 2016 | 38250907R | RESOLVE | CLASS - 2 | 40P07, 70P07 | $1,250 | $0 | Dec 19, 2016 |
| Aug 11, 2016 | 37001230K | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT ACCEPTABLE 7TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS & APPUR... | $5,000 | -$5,000 | Feb 6, 2017 |
| Sep 21, 2015 | 36023255H | RESOLVE | CLASS - 2 | FAILURE TO FILE AN ACCEPTABLE TECHNICAL REPORT IN COMPLIANCE W/CODE PROVISIONS: PERIODIC INSPECTION OF EXERIOR WALLS ... | $2,000 | $0 | Jul 25, 2016 |
| Aug 29, 2015 | 35160102L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BLDG.AS NOTED @ TIME OF INSPECTION ON AN OCCUPIED 11 STORY BLDG OBSERVED 3 LARGE HORIZON... | $500 | $0 | Apr 11, 2016 |
| Aug 6, 2015 | 35133335Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN EXTERIOR BLDG ROOF CORNICE-WEST ELEV.EXP.1 CRACKED FACADE MASONRY VENTICLE AND HORIZONTAL CRACKS ... | $500 | $0 | Jan 4, 2016 |
| Apr 3, 2015 | 38234697H | RESOLVE | CLASS - 2 | 14M07,64M07,61M07,68B07,100110. 14-PROVIDE MIRROR IN ELEVATOR CAB; 64-PROVIDE CITY ID TAG ON NEW MAIN LINE; 61-PROVID... | $1,250 | $0 | May 18, 2015 |
| May 5, 2014 | 36019138R | RESOLVE | CLASS - 2 | FAILURE TO FILE AN ACCEPTABLE CYCLE 7 TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS: PERIODIC INSPECTION OF EXT... | $800 | $0 | Dec 29, 2014 |
| Sep 25, 2012 | 34997286N | RESOLVE | CLASS - 1 | (ELECTRICAL WORK W/O PERMIT) AT 10:30 AM OBSERVED THAT ELECTRICAL WIRING HAD BEEN INSTALLED THRU/OUT HALLS AND LEADIN... | $1,600 | $0 | Nov 20, 2012 |
| Mar 29, 2012 | 34950147P | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH COMMISSIONERS ORDER CONTAINED IN NOTICE OF VIOLATION #34917576Z FOR WORK WITHOUT A PERMIT. REM... | $6,000 | $0 | Oct 17, 2012 |
| Mar 29, 2012 | 34950146N | RESOLVE | CLASS - 1 | OCCUPANCY CONTRARY TO THAT ALLOWED BY C OF O: CLASS 'A' APARTMENTS CREATED AT ALL LEVELS THROUGHOUT ENTIRE PREMISES C... | $2,400 | $0 | Oct 17, 2012 |
| Mar 24, 2012 | 34950148R | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN NOTICE OF VIOLATION #34917406X ISSUED 7-20-11 FOR WORK W/O A PERMIT... | $0 | $0 | May 8, 2020 |
| Jan 10, 2012 | 34963044P | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER CONTAINED IN NOV #34917576Z ISSUED ON 07/20/11. REM: COMPLY W/THE COMMIS... | $0 | $0 | Feb 27, 2012 |
| Jan 10, 2012 | 34971183P | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION W/THE DEPT OF BUILDINGS FOR NOV #349... | $0 | $0 | Feb 27, 2012 |
| Jan 10, 2012 | 34963043N | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER CONTAINED IN NOV #34917407H ISSUED ON 7/20/11. REM: COMPLY W/THE COMMISS... | $0 | $0 | Feb 27, 2012 |
| Jan 10, 2012 | 34963045R | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER CONTAINED IN NOV #34917406X ISSUED ON 07/20/11. REM: COMPLY W/THE COMMIS... | $0 | $0 | Feb 27, 2012 |
| Jan 10, 2012 | 34971445X | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERT OF CORRECTION WITH THE DOB FOR NOTICE OF VIOLATION #34... | $800 | $0 | Dec 3, 2012 |
| Nov 17, 2011 | 34962049J | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN NOTICE OF VIOLATIONS #34917576Z,34917406X ISSUED ON 07-2... | $6,000 | $0 | Dec 24, 2012 |
| Sep 13, 2011 | 34961476J | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER CONTAINED IN NOTICE OF VIOLATION #34917576Z;#34917406X ISSUED ON 7/20/11... | $2,400 | $0 | Oct 24, 2012 |
| Jul 20, 2011 | 32070311J | RESOLVE | CLASS - 2 | 28-301.1 2(B254) 15,16,32A,36,38. RECURRING CONDITIONS | $0 | $0 | Feb 1, 2012 |