ECB violations
130 Clay Street, Brooklyn • Block 02489 • Lot 0007
44 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 24, 2026 | 39186004Z | RESOLVE | CLASS - 2 | CLASS 2: 1) EMERGENCY PHONE INOPERATIVE. TWO-WAY EMERGENCY COMMUNICATION SYSTEM DOES NOT TRANSMIT AUDIBLE SIGNAL FROM... | $625 | $625 | Dec 1, 2026 |
| Apr 24, 2026 | 39186003R | ACTIVE | CLASS - 1 | CLASS 1 C/U: 1) DOOR ZONE RESTRICTOR INOPERATIVE. REMEDY: REPAIR/REPLACE AND VERIFY PROPER OPERATION. CODE: ASME A17.... | $1,250 | $0 | Jul 1, 2026 |
| Apr 23, 2026 | 39185789N | ACTIVE | CLASS - 1 | OBSERVED NEW GAS LINES IN BASEMENT. NO PERMIT ON FILE. PER 28-105.1 WORK WITHOUT A PERMIT., OBTAIN PERMIT | $2,500 | $2,500 | Jan 4, 2027 |
| Apr 23, 2026 | 39185738N | ACTIVE | CLASS - 3 | @STAIRWAY A @ROOF TOP FAR LEFT THE JOHNSON CONTROLS HVAC UNIT IS INOPERABLE+@CELLAR BOILER ROOM THE LAARS HWH#2 IS IN... | $500 | $500 | Dec 1, 2026 |
| Apr 28, 2025 | 39146354M | ACTIVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING MECHANICAL DOORS AND EXIT DOORS. THROUGHOUT THE BUILDING. POTEN... | $625 | $0 | Jul 9, 2025 |
| Apr 28, 2025 | 39146351R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8 (2014 C... | $0 | $0 | Jul 9, 2025 |
| Apr 28, 2025 | 39146352Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Jul 9, 2025 |
| Apr 28, 2025 | 39146353K | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. OBSERVED SECURITY MACHINCE SCANNER OBSTRUCTING EXIT DOOR ON THE FIRS... | $1,250 | $0 | Jul 9, 2025 |
| Mar 1, 2024 | 39107655Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. IN CAR COMMUNICATION INOPERATIVE, REPAIR. PIT DIRTY, CLEAN. | $625 | $0 | Oct 23, 2024 |
| Nov 20, 2023 | 39523494P | RESOLVE | CLASS - 2 | LIGHTING BC3307.6.4.8 @3STORY ACTIVE PERMIT FACADE REPAIR SITE I OBSERVE PEDESTRIAN PROTECTION SIDEWALK SHED IN PLACE... | $1,250 | $0 | Jun 25, 2024 |
| May 16, 2023 | 39086783Z | ACTIVE | CLASS - 2 | I OBSERVED THROUGHOUT THE BUILDING THE INSTALLATION ON CONDUITS, JUNCTION BOXES, BRANCH CIRCUIT WIRING AND RECEPTACLE... | $800 | $0 | Jul 26, 2023 |
| May 16, 2023 | 39086888P | ACTIVE | CLASS - 2 | I OBSERVED THE ROOFTOP STAIRWAY HEATER AND WALL MOUNTED A.C. FAN UNITS WITHOUT AN EQUIPMENT DISCONNECT SWITCH PRIOR T... | $800 | $0 | Aug 2, 2023 |
| Mar 15, 2022 | 35644254L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES&PUBLIC CORRIDOR PER BC1006.1;... | $312 | $0 | Aug 3, 2022 |
| Mar 15, 2022 | 35644253J | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELFCLOSING.OBSERVED:FIREPROOF SELFCLOSING DOOR@ROOF LEVEL,STAIRCASEA,@2FL SMOKE DOOR NEAR STAIRCASEA@1... | $625 | $0 | Aug 3, 2022 |
| Mar 15, 2022 | 35644255N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:NO FIRESTOPPING PER BC712.3;27-345 OBSERVED:@CELLAR LEVEL,ELECTRICAL... | $625 | $0 | Aug 3, 2022 |
| Dec 3, 2021 | 39052206N | ACTIVE | CLASS - 1 | DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED (CU). IN CAR PHONE NOT WORKING. RUSTED CABLE ON THE MACHINE. | $1,250 | $0 | May 11, 2022 |
| Apr 1, 2019 | 38268682K | RESOLVE | CLASS - 2 | 07L10,99BB05. 07L10-REPAIR/ADJUST/DOOR REOPENING DEVICE; 99BB05- EXPIRED CATI TEST TAG. | $0 | $0 | Jul 15, 2019 |
| Mar 6, 2019 | 38268426L | RESOLVE | CLASS - 2 | 98M5,99M07,70Z9. 98M5-ROPED HDRO NEED TO PERFORM AND FILE WITH DOB CAT5 TEST; 99M7-CURRENT 1 YEAR TEST TAG MISSING PR... | $625 | $0 | Jun 18, 2019 |
| Jan 18, 2019 | 38267348K | RESOLVE | CLASS - 1 | 6A10,6M7,60X10,67X10. 5A10-REAR DOOR ZONE RESTRICTOR NOT WORKING NEEDS TO BE ADJUSTED; 6M7-DOOR POSITION MONITORING D... | $3,125 | $0 | Apr 22, 2019 |
| Jan 18, 2019 | 38267349M | RESOLVE | CLASS - 1 | 6M7 DOOR POSITION MONITORING DID NOT WORK CODE DATA TAG 2000/03. | $3,125 | $0 | Apr 22, 2019 |
| Aug 29, 2018 | 35347068R | ACTIVE | CLASS - 3 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON ROOFCONDENSATE DRAINS,FROM HVAC UNITS BROKEN AND CO... | $250 | $0 | Feb 11, 2019 |
| Aug 29, 2018 | 35347070X | ACTIVE | CLASS - 1 | FGC408.2/MISCELLANEOUS VIOLATIONS:FUTURE CONNECTIONS EXIST ON GAS PIPING.OBSERVED IN BOILER ROOM ON THE LEFT SIDE OF ... | $2,500 | $0 | Feb 13, 2019 |
| Oct 25, 2017 | 38258773R | RESOLVE | CLASS - 2 | 10H11,16J1,5J1,17H11,28L10,29J1,32E1,70Z9. 10H11 CAR DOOR GIBS WORN REPLACE.16J1 HOIST WAY DOOR MISALIGNED ADJUST.5J1... | $250 | $0 | Dec 11, 2017 |
| Aug 16, 2017 | 35289626J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ON 08/16/2017 AT ABOVE ADDRESS EXCESSIVE STORAGE IN G... | $1,250 | $0 | Oct 2, 2017 |
| Aug 16, 2017 | 35289687N | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/OPERMIT.OBSERVE ON ROOF OF SECOND FL EXT.THE INSTALLATION OF A BACKUP POWER GENERATOR,POWER FEEDERS... | $0 | $0 | Nov 29, 2017 |
| Aug 16, 2017 | 35289686L | RESOLVE | CLASS - 1 | SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL.OBSERVED INELECTRICAL RM LOCATED IN BSMT.THE INSTALL... | $1,600 | $0 | Jan 24, 2018 |
| Jun 24, 2017 | 35275227P | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35260499R ISSUED ON 05/06/17 & TO FILE A C OF C PURSUAN... | $400 | $0 | Aug 14, 2017 |
| May 6, 2017 | 35260499R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT CELLAR LEVEL,GAS METER ROOM,EXCESSIVE STORAGE WHICH IS... | $2,500 | $0 | Jul 3, 2017 |
| May 6, 2017 | 35233491Z | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35234976L ISSUED ON 03/08/17 AND TO FIL... | $800 | $0 | Jun 26, 2017 |
| Mar 8, 2017 | 35228769H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES.DEFECTS NOTED:APPROXIMATELY 2"WIDE CRACKS BELOW 1ST FLR AND 2ND F... | $500 | $0 | Sep 20, 2017 |
| Mar 8, 2017 | 35234976L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.AT THE TIME OF INSPECTION IN OBSERVED IN THE GAS METER ROOM NO ... | $1,000 | $0 | Sep 20, 2017 |
| Mar 8, 2017 | 35234975J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.AT THE TIME OF INSPECTION I OBSERVED IN THE GAS METER ROOM EXCE... | $1,000 | $0 | Sep 20, 2017 |
| Mar 8, 2017 | 35234724P | ACTIVE | CLASS - 1 | FGC408.2/MISCELLANEOUS VIOLATIONS:FUTURE CONNECTIONS EXIST ON GAS PIPING.AT THE TIME OF INSPECTION I OBSERVED IN THE ... | $800 | $0 | Sep 20, 2017 |
| Nov 16, 2016 | 38251037R | RESOLVE | CLASS - 2 | 5X10,2X10,42B11,13X10. (5X)REPAIR DOOR ZONE LOCK. (2X)REPAIR ALARM BELL. (42B)INCORRECT FUSES ON THE CONTROLLER. (13X... | $250 | $0 | Jan 9, 2017 |
| Feb 17, 2016 | 35170919P | RESOLVE | CLASS - 2 | FAILURE TO PAINT DEDICATED SPRINKLER/VALVES CODE COMPLIANT. NOTED: UNPAINTED SPRINKLER MAIN,CROSS CONNECTIONS & RISER... | $800 | $0 | Apr 4, 2016 |
| Apr 16, 2008 | 34626092M | RESOLVE | Hazardous | USE OF RIGGING EQUIPMENT W/O DANGER SIGNS.(NO DANGER SIGNS FOR SIDEWALKS). | $500 | $0 | Sep 8, 2008 |
| Apr 16, 2008 | 34626091K | RESOLVE | Hazardous | OPERATION OF CRANE IN AN UNSAFE MANNER.(CRANE SET UP ON SIDEWALK). | $0 | $0 | Sep 29, 2009 |
| Apr 16, 2008 | 34626088J | RESOLVE | Hazardous | OPERATION OF CRANE W/O CERTIFICATE OF APPROVAL/CERTIFICATE OF OPERATION.(NO ANNUAL "CD" INSPECTION FOR CRANE ( )USED ... | $1,500 | $0 | Sep 29, 2009 |
| Apr 16, 2008 | 34626089L | RESOLVE | Hazardous | DIRECTED THE USE OF HOISTING MACHINE W//O A HOISTING MACHINE OPERATORSLICENSE WORKERS. | $500 | $0 | Sep 29, 2009 |
| Apr 16, 2008 | 34626090Z | RESOLVE | Hazardous | SEC.26-182. NO SPECIAL SIGN HANGER LICENSE ON SITE. | $500 | $0 | Sep 29, 2009 |
| Nov 28, 2006 | 34537054R | RESOLVE | Hazardous | WORK W/O PERMIT. ILLEGAL WORK NOTED: FULL HEIGHT PARTITIONS ERECTED AT1ST - 3RD FLS CREATING COMMON HALLWAYS W/ DOORS... | $2,500 | $0 | Feb 12, 2007 |
| Nov 28, 2006 | 34537056K | RESOLVE | Non-Hazardous | EXIT PASSAGEWAY TOTAL OBSTRUCTION. NOTE: AT NORTH SIDE OF BLDG. FIRE ESCAPE SLIDE LADDER IS BLOCKED FROM LOWERING TO ... | $480 | $0 | Jan 23, 2007 |
| Nov 28, 2006 | 34537055Z | RESOLVE | Non-Hazardous | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C OF O/ DOB RECORDS. NOTE: COF O #216684 STATES BLDG TOBE USED AS COMMERCIA... | $2,500 | $0 | Jan 22, 2007 |
| Jul 20, 1992 | 34076593R | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN (DEFECT IS)HAVING SEALED ROOF SCUTTLE ACCESSIBLE TO 3ED FLOOR ROOF.REMEDY:REOPEN 3RD FLOOR ROOF S... | $0 | $0 | Aug 31, 1992 |