Skip to content

ECB violations

240-244 Huron Street, Brooklyn • Block 02534 • Lot 0013

10 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Mar 8, 2010 32068056Z RESOLVE CLASS - 2 50ABC 50A-CANT READ RATING PLATE 50B-BOILER PARTLY DEACTIVATED MUST BE COMPLETELY DEACTIVATED IN ORDER TO BE REMOVED ... $250 $0 May 3, 2010
Mar 8, 2010 32068054P RESOLVE CLASS - 2 18B 32A 48B 50ABCD 32-WIRES EXPOSED ON TRANSFORMER 50A-UNION LEAKING ON UPPER WATER COLUMN 50B-RATING PLATE OVER CANT... $250 $0 May 3, 2010
Mar 8, 2010 32068055R RESOLVE CLASS - 1 32A 50 32A-WIRES EXPOSED ON WATER FEED PUMP 50-BOILER CARDS NOT AVAILABLE ON SITE $100 $100 May 3, 2010
Apr 15, 2008 32052949J ACTIVE Non-Hazardous 3A.32A.50A.50B.50C. 32A EXPOSED WIRE ON PRESSURE CONTROL 3A CORRODED FLU PIPE AT CHOMNEY BASE 50A PIPE SAFETY VALVE D... $800 $0 Jun 16, 2008
Jul 7, 2006 32051794J RESOLVE Non-Hazardous 50A-50A-BOILER NOT IN USE & NOT UP TO CURRENT MAINTAINANCE RESTORE TO SERVICE & MAINTAIN OR DISCONNECT*NOT LEGALLY DI... $0 $0 Aug 21, 2006
Jul 7, 2006 32051793H RESOLVE Non-Hazardous 18A,18B,50A,50B,50C,50D-50A-PROVIDE PLATFORM TO GAIN ACCESS AT REAR OFBOILER FOR INSPECTION 50B-PROVIDE APPROVED TYPE... $0 $0 Aug 21, 2006
Jul 7, 2006 32051795L RESOLVE Non-Hazardous 50A-50A BOILER NOT IN USE BUT NOT DISCONNECTED RESTORE BACK TO SERVICE& PROVIDE CURRENT MAINTAINANCE OR LEGALLY DISCO... $0 $0 Aug 21, 2006
Nov 8, 2004 32046580H ACTIVE Non-Hazardous 32A/50 1970 CYCLOTHERM NATL BD 14314 50-REVRSE THE VALVE ON THE BOTTOMLINE SO THAT THE QUICK OPENING VALVE IS CLOSE T... $180 $0 Jan 24, 2005
Nov 8, 2004 32046579K ACTIVE Non-Hazardous 32A/16/50 50-REVERSE THE VALVES ON THE BOTTOM BLOWN DOWN SO THAT QUICKOPENING VALVE IS CLOSET TO THE BOILER FOLLOWED ... $180 $0 Jan 24, 2005
Nov 8, 2004 32046578Z ACTIVE Hazardous 3A/32A/50B/48B/50A/16 1983-CYCKOTHERM NB 16163 50-REVERSE ON BLOW DOWNLINE SO THAT QUICK OPENING VALVE IS CLOSET TO T... $800 $0 Jan 24, 2005