ECB violations
1050-1060 Lorimer Street, Brooklyn • Block 02596 • Lot 0001
32 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Mar 30, 2026 | 39182462H | ACTIVE | CLASS - 1 | OBSERVED THROUGHOUT THE BUILDING NO TRAP WRAPS INSULATION UNDER SINKS. FOURTH FLOOR BATHROOM WASTES LINE PENETRATION ... | $2,500 | $0 | Sep 14, 2026 |
| Mar 30, 2026 | 39182455J | ACTIVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED THRU OUT BUILDING THE INSTALLATION OF EXIT SIGNS ALSO HAVING EXPOSED WIRES... | $1,250 | $0 | Jun 3, 2026 |
| Mar 30, 2026 | 39182325L | ACTIVE | CLASS - 2 | WEIL MCLAIN BOILER MODEL # 1288. FOUND REAR COIL LEAKING AND FRONT COIL DOMESTIC RELIEF VALVE LEAKING. CORRECT VIOLAT... | $1,250 | $0 | Jun 3, 2026 |
| Mar 30, 2026 | 39182463J | ACTIVE | CLASS - 1 | OBSERVED IN THE CELLAR GAS LINE NOT BEING SUPPORTED PROPERLY AND INSTALLED A WASTE LINE IN DEDICATED ELECTRIC ROOM. B... | $2,500 | $0 | Sep 14, 2026 |
| Mar 30, 2026 | 39182454H | ACTIVE | CLASS - 1 | ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED IN THE BASEMENT ELECTRICAL CLOSET... | $1,200 | $0 | Jun 3, 2026 |
| Mar 4, 2024 | 39107713N | RESOLVE | CLASS - 2 | I OBSERVED THE DISCONNECTION OF THE BRANCH CIRCUIT WIRING SUPPLYING POWER TO THE PREVIOUS SAUNA LOCATED IN THE REAR O... | $800 | $0 | May 15, 2024 |
| Feb 22, 2024 | 39106681N | RESOLVE | CLASS - 2 | OBSERVED IN THE GAS METER ROOM AS WELL AS IN THE BOILER ROOM EXCESSIVE COMBUSTIBLE STORAGE ( SHELVES FOR SHOES, AIR C... | $625 | $0 | May 1, 2024 |
| Feb 22, 2024 | 39106682P | RESOLVE | CLASS - 2 | OBSERVED GAS LEAK ON THE BOILER LOCATED IN THE BASEMENT/CELLAR. NATIONAL GRID TECH CONFIRMED THE LEAK. AS PER 102.3 O... | $625 | $0 | May 1, 2024 |
| Feb 22, 2024 | 39106683R | RESOLVE | CLASS - 2 | OBSERVED IN THE GAS METER ROOM LOCATED AT THE SUB CELLAR IN THE GAS METER ROOM NO FRESH AIR VENTILATION NOTED. AS PER... | $625 | $0 | May 1, 2024 |
| May 18, 2022 | 39062361M | RESOLVE | CLASS - 2 | AT CELLAR LEVEL, ELECTRICAL ROOM, CEILING DAMAGE DUE WATER PENETRATION AND AT ROOF LEVEL, STAIR, WALLS SHOW SIGNS OF ... | $625 | $0 | Dec 8, 2022 |
| May 18, 2022 | 39062363X | RESOLVE | CLASS - 2 | AT 4TH FL, STAIRCASE B DOOR , 3RD FL STAIRCASE A DOOR AND EXIT DOOR NEAR RM # 332, 2ND FL, STAIRCASE A DOOR, DO NOT C... | $312 | $0 | Dec 8, 2022 |
| May 18, 2022 | 39062367N | RESOLVE | CLASS - 2 | I OBSERVED IN THE BATHROOMS ON THE 4TH ,2ND AND 1ST FLOOR DAYCARE DEFECTIVE GFCI RECEPTACLES, MIS-WIRED AND/OR BROKEN... | $1,200 | $0 | Dec 8, 2022 |
| May 18, 2022 | 39062368P | RESOLVE | CLASS - 1 | I OBSERVED IN THE ELECTRICAL EQUIPMENT ROOM A FLEXIBLE LIQUID-TITE METALLIC CONDUIT SEALTITE IMPROPERLY TERMINATED WI... | $1,600 | $0 | Dec 8, 2022 |
| May 18, 2022 | 39062362Y | RESOLVE | CLASS - 2 | AT EXPOSURE # 1&2, SEVERAL (+15 UN) WINDOW A/A UNIT INSTALLED WITHOUT SUPPORT., REPAIR AND/OR REPLACE | $312 | $0 | Dec 8, 2022 |
| Dec 14, 2021 | 35636012Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.OBSERVED:@GAS METER RM,EXCESSIVE COMBUSTIBLE MATERIAL SUCH AS CARDBO... | $625 | $0 | Apr 27, 2022 |
| Dec 14, 2021 | 35636011R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:OBSERVED:@EXP1&2,WINDOW A/C UNITS W/O BRACKET.(>10UNITS).REPAIR &/OR... | $625 | $0 | Apr 27, 2022 |
| Mar 20, 2020 | 39020134R | RESOLVE | CLASS - 1 | I OBSERVED IN BASEMENT BOILER ROOM FLU PIPING FOR BOILER WITH HOLES IN THE PIPE ALLOWING CO TO ESCAPE AND INTO THE AI... | $1,250 | $0 | Sep 28, 2020 |
| Mar 20, 2020 | 39020124N | RESOLVE | CLASS - 1 | HOLES IS FLUE PIPE, IMPROPER COMBUSTION OF POWER FLAME BURNER. CEASE USE ISSUED.DO NOT OPERATE BOILER UNTILL ALL HAZA... | $0 | $0 | Sep 28, 2020 |
| Mar 20, 2020 | 39020129M | RESOLVE | CLASS - 1 | I OBSERVED IN BASEMENT BOILER ROOM AND METER ROOM NEWLY INSTALLED GAS PIPING AND FITTINGS FOR BOILER AND NO PERMIT ON... | $5,000 | $0 | Sep 28, 2020 |
| Mar 20, 2020 | 39020130J | RESOLVE | CLASS - 1 | I OBSERVED IN BASEMENT BOILER ROOM AND METER ROOM NEWLY INSTALLED GAS PIPING FOR BOILER AND AS PER DOB RECORDS THE LA... | $2,500 | $0 | Sep 28, 2020 |
| Aug 15, 2018 | 35337015Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMON/VIO# 35207850M ISSUED ON 9/9/16 & TO FILE A C OF C ... | $1,280 | $0 | Oct 29, 2018 |
| Feb 28, 2018 | 35311366K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3; 27-345. NOTE: HOLES IN SUB CELL... | $500 | $0 | Aug 20, 2018 |
| Feb 28, 2018 | 35321703L | RESOLVE | CLASS - 1 | FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH SECTION. OBSERVED THE FOLLOWING VIOLATING CONDITI... | $2,400 | $0 | Aug 20, 2018 |
| Mar 7, 2017 | 35234799J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED ON 3/07/17 EXCESSIVE STORAGE IN BOILER ROOM.(LOCKERS,A... | $500 | $0 | Jun 26, 2017 |
| Sep 9, 2016 | 35207851Y | RESOLVE | CLASS - 2 | FAILURE TO HAVE NEW OR ALTERED PLY SYSTEMS TESTED. OBSERVED ON 9/9/16 AT 11:15 IN BST THROUGHOUT NEW 5"NH DRAINAGE PI... | $500 | $0 | Dec 16, 2016 |
| Sep 9, 2016 | 35207852X | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQ'D OBSERVED ON 9/9/16 @ 11:30AM AT FRONT ENTRANCE NO SPR... | $0 | $0 | Dec 16, 2016 |
| Sep 9, 2016 | 35207850M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER. OBSERVED ON 9/9/16 @ 11:15AM IN BSMT-ILLEGAL GAS FITTING DRESSER (... | $1,000 | $0 | Dec 12, 2016 |
| May 19, 2016 | 35194886Y | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF CLOSING.NOTED:AT FIRST FLOOR,ADJACENT TO STRENGTH ROOM THE DOOR OPENING TO LORIMER ST NOT SELF CLO... | $0 | $0 | Jul 11, 2016 |
| May 19, 2016 | 35194887X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:NO FIRE STOPPING PER BC7123;27-345.NOTED:AT CELLAR,BOILER ROOM,... | $0 | $0 | Sep 12, 2016 |
| May 21, 2013 | 34983753X | RESOLVE | CLASS - 2 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND/OR APPROVED AMENDMENTS. INSP DWG NOV 3.11. PREMISES UNDE... | $500 | $0 | Jul 8, 2013 |
| May 21, 2013 | 34983754H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER. PREMISES UNDER PCALT II 320400419, L.O.C. 4.30.13. NOTE AT TIME ... | $250 | $0 | Jul 8, 2013 |
| Oct 15, 1991 | 34061890L | RESOLVE | Non-Hazardous | ALTERED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY REQUIRED BY OPEN ALTERATION APPLICATION#1307/87 RE... | $285 | $0 | Dec 2, 1991 |