1050-1060 Lorimer Street, Brooklyn • Block 02596 • Lot 0001

32 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Mar 30, 2026 39182462H ACTIVE CLASS - 1 OBSERVED THROUGHOUT THE BUILDING NO TRAP WRAPS INSULATION UNDER SINKS. FOURTH FLOOR BATHROOM WASTES LINE PENETRATION ... $2,500 $0 Sep 14, 2026
Mar 30, 2026 39182455J ACTIVE CLASS - 1 ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED THRU OUT BUILDING THE INSTALLATION OF EXIT SIGNS ALSO HAVING EXPOSED WIRES... $1,250 $0 Jun 3, 2026
Mar 30, 2026 39182325L ACTIVE CLASS - 2 WEIL MCLAIN BOILER MODEL # 1288. FOUND REAR COIL LEAKING AND FRONT COIL DOMESTIC RELIEF VALVE LEAKING. CORRECT VIOLAT... $1,250 $0 Jun 3, 2026
Mar 30, 2026 39182463J ACTIVE CLASS - 1 OBSERVED IN THE CELLAR GAS LINE NOT BEING SUPPORTED PROPERLY AND INSTALLED A WASTE LINE IN DEDICATED ELECTRIC ROOM. B... $2,500 $0 Sep 14, 2026
Mar 30, 2026 39182454H ACTIVE CLASS - 1 ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED IN THE BASEMENT ELECTRICAL CLOSET... $1,200 $0 Jun 3, 2026
Mar 4, 2024 39107713N RESOLVE CLASS - 2 I OBSERVED THE DISCONNECTION OF THE BRANCH CIRCUIT WIRING SUPPLYING POWER TO THE PREVIOUS SAUNA LOCATED IN THE REAR O... $800 $0 May 15, 2024
Feb 22, 2024 39106681N RESOLVE CLASS - 2 OBSERVED IN THE GAS METER ROOM AS WELL AS IN THE BOILER ROOM EXCESSIVE COMBUSTIBLE STORAGE ( SHELVES FOR SHOES, AIR C... $625 $0 May 1, 2024
Feb 22, 2024 39106682P RESOLVE CLASS - 2 OBSERVED GAS LEAK ON THE BOILER LOCATED IN THE BASEMENT/CELLAR. NATIONAL GRID TECH CONFIRMED THE LEAK. AS PER 102.3 O... $625 $0 May 1, 2024
Feb 22, 2024 39106683R RESOLVE CLASS - 2 OBSERVED IN THE GAS METER ROOM LOCATED AT THE SUB CELLAR IN THE GAS METER ROOM NO FRESH AIR VENTILATION NOTED. AS PER... $625 $0 May 1, 2024
May 18, 2022 39062361M RESOLVE CLASS - 2 AT CELLAR LEVEL, ELECTRICAL ROOM, CEILING DAMAGE DUE WATER PENETRATION AND AT ROOF LEVEL, STAIR, WALLS SHOW SIGNS OF ... $625 $0 Dec 8, 2022
May 18, 2022 39062363X RESOLVE CLASS - 2 AT 4TH FL, STAIRCASE B DOOR , 3RD FL STAIRCASE A DOOR AND EXIT DOOR NEAR RM # 332, 2ND FL, STAIRCASE A DOOR, DO NOT C... $312 $0 Dec 8, 2022
May 18, 2022 39062367N RESOLVE CLASS - 2 I OBSERVED IN THE BATHROOMS ON THE 4TH ,2ND AND 1ST FLOOR DAYCARE DEFECTIVE GFCI RECEPTACLES, MIS-WIRED AND/OR BROKEN... $1,200 $0 Dec 8, 2022
May 18, 2022 39062368P RESOLVE CLASS - 1 I OBSERVED IN THE ELECTRICAL EQUIPMENT ROOM A FLEXIBLE LIQUID-TITE METALLIC CONDUIT SEALTITE IMPROPERLY TERMINATED WI... $1,600 $0 Dec 8, 2022
May 18, 2022 39062362Y RESOLVE CLASS - 2 AT EXPOSURE # 1&2, SEVERAL (+15 UN) WINDOW A/A UNIT INSTALLED WITHOUT SUPPORT., REPAIR AND/OR REPLACE $312 $0 Dec 8, 2022
Dec 14, 2021 35636012Z RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.OBSERVED:@GAS METER RM,EXCESSIVE COMBUSTIBLE MATERIAL SUCH AS CARDBO... $625 $0 Apr 27, 2022
Dec 14, 2021 35636011R RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:OBSERVED:@EXP1&2,WINDOW A/C UNITS W/O BRACKET.(>10UNITS).REPAIR &/OR... $625 $0 Apr 27, 2022
Mar 20, 2020 39020134R RESOLVE CLASS - 1 I OBSERVED IN BASEMENT BOILER ROOM FLU PIPING FOR BOILER WITH HOLES IN THE PIPE ALLOWING CO TO ESCAPE AND INTO THE AI... $1,250 $0 Sep 28, 2020
Mar 20, 2020 39020124N RESOLVE CLASS - 1 HOLES IS FLUE PIPE, IMPROPER COMBUSTION OF POWER FLAME BURNER. CEASE USE ISSUED.DO NOT OPERATE BOILER UNTILL ALL HAZA... $0 $0 Sep 28, 2020
Mar 20, 2020 39020129M RESOLVE CLASS - 1 I OBSERVED IN BASEMENT BOILER ROOM AND METER ROOM NEWLY INSTALLED GAS PIPING AND FITTINGS FOR BOILER AND NO PERMIT ON... $5,000 $0 Sep 28, 2020
Mar 20, 2020 39020130J RESOLVE CLASS - 1 I OBSERVED IN BASEMENT BOILER ROOM AND METER ROOM NEWLY INSTALLED GAS PIPING FOR BOILER AND AS PER DOB RECORDS THE LA... $2,500 $0 Sep 28, 2020
Aug 15, 2018 35337015Y RESOLVE CLASS - 2 FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMON/VIO# 35207850M ISSUED ON 9/9/16 & TO FILE A C OF C ... $1,280 $0 Oct 29, 2018
Feb 28, 2018 35311366K RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3; 27-345. NOTE: HOLES IN SUB CELL... $500 $0 Aug 20, 2018
Feb 28, 2018 35321703L RESOLVE CLASS - 1 FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH SECTION. OBSERVED THE FOLLOWING VIOLATING CONDITI... $2,400 $0 Aug 20, 2018
Mar 7, 2017 35234799J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED ON 3/07/17 EXCESSIVE STORAGE IN BOILER ROOM.(LOCKERS,A... $500 $0 Jun 26, 2017
Sep 9, 2016 35207851Y RESOLVE CLASS - 2 FAILURE TO HAVE NEW OR ALTERED PLY SYSTEMS TESTED. OBSERVED ON 9/9/16 AT 11:15 IN BST THROUGHOUT NEW 5"NH DRAINAGE PI... $500 $0 Dec 16, 2016
Sep 9, 2016 35207852X RESOLVE CLASS - 1 FAILURE TO PROVIDE A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQ'D OBSERVED ON 9/9/16 @ 11:30AM AT FRONT ENTRANCE NO SPR... $0 $0 Dec 16, 2016
Sep 9, 2016 35207850M RESOLVE CLASS - 1 FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER. OBSERVED ON 9/9/16 @ 11:15AM IN BSMT-ILLEGAL GAS FITTING DRESSER (... $1,000 $0 Dec 12, 2016
May 19, 2016 35194886Y RESOLVE CLASS - 2 EXIT DOOR NOT SELF CLOSING.NOTED:AT FIRST FLOOR,ADJACENT TO STRENGTH ROOM THE DOOR OPENING TO LORIMER ST NOT SELF CLO... $0 $0 Jul 11, 2016
May 19, 2016 35194887X RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:NO FIRE STOPPING PER BC7123;27-345.NOTED:AT CELLAR,BOILER ROOM,... $0 $0 Sep 12, 2016
May 21, 2013 34983753X RESOLVE CLASS - 2 WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND/OR APPROVED AMENDMENTS. INSP DWG NOV 3.11. PREMISES UNDE... $500 $0 Jul 8, 2013
May 21, 2013 34983754H RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER. PREMISES UNDER PCALT II 320400419, L.O.C. 4.30.13. NOTE AT TIME ... $250 $0 Jul 8, 2013
Oct 15, 1991 34061890L RESOLVE Non-Hazardous ALTERED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY REQUIRED BY OPEN ALTERATION APPLICATION#1307/87 RE... $285 $0 Dec 2, 1991