ECB violations
379 Suydam Street, Brooklyn • Block 03210 • Lot 0041
12 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 18, 2019 | 39002211M | RESOLVE | CLASS - 1 | AT TIME OF INSPECTION IN CELLAR I OBSERVED PROHIBITED UNION ON GAS LINE. WORK WAS DONE UNDER JOB# 321576709. GAS SERV... | $2,500 | $0 | Feb 6, 2020 |
| Mar 22, 2018 | 35307602L | RESOLVE | CLASS - 2 | WORK WITHOUT PERMIT. PREMISES UNDER ALT #2 JOB# 321649187. AT TIME OF INSPECTION FOUND CONSTRUCTION FENCE WHICH MADE ... | $1,280 | $0 | May 14, 2018 |
| Mar 22, 2018 | 35307601J | RESOLVE | CLASS - 2 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND/OR APPROVED AMENDMENTS. PREMISES UNDER: ALT 2 JOB #32164... | $625 | $0 | May 14, 2018 |
| Dec 30, 2009 | 32067784M | RESOLVE | CLASS - 3 | 50:CYCLOTHERM FISH BOILER HP STEAM. 50)SCALE ACCUMULATION & EVIDENCE OF LEAKAGE @ HANDHOLES.FLUSH BOILER OF INTERNAL ... | $500 | $0 | Feb 22, 2010 |
| Dec 30, 2009 | 32067785Y | RESOLVE | CLASS - 3 | 50:CYCLOTHERM FISH BOILER HP STEAM 50-SCALE ACCUMULATION & EVIDENCE OFLEAKAGE @ HANDHOLES FLUSH BOILER OF INTERNAL SC... | $500 | $0 | Feb 22, 2010 |
| Dec 30, 2009 | 32067786X | RESOLVE | CLASS - 3 | 50:CYCLOTHERM FISH BOILER HP STOR 50)SCALE ACCUMULATION & EVIDENCE OF LEAKAGE @ HANDHOLES.FLUSH BOILER OF INTERIOR SC... | $500 | $0 | Feb 22, 2010 |
| Dec 23, 2005 | 32049162Z | RESOLVE | Hazardous | CEASE USE. 51/50. 50-REPLACE THE NON APPROVED RETURN TANK WITH A HIGH PRESSURE APPROVED TANK. | $0 | $0 | Apr 3, 2006 |
| Dec 23, 2005 | 32049163K | RESOLVE | Hazardous | CEASE USE. 50/51. REPLACE THE NON APPROVED CONDENSATE RETURN TANK WITHAN TANK THAT CAN WITHSTAND THE PROPER PRESSURE. | $0 | $0 | Apr 3, 2006 |
| Dec 23, 2005 | 32049161R | RESOLVE | Hazardous | CEASE USE. 50/51. 50)THE CONDENSATE RETURN TANK IS NOT DESIGNED FOR THE JOB. IT IS A 275 GAL. OIL TANK. INSTALL A HIG... | $0 | $0 | Apr 3, 2006 |
| Jan 26, 2005 | 32047018P | RESOLVE | Non-Hazardous | BQ9/40 36/18B 34A/50C 50A/32A 50B 18A 1966 CYCLOTHERM NATL BD 12933 34 INSTALL A DOOR ON THE BOILER ROOM. 50A INSTALL... | $430 | $0 | Mar 14, 2005 |
| Jan 26, 2005 | 32047020Y | RESOLVE | Non-Hazardous | BQ9/48B 36/50A 18A/50B 18B 32A 40 1969 CYCLOTHERM 3561 50A PIPE SAFETYVALVE DOWN TO A SAFEPOINT. 50B PIPE DOWN GLASS ... | $430 | $0 | Mar 14, 2005 |
| Jan 26, 2005 | 32047019R | RESOLVE | Non-Hazardous | BQ9/40 36/48B 18A/50A 18B/50B 32/50C 36 1983 CYCLOTHERM NATL BD. 1620850A PIPE DOWN SAFETY VALVE DISCHARGE TO A SAFE ... | $430 | $0 | Mar 14, 2005 |