Skip to content

ECB violations

556 Wilson Avenue, Brooklyn • Block 03417 • Lot 0026

8 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Feb 1, 2023 39078811R ACTIVE CLASS - 3 1F PENNCO BOILER SER#0221=BOILER FEED PIPE CORRODED/MISSING REMOTE SWITCH/HWH SAFETY DISCHARGE PIPE INCORRECT, MAINTA... $500 $500 Apr 12, 2023
Feb 1, 2023 39078812Z ACTIVE CLASS - 2 WEILMCLAIN ECO BOILER 155,000BTU SER#5403 DATED2017 IS INSTALLED WITHOUT DOB PERMIT, OBTAIN ALL PERMITS; CORRECT VIOL... $6,250 $6,250 Apr 12, 2023
Feb 1, 2023 39078813K ACTIVE CLASS - 2 WEILMCLAIN ECO SER#5403=SAFETY VALVE LEAKING/BOILER VENT PIPE INCORRECT MATERIAL/VENT TERMINATION INCORRECT/MISSING B... $3,125 $3,125 Apr 12, 2023
Feb 1, 2023 39078814M ACTIVE CLASS - 3 3R PENNCO BOILER SER#9020=BOILER CIRCULATOR DEFECTIVE/MISSING REMOTE SWITCH, MAINTAIN BOILER; CORRECT VIOLATION AND S... $500 $500 Apr 12, 2023
Feb 1, 2023 39078815Y ACTIVE CLASS - 2 1R WEILMCLAIN BOILER SER#8436=MISSING LWCO/MISSING MANUAL RESET AQUASTAT/MISSING REMOTE SWITCH/CHIMNEY BASE NOT ACCES... $3,125 $3,125 Apr 12, 2023
Feb 1, 2023 39078816X ACTIVE CLASS - 2 2F PENNCO BOILER SER#0148=MISSING REMOTE SWITCH/HWH SAFETY DISCHARGE PIPE INCORRECT/HWH FLUE SUPPORT INCORRECT/HWH FL... $3,125 $3,125 Apr 12, 2023
Feb 1, 2023 39078817H ACTIVE CLASS - 2 2R PENNCO BOILER SER#9014=FLUE DAMPER IS DEFECTIVE/MISSING REMOTE SWITCH, MAINTAIN BOILER; CORRECT VIOLATION AND SUBM... $3,125 $3,125 Apr 12, 2023