ECB violations
1673-1675 Broadway, Brooklyn • Block 03426 • Lot 0005
45 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Sep 16, 2025 | 39160521L | ACTIVE | CLASS - 2 | OBSERVED ON THE GROUND FLOOR SPRINKLER HEAD OBSTRUCTED BY LIGHT FIXTURE. ALSO CAPS FOR SPRINKLER HEADS PAINTED TO THE... | $1,250 | $0 | Oct 20, 2025 |
| Oct 11, 2024 | 39127332H | RESOLVE | CLASS - 2 | NON SELF CLOSING EXIT DOOR ON 1ST FLOOR EAST WING OF BUILDING. THIS CAN LEAD TO A POTENTIAL SMOKE OR FIRE HAZARD., RE... | $625 | $0 | Oct 18, 2024 |
| Oct 11, 2024 | 39127331X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Oct 18, 2024 |
| Oct 10, 2024 | 39127134R | RESOLVE | CLASS - 2 | SPRINKLER CAPS THROUGHOUT FIRST FLOOR ON THE EAST SIDE PAINTED. ALSO SPRINKLER HEAD ON FIRST FLOOR PAINTED. AS PER 10... | $625 | $0 | Oct 18, 2024 |
| Oct 10, 2024 | 39127135Z | ACTIVE | CLASS - 1 | OBSERVED GAS LEAK ON FOUR INCH HEAD OF SERVICE PIPING., REPAIR AND/REPLACE | $1,250 | $0 | Oct 18, 2024 |
| Jun 17, 2024 | 39117038H | ACTIVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDER AS STATED IN ECB# 39097445J ISSUED ON 10/17/2023 AND FILE ... | $2,500 | $0 | Jul 27, 2024 |
| Jun 17, 2024 | 39117037X | ACTIVE | CLASS - 1 | I OBSERVED IN THE ELECTRICAL CLOSETS ON ALL FLOORS THE INSTALLATION OF DATA EQUIPMENT AND WIRING FOR CAMERA AND WIFI ... | $1,200 | $0 | Jul 27, 2024 |
| Oct 17, 2023 | 39097446L | RESOLVE | CLASS - 1 | I OBSERVED IN THE ELECTRICAL ROOM FOR AP-1C THE INSTALLATION OF BX CABLING WITHOUT SUPPORT AS REQUIRED. OBSERVED EXCE... | $1,600 | $0 | Nov 28, 2023 |
| Oct 17, 2023 | 39097241H | RESOLVE | CLASS - 2 | HOLE PENETRATION AND UNFINISHED EXPOSED WALLS IN THE ELECTRICAL ROOM CLOSET WEST WING, MAIN FLOOR, GROUND LEVEL., REP... | $625 | $0 | Nov 28, 2023 |
| Oct 17, 2023 | 39097445J | ACTIVE | CLASS - 1 | I OBSERVED IN THE ELECTRICAL CLOSETS ON THE FLOORS THE INSTALLATION OF DATA EQUIPMENT, SHELVING AND WIRING. THIS EQUI... | $1,200 | $0 | Nov 28, 2023 |
| Oct 17, 2023 | 39097272K | ACTIVE | CLASS - 2 | OBSERVED IN BASEMENT DOMESTIC WATER PUMP AND ALSO PIPING INSTALLED WITHOUT ANY PERMITS ON FILE AT THE DOB., REPAIR AN... | $625 | $0 | Nov 28, 2023 |
| Jan 24, 2023 | 39078281Z | ACTIVE | CLASS - 2 | PRESSURE RELIEF VALVE LEAKING, COMBUSTION AIR INTAKE BLOWER MOTOR INOPERATIVE , SCREEN CLOGGED AND NOT INTERLOCKED WI... | $625 | $0 | Jan 25, 2023 |
| Jan 24, 2023 | 39078514K | ACTIVE | CLASS - 2 | OBSERVED DOMESTIC PUMP LEAKING PROFUSELY. AS PER PC 102.3 INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHA... | $625 | $0 | Feb 27, 2023 |
| Jan 24, 2023 | 39080048P | RESOLVE | CLASS - 2 | I OBSERVED IN THE 1ST FLOOR RECREATION NO GFCI PROTECTION FOR THE KITCHEN OUTLETS AND BASEMENT BOILER ROOM AS REQUIRE... | $2,400 | $0 | Feb 27, 2023 |
| Jan 24, 2023 | 39080052H | RESOLVE | CLASS - 2 | I OBSERVED NO WATER METER JUMPER INSTALLED AS PER EC 250.53 D 1, PROVIDE ADEQUATE GROUNDING; INSTALL GROUND CONDUCTOR... | $2,400 | $0 | Feb 27, 2023 |
| Jan 24, 2023 | 39080051X | RESOLVE | CLASS - 2 | I OBSERVED AT THE ENTRANCES TO THE BOILER ROOM ONLY 1 REMOTE SHUT-OFF SWITCH INSTALLED. AS REQUIRED UNDER MC 1006.8.1... | $1,250 | $0 | Feb 27, 2023 |
| Jan 24, 2023 | 39080050Y | RESOLVE | CLASS - 2 | I OBSERVED ON THE EAST WING "C" ROOF DEFECTIVE/NON- OPERABLE EXHAUST FANS IN USE., COMPLY WITH EC; REPAIR OR REPLACE | $800 | $0 | Feb 27, 2023 |
| Jan 24, 2023 | 39080049R | RESOLVE | CLASS - 2 | I OBSERVED IN THE "E' STAIRWELL THE INSTALLATION OF THE OVERCURRENT DEVICES ABOVE THE ALLOWABLE HEIGHT OF 6'7" AS PER... | $800 | $0 | Feb 27, 2023 |
| Mar 24, 2022 | 39058770L | RESOLVE | CLASS - 2 | RELIEF VALVE LEAKING; CORRECT VIOLATING CONDITION AND SUBMIT A CERTIFICATE OF CORRECTION. | $625 | $0 | Mar 29, 2022 |
| Mar 23, 2022 | 35651036Z | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING.OBSERVED FIRE PROOF SELF-CLOSING DOOR AT SECOND FLOOR STAIRCASE E,WEST WING NEAR RECREATIO... | $625 | $0 | Aug 17, 2022 |
| Mar 23, 2022 | 39058729J | ACTIVE | CLASS - 2 | I OBSERVED WATER LEAKING PROFUSELY FROM THE DOMESTIC WATER PUMPS THAT ARE LOCATED IN THE WATER METER ROOM IN BASEMENT... | $625 | $0 | Mar 29, 2022 |
| Mar 23, 2022 | 39058730R | ACTIVE | CLASS - 2 | I OBSERVED IN BASEMENT 2 ACTIVE LEAKS ON THE HOT WATER SUPPLY LINE., REPAIR AND/OR REPLACE | $625 | $0 | Mar 29, 2022 |
| Dec 23, 2021 | 39053393M | RESOLVE | CLASS - 1 | REMOVE OIL AND CLEAN PIT. PERFORM NECESSARY REPAIR FOR OIL LEAK. REPAIR SAFETY EDGE DEFECTIVE. | $1,250 | $0 | Jan 12, 2022 |
| Nov 3, 2021 | 39050722K | ACTIVE | CLASS - 2 | I OBSERVED IN BASEMENT DEFECTIVE DOMESTIC WATER PUMP. AT THE TIME OF MY INSPECTION DOMESTIC WATER PUMP LEAKING PROFUS... | $625 | $0 | Nov 12, 2021 |
| Mar 10, 2020 | 35475604H | ACTIVE | CLASS - 3 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED AT ABOVE ADDRESS IN CELLAR/BASEMENT O,S,&Y VALVE EXTR... | $500 | $0 | Jul 22, 2020 |
| Mar 9, 2020 | 39019259M | RESOLVE | CLASS - 2 | DOOR OPERATOR BELT DEFECTIVE. | $625 | $0 | Mar 16, 2020 |
| Mar 12, 2019 | 35383812Y | RESOLVE | CLASS - 2 | ALTERED/CHANGED BUILDING OCCUPIED W/O A VALID CERTIFICATE OF OCCUPANCYAS PER 28-118.3.1-28-118.3.2. NOTED: BUILDING F... | $0 | $0 | Jul 1, 2019 |
| Apr 25, 2018 | 32096375Y | RESOLVE | CLASS - 2 | 5,50A-AS PER CLASS 2(B254)28-301.1 VIOLATING CONDITIONS. 5)BACKFLOW LEAKING. 50A)FRESH AIR LOUVER SCREEN DIRTY. CORRE... | $0 | $0 | Jun 25, 2018 |
| Apr 24, 2018 | 35336777X | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION# 35316900Y ISSUED ON 2/10/18 & TO FILE A... | $0 | $0 | Jul 2, 2018 |
| Feb 10, 2018 | 35316900Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED IN HALLWAYS THROUGHOUT FIRE SPRINKLER HEAD LOCATED LESS T... | $0 | $0 | May 7, 2018 |
| Dec 2, 2017 | 35297556N | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED LINE SPRINKLER HEADS INSTALLED LESS THAN 6 INCHES FROM... | $0 | $0 | Feb 5, 2018 |
| Oct 4, 2017 | 35279781K | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION # 35286916Y ISSUED ON 8/4/17 & TO FILE... | $0 | $0 | Dec 11, 2017 |
| Oct 4, 2017 | 35293886H | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED SPRINKLER HEADS ARE INSTALLED RIGHT ABOVE LIGHT FIXTUR... | $0 | $0 | Dec 11, 2017 |
| Aug 4, 2017 | 35286916Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON8/4/17 AT ABOVE ADDRESS EXCESSIVE STORAGE IN BOILER ... | $0 | $0 | Oct 16, 2017 |
| Aug 4, 2017 | 35286917X | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON8/4/17 AT ABOVE ADDRESS SPRINKLER HEADS ARE INSTALLE... | $0 | $0 | Oct 16, 2017 |
| Feb 24, 2017 | 35225724K | RESOLVE | CLASS - 2 | ALTERED/CHANGED BUILDING OCCUPIED W/OUT A VALID CERTIFICATE OF OCCUPANCY AS PER 28-118.3.1-28-118.3.2.BUILDING FULLY ... | $0 | $0 | Mar 27, 2017 |
| Feb 24, 2017 | 35234726Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING CODE COMPLIANT MANNER:INSTALLATION/MAINTANENCE OF PLUMBING MATERIALS EQUIPTMENT-PER PC 1... | $0 | $0 | Mar 27, 2017 |
| Oct 7, 2016 | 35214316H | RESOLVE | CLASS - 1 | SEC: FGC401.5. GAS PIPING NOT LABELED. @ TIME OF INSP ON 10/7/16 @ THE ABOVE ADDRESS OBSERVED IN THE BASEMENT AREA GA... | $0 | $0 | Nov 14, 2016 |
| Oct 7, 2016 | 35214317J | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. @ TIME OF INSP ON 10/7/16 @ THE ABOVE ADDRESS I OBSERVED IN THE 1S... | $0 | $0 | Nov 14, 2016 |
| Oct 7, 2016 | 35214315X | RESOLVE | CLASS - 2 | FAILURE TO PAINT DEDICATED SPRINKLER PIPING/VALVES IN ACCORDANCE W/ SECTION. @ TIME OF INSP ON 10/7/16 @ THE ABOVE PL... | $1,630 | $0 | Nov 14, 2016 |
| Oct 7, 2016 | 35213744J | RESOLVE | CLASS - 2 | CHANGED BLDG OCCUPIED W/OUT A VALID C OF O. NOTED: BLDG FULLY OCCUPIEDW/ EXPIRED TCO# 3P0007076/T. TEMPORARY CERTIFIC... | $0 | $0 | Nov 14, 2016 |
| Oct 7, 2016 | 35214314Y | ACTIVE | CLASS - 1 | SEC: FGC408.2. FUTURE CONNECTIONS EXIST ON GAS PIPING. @ TIME OF INSP ON 10/7/16 @ ABOVE PLACE OF OCCURRENCE ADDRESS ... | $0 | $0 | Nov 14, 2016 |
| Feb 29, 2016 | 35171294Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG CODE COMPLIANT. NOTED: @ 1ST FLR EAST WING EXIT PASSAGE (COMPACTOR AREA), BROKEN EXIT DOOR B... | $0 | $0 | Jul 18, 2016 |
| Feb 29, 2016 | 35171295K | RESOLVE | CLASS - 2 | CHANGED BLDG OCCUPIED W/OUT A VALID C OF O. NOTED: BLDG FULLY OCCUPIED W/ EXPIRED TCO#3P0007076/T. TEMPORARY C OF O E... | $0 | $0 | Jul 18, 2016 |
| Jan 6, 2004 | 32043790M | RESOLVE | Non-Hazardous | 34A,34B,B4A,50. BOILER ROOM NOT A STORAGE ROOM | $0 | $0 | Feb 23, 2004 |