| Feb 1, 2023 | 39079004P | RESOLVE | CLASS - 2 | I OBSERVED ON ALL FLOORS THE INSTALLATION OF CONDUITS, BRANCH CIRCUIT WIRING AND EMERGENCY LIGHTS WITHOUT A PERMIT ON... | $0 | $0 | Apr 12, 2023 |
| Feb 1, 2023 | 39079734R | RESOLVE | CLASS - 2 | OBSERVED: AT CELLAR LEVEL, EXIT DOORS, ILLEGAL HARDWARE WAS INSTALLED BLOCKING EASY EVACUATION IN EMERGENCY CASE, PRO... | $312 | $0 | Sep 11, 2023 |
| Feb 1, 2023 | 39079005R | RESOLVE | CLASS - 2 | I OBSERVED IN THE BASEMENT MAINTENANCE STORAGE ROOM FAILURE TO TERMINATE BX CABLING TO JUNCTION AND OUTLET ALSO THE W... | $600 | $0 | Sep 11, 2023 |
| Feb 1, 2023 | 39079006Z | RESOLVE | CLASS - 2 | I OBSERVED THROUGHOUT THE BASEMENT THE IMPROPER SUPPORT OF CONDUITS AND CABLE ASSEMBLIES WITH BAND-IRON. THIS IS NOT ... | $2,000 | $0 | Sep 11, 2023 |
| Feb 1, 2023 | 39079003N | RESOLVE | CLASS - 2 | I OBSERVED ON ALL FLOORS THE FAILURE TO USE A JUNCTION BOX TO INSTALL POWER TO THE NEW EMERGENCY LIGHTS, THE USE OF T... | $0 | $0 | May 8, 2023 |
| Mar 11, 2022 | 35644272P | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING.OBSERVED:AT ROOF LEVEL AND FIRST FLOOR EXITDOORS DO NOT ALLOW EASY ESCAPE FROM BUILDING IN... | $312 | $0 | Aug 10, 2022 |
| Mar 11, 2022 | 35644273R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:LACK OF EMERGENCY LIGHTING FOR EXITS,EXIT DISCHARGES AND PUBLIC... | $0 | $0 | Nov 15, 2022 |
| Jan 18, 2018 | 35282662P | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #35287037M ISSUED 07/26/17 AND TO FILE... | $0 | $0 | May 15, 2018 |
| Nov 25, 2017 | 35281225M | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION #35287037M ISSUED ON 07/26/17 AND TO FI... | $0 | $0 | Apr 18, 2018 |
| Oct 31, 2017 | 35274256J | RESOLVE | CLASS - 1 | UNLAWFUL ACTS FAILURE TO COMPLY /AN ORDER OF THE COMMISSIONER.RECORDS INDICATE NO APPL WAS MADE TO CORRECT & CERTIFY ... | $2,400 | $0 | Mar 5, 2018 |
| Oct 12, 2017 | 35279820Y | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35287037M ISSUED ON 07/26/17 & TO FILE A C OF C PURSUAN... | $0 | $0 | Apr 5, 2018 |
| Jul 26, 2017 | 35287038Y | RESOLVE | CLASS - 1 | FAILURE TO HAVE NEW CR LATERED PLUMBING SYSTEM TESTED-INSTALLED THROUGHOUT BASEMENT.NEW 4"-3"-2" NO HUB DRAINAGE /(MT... | $1,000 | $0 | Apr 3, 2018 |
| Jul 26, 2017 | 35286722X | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE ADEQUATE CIRCUIT OVERCURRENT PROTECTION DEVICE PER TABLE. OBSERVED IN BASEMENT @ MAIN ELECTRICAL D... | $4,800 | $0 | Jan 23, 2018 |
| Jul 26, 2017 | 35287039X | RESOLVE | CLASS - 1 | MISC VIOLATION INSTALLED ON BOILER GAS LINE RUNNING(THROUGHOUT COPL). PROHIBITED FITTING IMPROPER GAS SUPPORTS AND GA... | $0 | $0 | Mar 7, 2018 |
| Jul 26, 2017 | 35287037M | RESOLVE | CLASS - 1 | WORK NO PERMIT.OBSERVED IN BST THROUGHOUT NEW 4"-3"-2" GAS HOUSE PIPING THROUGHOUT FOR COOKING ALL FLOORS.NOT PART OF... | $0 | $0 | Apr 4, 2018 |
| Jul 26, 2017 | 35286723H | RESOLVE | CLASS - 2 | FAILURE TO INSTALL GROUND-FAULT CIRCUIT INTERRUPTER(GFCI)PROTECTION AS REQUIRED. RECEPTACLES IN BASEMENTS BOILER ROOM... | $0 | $0 | Mar 7, 2018 |
| Jul 26, 2017 | 35286721Y | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS. OBSERVED IN BASEMENT @ WATER MAIN: MAIN GROUNDING CONDUCTOR FOR BLDGS ELECTRICA... | $1,200 | $0 | Jan 22, 2018 |
| Mar 31, 2016 | 35177399M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG CODE COMPLIANT. NO FIRESTOPPING PER BC 712.3;27-345. NOTED: AT CELLAR GAS AND ELECTRIC METER... | $250 | -$250 | May 16, 2016 |